York DY 060, DY 048 Capacity Ratings ARI 210/2401, GAS Heat RATINGS1, Stage GAS Heat Ratings

Page 8

ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.

BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work.

FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.

343615-YTG-B-0308

CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits.

COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.

HAIL GUARD - Hail Guard kit is available to prevent unit from hail damage. This is a sloped hood that fits above the coil.

GAS PIPING KIT - This kit supplies all necessary fittings and shut off valve.

TABLE 1: CAPACITY RATINGS - (ARI 210/240)1

MODEL

MBH

EER2

SEER3

 

SOUND

CFM

RATING

 

 

 

 

 

(Db)4

DY036

35.6

12

14

1200

84

DY048

46.0

12

14

1600

83

DY060

59.0

11.6

14

1750

81

1.80/67°F Indoor and 95°F outdoor.

2.EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).

3.SEER = Seasonal Energy Efficiency Ratio.

4.Rated in accordance with ARI 270 Standard.

TABLE 2: GAS HEAT RATINGS1

MODEL

MBH

MBH

AFUE

TEMP

INPUT

OUTPUT

(%)

RISE ºF

 

DY036N04

50

40

80.9

15 - 45

DY036N08

100

80

80.5

45 - 75

DY048N06

75

60

80.9

25 - 70

DY048N10

125

100

80.3

45 - 75

DY060N08

100

80

80.5

25 - 55

DY060N10

125

100

80.3

30 - 75

1. All units are single-stage heating.

TABLE 3: 2 STAGE GAS HEAT RATINGS

MODEL1

MBH INPUT

MBH OUTPUT

STEADY STATE EFFICIENCY

RISE

MINIMUM HEATING

1ST STAGE

2ND STAGE

1ST STAGE

2ND STAGE

1ST STAGE

2ND STAGE

MIN.

MAX.

AIRFLOW (CFM)

 

DY036D06

45

75

35.8

60.8

79.4

81.1

35

70

790

DY036D10

69

115

55.2

92

80.0

80.2

55

90

950

DY048D06

45

75

35.7

60.8

79.4

81.1

25

70

790

DY048D10

75

125

60.4

100.6

80.5

80.5

45

75

1230

DY060D06

45

75

35.8

60.8

79.4

81.1

20

55

1010

DY060D10

75

125

60.4

100.6

80.5

80.5

35

75

1230

1. Models are 3Ø only.

8

Johnson Controls Unitary Products

Image 8
Contents Warranty DescriptionTable of Contents Product Nomenclature Ton Sunline Magnum Model Number NomenclatureFeatures Unit Cutaway FACTORY-INSTALLED Options FIELD-INSTALLED Accessories Stage GAS Heat Ratings Capacity Ratings ARI 210/2401GAS Heat RATINGS1 Configuration Horizontal Ducted InletVertical Ducted Inlet DY048 / 4 Ton 791 794 1084 1095 DY060 / 5 Ton Vertical Ducted Inlet DY036 Cooling Capacities 3 TON MBHDY048 Cooling Capacities 4 TON DY060 Cooling Capacities 5 TON 1500MED Static Resistances Electric Heat CFM LimitationsMCA MCA1 YTG-B-0308 YTG-B-0308 Voltage LIMITATIONS1 DY Physical DataElectric Heat Correction Factors Typical Power Wiring Unit Dimensions 3 5 TON COOLING/GAS Heat Front View Detail a Unit Dimensions Rear View Minimum ClearancesTypical Applications Center of Gravity Unit TotalOperating Weights LBS Roof Curb DimensionsGuide Specifications Indoor Evaporator FAN AssemblyOutdoor Condenser FAN Assembly Unit CabinetUnit Operating Characteristics Unit ControlsGAS Heating Section Single or 2 Stage Electric Heating SectionManual Outdoor AIR Damper Other PRE-ENGINEERED Accessories AvailableElectric Heaters YTG-B-0308 Johnson Controls Unitary Products Johnson Controls Unitary Products York Drive Norman, OK