Lochinvar Harmony Gain/Throttle, Process Gain/Throttling Range Table, Operating Mode - Normal

Page 15
GAIN/THROTTLE

---

SETTINGS

---ADJUST

Press to

Set Point

 

show

>Gain

Stage

PRESS TO SELECT

Lead

 

setting

GAIN/THROTTLE

OPERATING MODE - NORMAL

Default = 0

GAIN

--- GAIN ---

Value -> New Value

--- GAIN ---

Value -> New Value

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

Turn to

adjust value

Press to

select

new

The Gain adjusts the PID logic in the Harmony to control how much modulation is changed when the system temperature is different from the Set Point.

A Gain of 0 is a good starting point for all systems.

If, during normal load conditions, the system temperature tends to fluctuate significantly above and below the Set Point, decrease the Gain by two numbers (for example, from 0 to -2). Wait for at least 15 minutes before evaluating how the change has affected the system.

If, during normal load conditions the system temperature tends to remain consistently below the Set Point (or consistently above the Set Point), increase the Gain by two numbers (for example, from 0 to 2). Wait for at least 15 minutes before evaluating how the change has affected the system.

OPERATING MODE - PROCESS

Default = 1.0

The Gain acts as a throttling range around the Set Point.

When the actual temperature is equal to the Set Point, the lead stage will be at 100% modulation.

Each throttling range above or below the Set Point controls one stages modulation linearly from 0 to 100%.

The Process Gain Table below shows the relationship between the Gain and stage modulation.

The Process Gain Table does not show all the possible modulation values. The table is for example only. The Harmony will control the modulation in one percent increments based on the Set Point and Gain value.

- THROTTLE

PROCESS GAIN/THROTTLING RANGE TABLE

SYSTEM TEMPERATURE

STAGES MODULATION

3 x Gain Setting Above Set Point

All Stages OFF

2.5 x Gain Setting Above Set Point

All Stages OFF

 

 

2 x Gain Above Set Point

Lead Stage at 0%

1 x Gain Above Set Point

Lead Stage at 0%

 

 

0.5 x Gain AboveSet Point

Lead Stage at 50%

At Set Point

Lead Stage at 100%

 

 

0.5 x Gain Below Set Point

Lead Stage at 100%, 1 Lag at 50%

1x Gain Below Set Point

Lead and 1 Lag at 100%

 

 

2 x Gain Below Set Point

Lead and 2 Lag at 100%

2.5 x Gain Below Set Point

Lead and 2 Lag at 100%

 

 

3 x Gain Below Set Point

All Stages at 100%

 

 

15

Image 15
Contents TABLE OF CONTENTS LochinvarHARMONY SEQUENCING CONTROL Harmony Function ChartHARMONY FULL MODULATIONHarmony Overview WIRING THE POWER INSTALLATIONINPUT WIRING INPUT WIRINGEMS Sourcing Current INSTALLATION INPUT WIRINGWIRING THE SHUTDOWN WIRING THE SYSTEM PROVESystem Prove WIRING THE BOILER ACTIVE INPUTSSignal Dry ContactEMS INPUT OUTPUT WIRINGWIRING A SETBACK CONNECTING AN OUTDOOR SENSORWiring the SYS Output WIRING THE SYSTEM OUTPUTWIRING THE STAGE OUTPUTS System Output Operation in Reset ModeINSTALLATION OUTPUT WIRINGWIRING TO 4-20MA MODULATING MOTORS WIRING TO VOLTAGE MODULATING MOTORSMAKING SELECTIONS USING THE MENUSUSING MENUS CHANGING SETTINGSDefault - F SYSTEM STARTUPSTARTUP SEQUENCE SELECTING THE SENSOR TYPENot available for Reset Sensor Types EMS INPUT Default - SetbackSELECTING THE MODULATING MODE Default - Normal SELECTING THE OUTPUT TYPEPress to select Process SELECTING THE OPERATING MODE Default - NormalSYSTEM STARTUP Press to select Normal or turn to scroll downTHE MAIN DISPLAY OPERATING SETTINGSRESET F AND RESET C SET POINTPROCESS GAIN/THROTTLING RANGE TABLE Default =THROTTLE GAIN/THROTTLELEAD STAGE LEAD STAGEUsed to manually change the lead stage THE SYSTEM SETTINGS MENU SYSTEM SETTINGSSETTINGS SYSTEM SETTINGSSYSTEM SETTINGS PURGE DELAY Default - 1.0 minDefault - 0 min LAG DELAYSETBACK STANDBY TIME Default - 10 minSYSTEM RUN-ONDefault - 0 min DefaultLAST STAGE HOLD Default 24hrDefault ROTATE TIMESYSTEM SETTINGS PASSWORDDefault Disabled SET TIMEMODE STAGE SETTINGSINDIVIDUAL STAGE ADJUSTMENTS THE STAGE MENU Default - OFFPress to show setting Turn to adjust value IGNITION POINT Default - 1%MODULATION START Default - 75% STAGE SETTINGSCOPY SETTINGS - STAGE A ONLY STAGE SETTINGSModulating Mode - PARALLEL OFFSET Default RESET SETTINGSRESET RATIO DefaultOUTDOOR CUTOFF RESETDefault 64F MINIMUM WATER TEMPERATURE Default 70FSTAGE OUTPUTS TROUBLESHOOTINGTROUBLESHOOTING TEMPERATURE INPUTSAPPENDIX APPENDIXSYSTEM STARTUP MENU EXTERNAL SET POINT 4-20MA EMS-CONTROLRANGEMOVING AROUND THE STAGES MENUS MANUAL CONVENTIONSAPPENDIX Symbols INDEXIndex INDEX HARMONY SPECIFICATIONS Lead Stage Rotation4-20mAExternal Input