Toshiba MMK-AP0092H, MMK-AP0122H, MMK-AP0072H Wiring connection for flow selector unit

Page 17

Tighten the screws of the terminal block, and fix the cables with cord clamp attached to the electric parts box.

(Do not apply tension to the connecting section of the terminal block.)

L

N

U1 U2 A

B

L

N

U1 U2 A

B

R(L) S(N)

>ABS<

Cord clamp

 

Cord clamp

 

Remote

L N

controller cable

 

Power supply

 

cable

 

 

 

 

10mm

10mm

Notch

110mm

Terminal block

40mm

Screw

Connector cover

 

Wiring connection for flow selector unit

How to connect the wiring of flow selector unit

For the flow selector unit that have power supply cord, connect a power supply cable to it as mentioned below.

1.Open the air inlet grille upward.

2.Remove the four screws securing the front panel.

3.Slightly open the lower part of the front panel then pull the upper part of the front panel toward you to remove it from the rear plate.

4.After removing the front panel, remove the wiring cover and the cord clamp.

5.Connect and secure the power supply cable of flow selector unit and secure the cord clamp.

6.The control wires are included in terminal block part of the power supply. Take out the control wires outwards through the slit of the terminal block.

7.Fasten the wiring cover surely with screws.

8.Connect the control wire taken out through the slit on the terminal block and the control wire from the flow selector unit at the relay terminal section.

 

 

Earth line

 

 

 

Terminal

 

 

 

block

Cord clamp

 

Terminal

 

Screw

 

block

 

 

 

 

 

 

 

Screw

 

 

 

Screw

Control wire

Control wire from

 

 

the flow selector

Power supply cable

 

 

 

 

 

 

 

Slit of the

for flow selector unit

 

 

terminal block

Wiring cover

 

 

14

Image 17
Contents MMK-AP0072H, MMK-AP0092H, MMK-AP0122H Adoption of NEW Refrigerant Contents Refrigerant piping OthersSeparate sold parts To Disconnect the Appliance from Main Power Supply Precautions for SafetyNew Refrigerant Air Conditioner Installation Precautions for Safety Selection of Installation PlaceInstallation place Installation spaceInstallation diagram of Indoor and outdoor units Remote controller Installation of Indoor UnitSelection of Installation Place Cutting a hole Mounting the installation plateWhen the installation plate is directly mounted on the wall Piping and drain hose forming Piping and Drain Hose InstallationLeft- hand connection with piping Case of right or left pipingCase of bottom right or bottom left piping Drainage Indoor Unit FixingRefrigerant Piping Piping material and dimensionsPermissible pipe length and permissible height difference Pipe Forming/End PositioningConnection of refrigerant pipe Refrigerant PipingAirtight test/Air purge, etc Open fully valves of the outdoor unit Gas leak checkElectric Work Power supply specificationsElectric Work Wiring connectionHow to connect the wiring of flow selector unit Wiring connection for flow selector unitWiring between indoor and outdoor units Remote controller wiringAddress setup Wiring diagramApplicable Controls Exchange of applicable control setupBasic operation procedure for setup exchange Applicable Controls Adjustment of air directionChange of lighting time of filter sign To secure better effect of heatingCase of wired remote controller How to execute test operationTest RUN Before test operationTest RUN Check wiring/piping of indoor and outdoor unitsCheck transmission of remote controller Confirmation and check TroubleshootingConfirmation of error history Check code list TroubleshootingCheck method TerminologyRemote Indication Auxiliary code Error detected by TCC-LINK central control deviceDifference between the new check code and the current system New check codeCheck of Concentration Limit Indoor unit setup check sheet Confirmation of Indoor Unit Setup