TABLE 4: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED INLET)
UNIT DESCRIPTION / MODEL |
|
|
| DY036 / 3 Ton |
|
|
| ||
CONFIGURATION |
|
|
| Horizontal Ducted Inlet |
|
|
| ||
Indoor Blower Speed (RPM) | 630 | 631 | 879 | 885 | |||||
Blower Static Pressure (IWG) | 0.2 | 0.3 | 0.2 | 0.7 | |||||
Airflow (CFM) | 1116 | 928 | 1979 | 1020 | |||||
Blower Motor BHP | 0.41 | 0.37 | 0.76 | 0.53 | |||||
| ID Blower | Cooling | ID Blower | Cooling | ID Blower |
| Cooling | ID Blower | Cooling |
Octave Center Freq. | Operation2 | Operation2 |
| Operation2 | Operation2 | ||||
| Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) |
| (dB) | Only (dB) | (dB) |
|
|
|
|
|
| ||||
63 | 80 | 82 | 80 | 82 | 78 |
| 83 | 81 | 85 |
125 | 76 | 77 | 76 | 77 | 82 |
| 83 | 81 | 82 |
250 | 56 | 59 | 56 | 60 | 60 |
| 61 | 58 | 60 |
500 | 50 | 50 | 49 | 50 | 54 |
| 54 | 51 | 52 |
1000 | 40 | 43 | 39 | 42 | 49 |
| 50 | 44 | 45 |
2000 | 41 | 42 | 40 | 42 | 49 |
| 49 | 43 | 44 |
4000 | 41 | 41 | 41 | 41 | 49 |
| 49 | 41 | 41 |
8000 | 45 | 45 | 45 | 45 | 47 |
| 47 | 45 | 45 |
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
TABLE 5: DY036 INDOOR SOUND POWER LEVELS (HORIZONTAL DUCTED DISCHARGE)
UNIT DESCRIPTION / MODEL |
|
|
| DY036 / 3 Ton |
|
|
| |
CONFIGURATION |
|
| Horizontal Ducted Discharge |
|
| |||
Indoor Blower Speed (RPM) | 630 | 631 | 879 | 885 | ||||
Blower Static Pressure (IWG) | 0.2 | 0.3 | 0.2 | 0.7 | ||||
Airflow (CFM) | 1116 | 928 | 1979 | 1020 | ||||
Blower Motor BHP | 0.41 | 0.37 | 0.76 | 0.53 | ||||
| ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling | ID Blower | Cooling |
Octave Center Freq. | Operation2 | Operation2 | Operation2 | Operation2 | ||||
| Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) | Only (dB) | (dB) |
|
|
|
|
| ||||
63 | 80 | 84 | 80 | 83 | 85 | 87 | 84 | 87 |
125 | 74 | 77 | 74 | 76 | 80 | 82 | 80 | 83 |
250 | 58 | 61 | 58 | 61 | 68 | 68 | 63 | 65 |
500 | 48 | 51 | 47 | 50 | 58 | 58 | 53 | 54 |
1000 | 41 | 45 | 39 | 43 | 55 | 55 | 49 | 50 |
2000 | 39 | 41 | 37 | 39 | 53 | 53 | 46 | 47 |
4000 | 41 | 41 | 38 | 38 | 55 | 55 | 49 | 49 |
8000 | 45 | 45 | 44 | 44 | 52 | 53 | 47 | 47 |
1.Tested in accordance with ARI Standard 260. Refer to 2001 Standard for Sound Rating of Ducted Air Moving and Conditioning Equipment .
2.Cooling Operation – ID blower, compressor and outdoor fan operating.
3.Test Duct Dimension: 12 in. wide x 18 in. high x 8 ft. long (0.30m x 0.46m x 2.44m).
4.Test duct termination is flush with reverberation room wall.
5.Duct end (sound reflection) correction: (11, 6, 3, 1, 0, 0, 0, 0) dB at (63, 125, 250, 500, 1k, 4k, 8k) Hz.
Johnson Controls Unitary Products | 9 |