| TABLE 10: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED INLET) | 
 | 
 | 
 | 
 | ||||||
| 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | UNIT DESCRIPTION / MODEL | 
 | 
 | 
 | DY048 / 4 Ton | 
 | 
 | 
 | 
 | |
| 
 | CONFIGURATION | 
 | 
 | 
 | Vertical Ducted Inlet | 
 | 
 | 
 | 
 | |
| 
 | Indoor Blower Speed (RPM) | 791 | 794 | 1084 | 1095 | 
 | ||||
| 
 | Blower Static Pressure (IWG) | 0.2 | 0.5 | 0.2 | 1.0 | 
 | ||||
| 
 | Airflow (CFM) | 1408 | 1000 | 2336 | 1275 | 
 | ||||
| 
 | Blower Motor BHP | 0.54 | 0.42 | 1.12 | 0.73 | 
 | ||||
| 
 | 
 | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | 
 | 
| 
 | Octave Center Freq. | Operation2 | Operation2 | Operation2 | Operation2 | |||||
| 
 | 
 | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | |
| 
 | 
 | 
 | 
 | 
 | 
 | |||||
| 
 | 63 | 76 | 95 | 77 | 93 | 80 | 91 | 79 | 91 | 
 | 
| 
 | 125 | 68 | 84 | 67 | 82 | 76 | 84 | 73 | 80 | 
 | 
| 
 | 250 | 54 | 57 | 52 | 56 | 63 | 61 | 57 | 59 | 
 | 
| 
 | 500 | 48 | 53 | 46 | 53 | 54 | 57 | 50 | 53 | 
 | 
| 
 | 1000 | 43 | 44 | 40 | 41 | 52 | 52 | 47 | 47 | 
 | 
| 
 | 2000 | 40 | 43 | 38 | 42 | 49 | 51 | 44 | 46 | 
 | 
| 
 | 4000 | 38 | 43 | 36 | 40 | 49 | 54 | 43 | 45 | 
 | 
| 
 | 8000 | 43 | 43 | 43 | 43 | 45 | 47 | 44 | 44 | 
 | 
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 11: DY048 INDOOR SOUND POWER LEVELS (VERTICAL DUCTED DISCHARGE)
| UNIT DESCRIPTION / MODEL | 
 | 
 | 
 | DY048 / 4 Ton | 
 | 
 | 
 | |
| CONFIGURATION | 
 | 
 | Vertical Ducted Discharge | 
 | 
 | |||
| Indoor Blower Speed (RPM) | 791 | 794 | 1084 | 1095 | ||||
| Blower Static Pressure (IWG) | 0.2 | 0.5 | 0.2 | 1.0 | ||||
| Airflow (CFM) | 1408 | 1000 | 2336 | 1275 | ||||
| Blower Motor BHP | 0.54 | 0.42 | 1.12 | 0.73 | ||||
| 
 | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | 
| Octave Center Freq. | Operation2 | Operation2 | Operation2 | Operation2 | ||||
| 
 | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | 
| 
 | 
 | 
 | 
 | 
 | ||||
| 63 | 78 | 95 | 77 | 93 | 85 | 92 | 82 | 91 | 
| 125 | 73 | 84 | 72 | 82 | 84 | 87 | 78 | 82 | 
| 250 | 56 | 58 | 53 | 56 | 68 | 68 | 60 | 61 | 
| 500 | 51 | 54 | 48 | 53 | 61 | 62 | 54 | 55 | 
| 1000 | 46 | 46 | 43 | 44 | 57 | 57 | 50 | 50 | 
| 2000 | 42 | 44 | 38 | 42 | 53 | 54 | 46 | 48 | 
| 4000 | 43 | 45 | 39 | 41 | 55 | 57 | 49 | 50 | 
| 8000 | 44 | 44 | 43 | 43 | 52 | 52 | 46 | 47 | 
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
| 12 | Johnson Controls Unitary Products |