| TABLE 14: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) | 
 | 
 | 
 | 
 | ||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | UNIT DESCRIPTION / MODEL | 
 | 
 | 
 | DY060 / 5 Ton | 
 | 
 | 
 | 
 | |
| 
 | CONFIGURATION | 
 | 
 | 
 | Vertical Ducted Inlet | 
 | 
 | 
 | 
 | |
| 
 | Indoor Blower Speed (RPM) | 834 | 840 | 1171 | 1194 | 
 | ||||
| 
 | Blower Static Pressure (IWG) | 0.2 | 0.6 | 0.2 | 1.3 | 
 | ||||
| 
 | Airflow (CFM) | 1525 | 1019 | 2624 | 1256 | 
 | ||||
| 
 | Blower Motor BHP | 0.61 | 0.44 | 1.43 | 0.83 | 
 | ||||
| 
 | 
 | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | 
 | 
| 
 | Octave Center Freq. | Operation2 | Operation2 | Operation2 | Operation2 | |||||
| 
 | 
 | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | |
| 
 | 
 | 
 | 
 | 
 | 
 | |||||
| 
 | 63 | 77 | 86 | 79 | 88 | 81 | 86 | 83 | 87 | 
 | 
| 
 | 125 | 69 | 70 | 70 | 72 | 71 | 73 | 72 | 72 | 
 | 
| 
 | 250 | 56 | 63 | 56 | 58 | 64 | 72 | 63 | 69 | 
 | 
| 
 | 500 | 50 | 52 | 48 | 49 | 57 | 59 | 53 | 56 | 
 | 
| 
 | 1000 | 48 | 51 | 44 | 45 | 57 | 58 | 49 | 52 | 
 | 
| 
 | 2000 | 43 | 47 | 39 | 41 | 54 | 57 | 47 | 50 | 
 | 
| 
 | 4000 | 47 | 49 | 40 | 41 | 55 | 61 | 47 | 52 | 
 | 
| 
 | 8000 | 46 | 47 | 44 | 45 | 51 | 57 | 47 | 49 | 
 | 
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 15: DY060 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
| UNIT DESCRIPTION / MODEL | 
 | 
 | 
 | DY060 / 5 Ton | 
 | 
 | 
 | |
| CONFIGURATION | 
 | 
 | Vertical Ducted Discharge | 
 | 
 | |||
| Indoor Blower Speed (RPM) | 834 | 840 | 1171 | 1194 | ||||
| Blower Static Pressure (IWG) | 0.2 | 0.6 | 0.2 | 1.3 | ||||
| Airflow (CFM) | 1525 | 1019 | 2624 | 1256 | ||||
| Blower Motor BHP | 0.61 | 0.44 | 1.43 | 0.83 | ||||
| 
 | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | 
| Octave Center Freq. | Operation2 | Operation2 | Operation2 | Operation2 | ||||
| 
 | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | 
| 
 | 
 | 
 | 
 | 
 | ||||
| 63 | 83 | 88 | 82 | 88 | 91 | 91 | 85 | 88 | 
| 125 | 78 | 78 | 75 | 76 | 85 | 85 | 79 | 79 | 
| 250 | 66 | 67 | 62 | 62 | 77 | 78 | 70 | 72 | 
| 500 | 59 | 60 | 54 | 54 | 70 | 70 | 61 | 61 | 
| 1000 | 57 | 58 | 51 | 51 | 68 | 68 | 57 | 58 | 
| 2000 | 51 | 52 | 45 | 45 | 62 | 63 | 52 | 53 | 
| 4000 | 54 | 54 | 47 | 47 | 65 | 66 | 55 | 56 | 
| 8000 | 52 | 52 | 46 | 47 | 65 | 66 | 52 | 53 | 
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.