Toshiba MMK-AP0122H New check code, Difference between the new check code and the current system

Page 27

New check code

1. Difference between the new check code and the current system

The displaying method of the check code changes in this model and after.

 

Check code in current system

New check code

 

 

 

Used characters

Hexadecimal notation, 2 digits

Alphabet + Decimal notation, 2 digits

 

 

 

Characteristics of code classification

Few classification of communication/incorrect setup system

Many classification of communication/incorrect setup system

 

 

 

Block display

Indoor P.C. board, Outdoor P.C. board, Cycle, Communication

Communication/Incorrect setup (4 ways), Indoor protection,

Outdoor protection, Sensor, Compressor protection, etc.

 

 

 

 

 

<Display on wired remote controller>

[] goes on.

[UNIT No.] + Check code + Operation lamp (Green) flash

<Display on sensor part of wireless>

• Block display of combination of [] [] []

<Display on indicater on wireless remote controller receiver part>

Unit No. and check code are displayed.

In a case of error with auxiliary code, check code and auxiliary code are displayed alternately.

→

Display

Classification

 

 

A

Unused

 

 

C

Central control system error

 

 

E

Communication system error

 

 

F

Each sensor error (Failure)

 

 

H

Compressor protective system error

 

 

J

Unused

 

 

L

Setup error, Other errors

 

 

P

Protective device operation

 

 

24

Image 27
Contents MMK-AP0072H, MMK-AP0092H, MMK-AP0122H Adoption of NEW Refrigerant Contents Others Separate sold partsRefrigerant piping Precautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Precautions for Safety Selection of Installation PlaceInstallation space Installation diagram of Indoor and outdoor unitsInstallation place Installation of Indoor Unit Selection of Installation PlaceRemote controller Mounting the installation plate When the installation plate is directly mounted on the wallCutting a hole Piping and drain hose forming Piping and Drain Hose InstallationCase of right or left piping Case of bottom right or bottom left pipingLeft- hand connection with piping Drainage Indoor Unit FixingPipe Forming/End Positioning Piping material and dimensionsRefrigerant Piping Permissible pipe length and permissible height differenceOpen fully valves of the outdoor unit Gas leak check Refrigerant PipingConnection of refrigerant pipe Airtight test/Air purge, etcElectric Work Power supply specificationsElectric Work Wiring connectionHow to connect the wiring of flow selector unit Wiring connection for flow selector unitWiring diagram Remote controller wiringWiring between indoor and outdoor units Address setupExchange of applicable control setup Basic operation procedure for setup exchangeApplicable Controls To secure better effect of heating Adjustment of air directionApplicable Controls Change of lighting time of filter signBefore test operation How to execute test operationCase of wired remote controller Test RUNCheck wiring/piping of indoor and outdoor units Check transmission of remote controllerTest RUN Troubleshooting Confirmation of error historyConfirmation and check Terminology TroubleshootingCheck code list Check methodRemote Indication Auxiliary code Error detected by TCC-LINK central control deviceDifference between the new check code and the current system New check codeCheck of Concentration Limit Indoor unit setup check sheet Confirmation of Indoor Unit Setup