8 REFRIGERANT PIPING

• Projection margin in flaring :

B

B (Unit : mm)

 

Rigid (Clutch type)

Outer diam. of

R410A tool used

Conventional tool used

 

 

 

 

copper pipe

R410A

R22

R410A

R22

 

 

 

 

 

 

6.4

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

9.5

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

12.7

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

15.9

0 to 0.5

(Same as left)

1.0 to 1.5

0.5 to 1.0

 

 

 

 

 

Imperial (Wing nut type)

Outer diam. of copper pipe

R410A

R22

 

 

 

6.4

1.5 to 2.0

1.0 to 1.5

 

 

 

9.5

1.5 to 2.0

1.0 to 1.5

 

 

 

12.7

2.0 to 2.5

1.5 to 2.0

 

 

 

15.9

2.0 to 2.5

1.5 to 2.0

 

 

 

Connection of refrigerant pipe

Connect all the refrigerant pipes with flare connecting work.

Since the atmospheric pressure only is sealed as the sealing gas, it is not abnormal that “Pushu…” sound is not heard when the flare nut is removed.

Be sure to use a double spanner for pipe connecting work of the indoor unit.

Work using double spanner

• Refer to the following table for tightening torque.

Connecting pipe

Tightening torque

Re-tightening

outer dia. (mm)

(N•m)

torque (N•m)

 

 

 

Ø6.4

14 to 18

18

(1.4 to 1.8 kgf•m)

(1.8 kgf•m)

 

 

 

 

Ø9.5

33 to 42

42

(3.3 to 4.2 kgf•m)

(4.2 kgf•m)

 

 

 

 

Ø12.7

50 to 62

50

(5.0 to 6.2 kgf•m)

(5.0 kgf•m)

 

 

 

 

Ø15.9

68 to 82

68

(6.8 to 8.2 kgf•m)

(6.8 kgf•m)

 

 

 

 

Airtight test/Air purge, etc.

For airtight test, air purge, addition of refrigerant, and gas leak check, follow the Installation Manual attached to the outdoor unit.

Open fully valves of the outdoor unit

Gas leak check

Check with a leak detector or soap water whether gas leaks or not, from the pipe connecting section or cap of the valve.

REQUIREMENT

Use a leak detector manufactured exclusively for HFC refrigerant (R410A, R134a, etc.).

11

Image 14
Contents MMK-AP0072H, MMK-AP0092H, MMK-AP0122H Adoption of NEW Refrigerant Contents Refrigerant piping OthersSeparate sold parts To Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation Selection of Installation Place Precautions for SafetyInstallation place Installation spaceInstallation diagram of Indoor and outdoor units Remote controller Installation of Indoor UnitSelection of Installation Place Cutting a hole Mounting the installation plateWhen the installation plate is directly mounted on the wall Piping and Drain Hose Installation Piping and drain hose formingLeft- hand connection with piping Case of right or left pipingCase of bottom right or bottom left piping Indoor Unit Fixing DrainagePermissible pipe length and permissible height difference Piping material and dimensionsRefrigerant Piping Pipe Forming/End PositioningAirtight test/Air purge, etc Refrigerant PipingConnection of refrigerant pipe Open fully valves of the outdoor unit Gas leak checkPower supply specifications Electric WorkWiring connection Electric WorkWiring connection for flow selector unit How to connect the wiring of flow selector unitAddress setup Remote controller wiringWiring between indoor and outdoor units Wiring diagramApplicable Controls Exchange of applicable control setupBasic operation procedure for setup exchange Change of lighting time of filter sign Adjustment of air directionApplicable Controls To secure better effect of heatingTest RUN How to execute test operationCase of wired remote controller Before test operationTest RUN Check wiring/piping of indoor and outdoor unitsCheck transmission of remote controller Confirmation and check TroubleshootingConfirmation of error history Check method TroubleshootingCheck code list TerminologyRemote Error detected by TCC-LINK central control device Indication Auxiliary codeNew check code Difference between the new check code and the current systemCheck of Concentration Limit Confirmation of Indoor Unit Setup Indoor unit setup check sheet