2 hp and 3.5 hp Water-Cooled Portable Chillers
Nominal operating parameters for
|
|
| Nominal |
|
| Condenser water |
|
| ||
| Nominal cooling | water | Com- | Nominal | Water | flow in gpm | Amp draws g | |||
HP | capacity c in tons | flow | pressor | pump | conn. | Tower | City | 460/3/60 h | ||
| no pump | 1 pump | gpm d | hp | hp | in. NPT | water e | water f | rated | running |
2 | 2.1 | 1.9 | 5.1 | 2.0 | 1.0 | 1.0” | 6.2 | 4.2 | 12.2 | 8.3 |
3.5 | 3.6 | 3.4 | 8.6 | 3.5 | 1.0 | 1.0” | 10.5 | 7.2 | 16.4 | 11.8 |
cBased on 50ºF (10ºC) chilled water supply temperature and 85ºF (29ºC) tower water. Optional additional process pump hp (kW) reduces chiller capacity by 0.2 tons per hp (0.703 kW ref. cap. per 0.746 kW pump power).
dBased on 2.4 gpm per ton (9.1 lpm per 3.517 kW), nominal 1 pump.
eBased on availability of 85ºF (29ºC) tower water at 25 psi (172.4 kPa/1.7 bars) minimum. f Based on availability of 70ºF (21ºC) city water at 25 psi (172.4 kPa/1.7 bars) minimum.
gAn optional oversized process pump adds to the total rated or running chiller amperage. To find the new total chiller amperage, subtract the standard process pump amperage from the optional pump amperage (see Figure 1 on page 16), and add it to the chiller rated or running amperage.
hMultiply 460/3/60 amperage by 2.0 for
2 hp and 3.5 hp
|
| Process |
|
|
|
| Weights |
| |
HP | Compressor | connections | Dimensions in inches c | Dry d | Shipping d | Operating d e | |||
| hp | in. NPT | height | width | depth | lbs. | lbs. |
| lbs. |
2 | 2.0 | 1.0” | 28.3” | 22.0” | 41.7” | 333 | 363 |
| 383 |
3.5 | 3.5 | 1.0” | 28.3” | 22.0” | 41.7” | 362 | 392 |
| 412 |
cTo convert to cm, multiply by 2.54. Add to height dimension based on mounting options.
dWeight is for standard chiller. Some optional features will increase weight. Multiply by 0.454 to calculate Kg. e Operating weight is with a full
Chapter 7: Appendix | 49 of 78 |