Lochinvar Harmony Installation Input Wiring, EMS Sourcing Current, Wiring The Shutdown, Ems Input

Page 5
Harmony Sources Current 24VDC Excitation Voltage

Harmony Sources Current 24VDC Excitation Voltage

EMS INPUT

+ SIGNAL

(-)

EMS

(+)

Input

SHIELD

 

 

EMS Sourcing Current

EMS INPUT

+ SIGNAL

(-)

EMS

(+)

Input

SHIELD

 

 

CONNECTING AN EXTERNAL SET POINT (4-20mA EMS-CONTROL)

The Harmony can take a 4-20mA signal from an Energy Manage- ment System (EMS) or other signal source to change the set point remotely (see pg. 28 for additional details).

The signal must be a two-wire 4-20mA.

A system sensor must be installed as described in the previous section.

The External Set Point must be set up correctly (see pg. 12). These settings will allow the Harmony to read and monitor the system temperature and also monitor the 4-20mA input to remotely adjust the Harmony set point to the desired value.

The Harmony can source the current for the 4-20mA input. It provides an excitation voltage of 24VDC. If using the Harmony to source the power, attach the (+) side of the 4-20mA input to the Harmony EMS terminal marked +. Attach the (-) side of the 4-20mA signal to the EMS terminal marked SIGNAL.

If the EMS or other signal sources the current (provides the excitation voltage), attach the (+) side of the 4-20mA input to the Harmony EMS terminal marked SIGNAL. Attach the (-) side of the 4-20mA input to the EMS terminal marked SHIELD.

INSTALLATION INPUT WIRING

INPUTS

 

A1

T

 

TEMP

A2

 

A3

SHUTDOWN

 

A4

 

A5

+

A6

S

A7

NETWORK

 

A8

 

A9

SYSTEM

 

A10

PROVE

 

Dry Contact

Shutdown

Signal

WIRING THE SHUTDOWN

This feature can be used whenever it is desirable to turn off the Harmony from a remote location or another controller.

A typical use for this feature would be to turn off all boiler stages when an EMS panel no longer requires heat in the system.

When the Shutdown feature is enabled by closing a dry contact, all active stages will immediately modulate down to low. They will remain in low for 45 seconds and then turn off.

If the System Output relay was active, it will remain active until the System Delay is over, then it will also turn off.

The Shutdown signal must be a dry contact only. No voltage can be placed across the SHUTDOWN terminals.

Bring the two wires from the dry contact to the terminals marked SHUTDOWN- A3, A4.

WIRING THE SYSTEM PROVE

5

Image 5
Contents HARMONY TABLE OF CONTENTSLochinvar HARMONY Harmony Function ChartFULL MODULATION SEQUENCING CONTROLHarmony Overview INPUT WIRING INSTALLATIONINPUT WIRING WIRING THE POWERWIRING THE SHUTDOWN INSTALLATION INPUT WIRINGWIRING THE SYSTEM PROVE EMS Sourcing CurrentSignal WIRING THE BOILER ACTIVE INPUTSDry Contact System ProveWIRING A SETBACK OUTPUT WIRINGCONNECTING AN OUTDOOR SENSOR EMS INPUTWIRING THE STAGE OUTPUTS WIRING THE SYSTEM OUTPUTSystem Output Operation in Reset Mode Wiring the SYS OutputWIRING TO 4-20MA MODULATING MOTORS OUTPUT WIRINGWIRING TO VOLTAGE MODULATING MOTORS INSTALLATIONUSING MENUS USING THE MENUSCHANGING SETTINGS MAKING SELECTIONSSTARTUP SEQUENCE SYSTEM STARTUPSELECTING THE SENSOR TYPE Default - FSELECTING THE MODULATING MODE Default - Normal EMS INPUT Default - SetbackSELECTING THE OUTPUT TYPE Not available for Reset Sensor TypesSYSTEM STARTUP SELECTING THE OPERATING MODE Default - NormalPress to select Normal or turn to scroll down Press to select ProcessRESET F AND RESET C OPERATING SETTINGSSET POINT THE MAIN DISPLAYTHROTTLE Default =GAIN/THROTTLE PROCESS GAIN/THROTTLING RANGE TABLEUsed to manually change the lead stage LEAD STAGELEAD STAGE SETTINGS SYSTEM SETTINGSSYSTEM SETTINGS THE SYSTEM SETTINGS MENUDefault - 0 min PURGE DELAY Default - 1.0 minLAG DELAY SYSTEM SETTINGSSYSTEM RUN-ONDefault - 0 min STANDBY TIME Default - 10 minDefault SETBACKDefault Default 24hrROTATE TIME LAST STAGE HOLDDefault Disabled PASSWORDSET TIME SYSTEM SETTINGSINDIVIDUAL STAGE ADJUSTMENTS THE STAGE MENU STAGE SETTINGSDefault - OFF MODEMODULATION START Default - 75% IGNITION POINT Default - 1%STAGE SETTINGS Press to show setting Turn to adjust valueModulating Mode - PARALLEL COPY SETTINGS - STAGE A ONLYSTAGE SETTINGS RESET RATIO RESET SETTINGSDefault OFFSET DefaultDefault 64F RESETMINIMUM WATER TEMPERATURE Default 70F OUTDOOR CUTOFFTROUBLESHOOTING TROUBLESHOOTINGTEMPERATURE INPUTS STAGE OUTPUTSSYSTEM STARTUP MENU APPENDIXEXTERNAL SET POINT 4-20MA EMS-CONTROLRANGE APPENDIXAPPENDIX MOVING AROUND THE STAGES MENUSMANUAL CONVENTIONS Index SymbolsINDEX INDEX 4-20mAExternal Input HARMONY SPECIFICATIONSLead Stage Rotation