343615-YTG-B-0308
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)
Filter Access |
|
|
Blower Motor Access |
|
|
Dot Plugs |
|
|
|
| |
Switch Location |
|
|
Mounting Bracket for |
|
|
Disconnect Switch | A,B |
|
(Field Supplied) |
| |
| Wiring Entry | Control Box Access |
| (See Detail “B”) |
Disconnect Switch Location and Motor Access Panel for Unit with
FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION TABLE 28: UTILITIES ENTRY
HOLE | OPENING SIZE (DIA.) | USED FOR |
| |
A | 7/8” KO1 | Control Wiring2 |
| Side |
| Bottom | |||
|
|
|
| |
|
|
|
|
|
B | 2” KO1 | Power Wiring |
| Side |
|
| |||
| Bottom | |||
|
|
|
| |
|
|
|
| |
C | Gas Piping (Front) | |||
D | Gas Piping (Bottom) | |||
|
|
|
|
|
1.Opening in the bottom to the unit can be located by the side in the insulation.
2.Do not remove the 2” knockout ring.
TABLE 29: MINIMUM CLEARANCES
LOCATION | CLEARANCE | |
Front | 24” (Cooling/Electric Heat) | |
32” (Gas Heat) | ||
| ||
|
| |
Rear | 12” (Less Economizer) | |
36” (With Economizer or Fixed | ||
| Air/Motorized Damper) | |
|
| |
Left Side (Filter Access) | 24” (Less Economizer) | |
36” (With Economizer) | ||
| ||
|
| |
Right Side (Cond. Coil) | 24” | |
Below Unit1 | 0” | |
Above Unit2 | 72” (For | |
Condenser Air Discharge) | ||
|
1.Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
2.Units must be installed outdoors. Overhanging struc- tures or shrubs should not obstruct condenser air dis- charge outlet.
28 | Johnson Controls Unitary Products |