11 TEST RUN

Before test operation

WARNING

• Before turning on the power supply, carry out the following items.

1) Using 500V-megger, check there is 1Mor more between the terminal block of the power supply and the earth. If 1Mor less is detected, do not run the unit.

2) Check that all the valves of the outdoor unit are fully opened.

To protect the compressor at starting time, keep power-ON condition before 12 hours or more.

Never push the electromagnetic contactor to carry out a forced test operation. (It is very dangerous because a protective device does not work.)

How to execute test operation

Using the remote controller, check the operation in the usual operation. For the operation procedure, refer to the attached Owner’s Manual.

A forced test operation can be executed in the following procedure under condition of thermo-OFF of room temperature.

In order to prevent a serial operation, the forced test operation is released after 60 minutes and returns to the usual operation.

NOTE

Do not use a forced operation in cases other than test operation because it applies an excessive load to the air conditioner.

In case of wired remote controller

1, 5

2, 4

3

UNIT

SET CL

Procedure

 

 

Description

1

Keep

button pushed for 4 seconds or more. [TEST] is displayed

on the display part and the selection of mode in the test mode is

 

 

permitted.

 

TEST

2

Push

button.

 

 

Using

button, select the operation mode, [COOL] or [HEAT].

3

• Do not run the air conditioner in a mode other than [COOL] or [HEAT].

• The temperature controlling function does not work during test

 

operation.

 

 

• The detection of error is performed as usual.

4

After the test operation, push

button to stop the operation.

(Display part is same as procedure 1 )

 

 

 

5

Push

button to cancel (release from) the test operation mode.

([TEST] disappears on the display part and the status returns to a

 

normal stop status.)

 

18

Image 21
Contents MMK-AP0072H, MMK-AP0092H, MMK-AP0122H Adoption of NEW Refrigerant Contents Others Separate sold partsRefrigerant piping Precautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Precautions for Safety Selection of Installation PlaceInstallation space Installation diagram of Indoor and outdoor unitsInstallation place Installation of Indoor Unit Selection of Installation PlaceRemote controller Mounting the installation plate When the installation plate is directly mounted on the wallCutting a hole Piping and drain hose forming Piping and Drain Hose InstallationCase of right or left piping Case of bottom right or bottom left pipingLeft- hand connection with piping Drainage Indoor Unit FixingRefrigerant Piping Piping material and dimensionsPermissible pipe length and permissible height difference Pipe Forming/End PositioningConnection of refrigerant pipe Refrigerant PipingAirtight test/Air purge, etc Open fully valves of the outdoor unit Gas leak checkElectric Work Power supply specificationsElectric Work Wiring connectionHow to connect the wiring of flow selector unit Wiring connection for flow selector unitWiring between indoor and outdoor units Remote controller wiringAddress setup Wiring diagramExchange of applicable control setup Basic operation procedure for setup exchangeApplicable Controls Applicable Controls Adjustment of air directionChange of lighting time of filter sign To secure better effect of heatingCase of wired remote controller How to execute test operationTest RUN Before test operationCheck wiring/piping of indoor and outdoor units Check transmission of remote controllerTest RUN Troubleshooting Confirmation of error historyConfirmation and check Check code list TroubleshootingCheck method TerminologyRemote Indication Auxiliary code Error detected by TCC-LINK central control deviceDifference between the new check code and the current system New check codeCheck of Concentration Limit Indoor unit setup check sheet Confirmation of Indoor Unit Setup