TABLE 8: DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
| UNIT DESCRIPTION / MODEL | 
 | 
 | 
 | DY048 / 4 Ton | 
 | 
 | 
 | ||
| CONFIGURATION | 
 | 
 | 
 | Horizontal Ducted Inlet | 
 | 
 | 
 | ||
| Indoor Blower Speed (RPM) | 766 | 769 | 1077 | 1087 | |||||
| Blower Static Pressure (IWG) | 0.2 | 0.5 | 0.4 | 1.0 | |||||
| Airflow (CFM) | 1484 | 993 | 2270 | 1406 | |||||
| Blower Motor BHP | 0.67 | 0.54 | 1.24 | 0.90 | |||||
| 
 | ID Blower | Cooling | ID Blower | Cooling | ID Blower | 
 | Cooling | ID Blower | Cooling | 
| Octave Center Freq. | Operation2 | Operation2 | 
 | Operation2 | Operation2 | ||||
| 
 | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | 
 | (dB) | Only (dB) | (dB) | 
| 
 | 
 | 
 | 
 | 
 | 
 | ||||
| 63 | 74 | 97 | 74 | 95 | 77 | 
 | 90 | 77 | 90 | 
| 125 | 70 | 86 | 69 | 86 | 73 | 
 | 78 | 72 | 77 | 
| 250 | 53 | 58 | 52 | 57 | 60 | 
 | 61 | 58 | 61 | 
| 500 | 49 | 55 | 47 | 54 | 54 | 
 | 56 | 51 | 53 | 
| 1000 | 42 | 42 | 38 | 39 | 50 | 
 | 55 | 45 | 45 | 
| 2000 | 40 | 44 | 38 | 43 | 48 | 
 | 51 | 45 | 46 | 
| 4000 | 38 | 44 | 36 | 41 | 48 | 
 | 52 | 43 | 45 | 
| 8000 | 42 | 43 | 42 | 44 | 45 | 
 | 48 | 44 | 45 | 
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 9: DY048 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
| UNIT DESCRIPTION / MODEL | 
 | 
 | 
 | DY048 / 4 Ton | 
 | 
 | 
 | |
| CONFIGURATION | 
 | 
 | Horizontal Ducted Discharge | 
 | 
 | |||
| Indoor Blower Speed (RPM) | 766 | 769 | 1077 | 1087 | ||||
| Blower Static Pressure (IWG) | 0.2 | 0.5 | 0.4 | 1.0 | ||||
| Airflow (CFM) | 1484 | 993 | 2270 | 1406 | ||||
| Blower Motor BHP | 0.67 | 0.54 | 1.24 | 0.90 | ||||
| 
 | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | 
| Octave Center Freq. | Operation2 | Operation2 | Operation2 | Operation2 | ||||
| 
 | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | 
| 
 | 
 | 
 | 
 | 
 | ||||
| 63 | 77 | 97 | 75 | 95 | 84 | 91 | 82 | 91 | 
| 125 | 72 | 86 | 69 | 85 | 81 | 83 | 78 | 80 | 
| 250 | 60 | 62 | 57 | 59 | 71 | 71 | 66 | 67 | 
| 500 | 53 | 56 | 49 | 54 | 60 | 61 | 55 | 56 | 
| 1000 | 47 | 47 | 42 | 43 | 58 | 59 | 52 | 52 | 
| 2000 | 45 | 46 | 40 | 43 | 54 | 55 | 50 | 50 | 
| 4000 | 46 | 47 | 40 | 42 | 57 | 58 | 52 | 52 | 
| 8000 | 47 | 47 | 45 | 45 | 54 | 54 | 48 | 49 | 
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
| Johnson Controls Unitary Products | 11 |