9 ELECTRIC WORK

Indoor unit power supply

(*1)

For the power supply of the indoor unit, prepare the exclusive power supply separated from that of the outdoor unit.

Arrange the power supply, earth leakage breaker, and main switch of the indoor unit connected to the same outdoor unit so that they are commonly used.

Power supply cord specification : Cable 3-core 2.5mm², in conformity with Design 60245 IEC 57.

Indoor/Outdoor inter-unit wiring, Central controller wiring

(*2) (*3)

2-core with polarity wires are used for the Indoor/Outdoor inter-unit wiring and Central controller wiring.

To prevent noise trouble, use 2-core shield wire.

The length of the communication line means the total length of the inter-unit wire length between indoor and outdoor units added with the central control system wire length.

Remote controller wiring

(*4)

2-core with non-polarity wire is used for wiring of the remote controller wiring and group remote controllers wiring.

Remote controller wiring, remote

Twist wire: 0.5mm2

to 2.0mm2 × 2

controller inter-unit wiring

 

 

 

 

 

Total wire length of remote controller

In case of wired type only

Up to 500m

wiring and remote controller inter-unit

 

 

In case of wireless type included

Up to 400m

wiring = L + L1 + L2 + … Ln

 

 

 

Total wire length of remote controller inter-unit wiring = L1 + L2 + … Ln

Up to 200m

 

 

 

CAUTION

The remote controller wire (Communication line) and AC220–240V wires cannot be parallel to contact each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise, etc.

Remote controller wiring

Indoor unit

 

Indoor unit

 

Indoor unit

 

Indoor unit

 

 

 

 

 

 

 

 

L1

 

L2

Ln

Remote

Remote controller inter-unit wiring

(Max. 8 units)

controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Wiring connection

How to connect the power cable

For the air conditioner that does not have power cable, connect a power cable to it as mentioned below.

1.Open the air inlet grille upward.

2.Remove the four screws securing the front panel.

3.Slightly open the lower part of the front panel then pull the upper part of the front panel toward you to remove it from the rear plate.

4.After removing the front panel, remove the power cable connect cover and the cord clamp.

5.Connect and secure the power supply cable and secure the cord clamp and the power connect cover.

6.Cut the slit and front panel, and put the power supply cable through the notch.

7.Be sure to smooth the notch with a file, etc.

Air inlet grille

Front panel

REQUIREMENT

Be sure to pass the cable through the cable connection port of the indoor unit.

The low-voltage circuit is provided for the remote controller.

2

1

 

3

13

Image 16
Contents MMK-AP0072H, MMK-AP0092H, MMK-AP0122H Adoption of NEW Refrigerant Contents Separate sold parts OthersRefrigerant piping New Refrigerant Air Conditioner Installation Precautions for SafetyTo Disconnect the Appliance from Main Power Supply Selection of Installation Place Precautions for SafetyInstallation diagram of Indoor and outdoor units Installation spaceInstallation place Selection of Installation Place Installation of Indoor UnitRemote controller When the installation plate is directly mounted on the wall Mounting the installation plateCutting a hole Piping and Drain Hose Installation Piping and drain hose formingCase of bottom right or bottom left piping Case of right or left pipingLeft- hand connection with piping Indoor Unit Fixing DrainagePiping material and dimensions Refrigerant PipingPermissible pipe length and permissible height difference Pipe Forming/End PositioningRefrigerant Piping Connection of refrigerant pipeAirtight test/Air purge, etc Open fully valves of the outdoor unit Gas leak checkPower supply specifications Electric WorkWiring connection Electric WorkWiring connection for flow selector unit How to connect the wiring of flow selector unitRemote controller wiring Wiring between indoor and outdoor unitsAddress setup Wiring diagramBasic operation procedure for setup exchange Exchange of applicable control setupApplicable Controls Adjustment of air direction Applicable ControlsChange of lighting time of filter sign To secure better effect of heatingHow to execute test operation Case of wired remote controllerTest RUN Before test operationCheck transmission of remote controller Check wiring/piping of indoor and outdoor unitsTest RUN Confirmation of error history TroubleshootingConfirmation and check Troubleshooting Check code listCheck method TerminologyRemote Error detected by TCC-LINK central control device Indication Auxiliary codeNew check code Difference between the new check code and the current systemCheck of Concentration Limit Confirmation of Indoor Unit Setup Indoor unit setup check sheet