9 ELECTRIC WORK

WARNING

1.Using the specified wires, ensure to connect the wires, and fix wires securely so that the external strength of the wires do not transmit to the connecting part of the terminals.

Incomplete connection or fixation may cause a fire, etc.

2.Be sure to connect earth wire. (Grounding work)

Do not connect the earth wire to gas pipe, city water pipe, lightning rod, or the earth wire of telephone. Incomplete grounding causes an electric shock.

3.For electric work, strictly follow to the Local Regulation in each country and the Installation Manual, and use an exclusive circuit.

Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.

CAUTION

Be sure to install an earth leakage breaker.

If an earth leakage breaker is not installed, an electric shock may be caused.

REQUIREMENT

For power supply wiring, strictly conform to the Local Regulation in each country.

For wiring of power supply of the outdoor units, follow to the Installation Manual of each outdoor unit.

Never connect 220–240V power to the terminal blocks (A, B, U1, U2, X, Y, etc.) for control wiring. (Otherwise, the system will be failed.)

Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe. The coating may melt resulted in an accident.

After connecting wires to the terminal blocks, provide a trap and fix wires with the wire clamp.

Store the refrigerant piping line and control wiring line in the same line.

Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.

Power supply specifications

Cables and remote controller wires are procured locally.

For the power supply specifications, follow to the table below. If capacity is little, it is dangerous because overheat or seizure may be caused.

For specifications of the power capacity of the outdoor unit and the power supply cables, refer to the Installation Manual attached to the outdoor unit.

 

Power supply

220–240V ~ 50Hz

 

220V ~ 60Hz

Indoor unit power supply (*1)

Power supply switch/Earth leakage breaker or power supply wiring/fuse rating for

 

indoor units should be selected by the accummulated total current values of the indoor units.

 

 

 

 

 

Power supply wiring

20m or less

Twist wire : 2.0 mm²

 

50m or less

Twist wire : 2.5 mm²

 

 

 

 

 

 

 

 

Q’ty

2

 

Indoor/Outdoor inter-unit wiring (*2)

 

 

 

Wire size

(Up to 1000m) Twist wire : 1.25 mm²

 

 

(Up to 2000m) Twist wire : 2.00 mm²

 

 

 

 

 

 

 

Communication line

 

Q’ty

2

Central control line wiring (*3)

Wire size

(Up to 1000m) Twist wire : 1.25 mm²

 

 

(Up to 2000m) Twist wire : 2.00 mm²

 

 

 

 

Remote controller wiring (*4)

Q’ty

2

 

 

 

 

Wire size

Twist wire : 0.5 to 2.0 mm²

 

 

 

 

 

 

12

Image 15
Contents MMK-AP0072H, MMK-AP0092H, MMK-AP0122H Adoption of NEW Refrigerant Contents Others Separate sold partsRefrigerant piping Precautions for Safety New Refrigerant Air Conditioner InstallationTo Disconnect the Appliance from Main Power Supply Precautions for Safety Selection of Installation PlaceInstallation space Installation diagram of Indoor and outdoor unitsInstallation place Installation of Indoor Unit Selection of Installation PlaceRemote controller Mounting the installation plate When the installation plate is directly mounted on the wallCutting a hole Piping and drain hose forming Piping and Drain Hose InstallationCase of right or left piping Case of bottom right or bottom left pipingLeft- hand connection with piping Drainage Indoor Unit FixingPipe Forming/End Positioning Piping material and dimensionsRefrigerant Piping Permissible pipe length and permissible height differenceOpen fully valves of the outdoor unit Gas leak check Refrigerant PipingConnection of refrigerant pipe Airtight test/Air purge, etcElectric Work Power supply specificationsElectric Work Wiring connectionHow to connect the wiring of flow selector unit Wiring connection for flow selector unitWiring diagram Remote controller wiringWiring between indoor and outdoor units Address setupExchange of applicable control setup Basic operation procedure for setup exchangeApplicable Controls To secure better effect of heating Adjustment of air directionApplicable Controls Change of lighting time of filter signBefore test operation How to execute test operationCase of wired remote controller Test RUNCheck wiring/piping of indoor and outdoor units Check transmission of remote controllerTest RUN Troubleshooting Confirmation of error historyConfirmation and check Terminology TroubleshootingCheck code list Check methodRemote Indication Auxiliary code Error detected by TCC-LINK central control deviceDifference between the new check code and the current system New check codeCheck of Concentration Limit Indoor unit setup check sheet Confirmation of Indoor Unit Setup