York DY 060, DY 048 DY Physical Data, Electric Heat Correction Factors, Voltage LIMITATIONS1

Page 24

343615-YTG-B-0308

TABLE 25: DY PHYSICAL DATA

 

MODELS

 

DY

 

 

036

048

060

 

 

EVAPORATOR

Centrifugal Blower (Dia. x Wd. in.)

12 X 10

12 X 10

12 X 10

BLOWER

Fan Motor HP (Direct Drive)

3/4

1

1

 

 

 

 

 

EVAPORATOR

Rows Deep

3

4

4

 

 

 

 

Fins Per Inch

13

13

13

COIL

 

 

 

 

Face Area (Ft.2)

5.1

5.1

5.1

 

CONDENSER

Propeller Dia. (in.)

24

24

24

 

 

 

 

Fan Motor HP

1/2

1/2

1/2

FANS

 

 

 

 

Nom. CFM

4200

4200

4200

 

 

 

 

 

 

CONDENSER

Rows Deep

2

2

2

 

 

 

 

Fins Per Inch

18

18

18

COILS

 

 

 

 

Face Area (Ft.2)

17.1

17.1

17.1

 

COMPRESSOR

Quantity

1

1

1

 

 

 

 

Type

Recip.

Recip.

Scroll

 

 

 

 

 

 

AIR

Quantity Per Unit (15” X 20” X 1” or 2“)

2

2

2

 

 

 

 

Quantity Per Unit (14” X 25” X 1” or 2“)

1

1

1

FILTERS

 

 

 

 

Total Face Area (Ft.2)

6.3

6.3

6.3

 

CHARGE

Refrigerant 22 (lbs./oz.)

9/4

9/8

11/8

TABLE 26: ELECTRIC HEAT CORRECTION FACTORS

NOMINAL VOLTAGE

VOLTAGE

kW CAP. MULTI-

PLIER

 

 

208

208

1.00

 

 

 

240

230

0.92

480

460

0.92

600

575

0.92

TABLE 27: VOLTAGE LIMITATIONS1

POWER SUPPLY

 

VOLTAGE

 

 

 

 

MIN.

 

MAX.

208/230-1-60

187

 

252

 

 

 

 

208/230-3-60

187

 

252

 

 

 

 

460-3-60

432

 

504

575-3-60

540

 

630

1.Utilization Range “A” in accordance with ARI Standard 110.

24

Johnson Controls Unitary Products

Image 24
Contents Warranty DescriptionTable of Contents Product Nomenclature Ton Sunline Magnum Model Number NomenclatureFeatures Unit Cutaway FACTORY-INSTALLED Options FIELD-INSTALLED Accessories Capacity Ratings ARI 210/2401 GAS Heat RATINGS1Stage GAS Heat Ratings Configuration Horizontal Ducted InletVertical Ducted Inlet DY048 / 4 Ton 791 794 1084 1095 DY060 / 5 Ton Vertical Ducted Inlet DY036 Cooling Capacities 3 TON MBHDY048 Cooling Capacities 4 TON DY060 Cooling Capacities 5 TON 1500MED Static Resistances Electric Heat CFM LimitationsMCA MCA1 YTG-B-0308 YTG-B-0308 DY Physical Data Electric Heat Correction FactorsVoltage LIMITATIONS1 Typical Power Wiring Unit Dimensions 3 5 TON COOLING/GAS Heat Front View Detail a Unit Dimensions Rear View Minimum ClearancesTypical Applications Center of Gravity Unit TotalOperating Weights LBS Roof Curb DimensionsGuide Specifications Indoor Evaporator FAN AssemblyOutdoor Condenser FAN Assembly Unit CabinetUnit Operating Characteristics Unit ControlsGAS Heating Section Single or 2 Stage Electric Heating SectionOther PRE-ENGINEERED Accessories Available Electric HeatersManual Outdoor AIR Damper YTG-B-0308 Johnson Controls Unitary Products Johnson Controls Unitary Products York Drive Norman, OK