RESET SETTINGS

RESET RATIOS

 

1:4

1:3

1:2

1:1.5

 

220

 

 

 

 

210

 

 

1:1.25

°F)

 

 

 

200

 

 

 

(in

190

 

 

1:1

Temperature

180

 

 

 

170

 

 

1.25:1

 

 

 

160

 

 

1.5:1

150

 

 

2:1

Water

140

 

 

 

 

 

130

 

 

3:1

 

120

 

 

4:1

 

 

 

 

 

110

 

 

 

 

100

 

 

 

 

70 60 50 40

30

20 10

0 -10 -20

Outdoor Temperature (in °F)

 

Temp

 

 

 

<A>

B

C

D

 

OFF

OFF

OFF

OFF

 

---

SETTINGS

---ADJUST Press to

>Set Point

 

 

show

Lead Stage

 

PRESS TO SELECT

Settings

Gain

 

 

 

RESET SETTINGS

RESET RATIO

Default 1:1

The Reset Ratio controls how much heat will be added based on outdoor temperature. The Reset Ratios are shown as Outdoor Temperature:Water Temperature.

A 1:1 Reset Ratio signifies for each degree it gets colder outside, the Calculated water temperature will raise 1 degree.

The other Reset Ratios are adjustable from 1:4 to 4:1.

The Reset Ratio curves start at 70°F. At 70°F the Harmony will require 100°F water. Note that this is not the point where the Harmony will begin giving heat. That point is determined by the Outdoor Cutoff (next page). Also note that this starting point can be changed by adjusting the Offset (below).

For new installations with standard baseboard heating, begin with a Reset Ratio of 1:1.

For new installations with radiant heat, begin with a Reset Ratio curve of 2:1.

Adjust the Reset Ratio value in cold weather. If the ambient indoor temperatures are cold in the cold weather, pick the next higher Reset Ratio (that is, go from 1:1 to 1:1.25). If the ambient building tempera- tures are warm in the cold weather, pick the next lower Reset Ratio (from 1:1 to 1.25:1).

After adjusting the Reset Ratio curve, wait at least 24 hours before making another adjustment.

To adjust the Reset Ratio, from the main display press the ADJUST/ SELECT knob to obtain the Settings menu. Select Set Point. The Reset Ratio choices will now be shown.

RESET SETTINGS

---

RESET

RATIO ---

1.00°OD =

1.25°Sys

>1.00°OD =

1.00°Sys

1.25°OD =

1.00°Sys

 

 

 

---

RESET

RATIO ---

1.00°OD =

1.50°Sys

>1.00°OD =

1.25°Sys

1.00°OD =

1.00°Sys

 

 

 

---

RESET

RATIO ---

1.00°OD =

1.50°Sys

>1.00°OD =

1.25°Sys

1.00°OD =

1.00°Sys

ADJUST

Press to

 

select

PRESS TO SELECTSet Point

ADJUST

Turn to

 

PRESS TO SELECT

scroll

ADJUST

Press to

 

select

PRESS TO SELECT

new

OFFSET Default 0

The Offset value moves the starting point of the Reset Ratio curves (see charts below).

Therefore, any change made to the Offset will immediately change the value of the Harmony Set Point water temperature by the same amount.

For example, if the calculated Set Point water temperature were 150°F based on the specific outdoor temperature and Reset Ratio, then increasing the Offset from 0°F to 10°F would increase the Set Point water temperature to 160°F.

Temperature

130

 

1:3

 

1:1

Temperature

110

 

1:3

 

1:1

Temperature

150

 

1:3

 

1:1

120

 

 

 

 

100

 

 

 

 

140

 

 

 

 

Water

 

 

 

 

Water

 

 

 

 

Water

 

 

 

 

110

 

 

 

4:1

90

 

 

 

4:1

130

 

 

 

4:1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

100 70

60

50

40

 

8070

60

50

40

120 70

60

50

40

 

 

Outdoor Temperature

 

 

Outdoor Temperature

 

 

Outdoor Temperature

With a 0° Offset, the ratio curves

With a -20° Offset, the ratio curves

With a +20° Offset, the ratio curves

begin at 100° Water Temperature.

begin at 80° Water Temperature.

begin at 120° Water Temperature.

25

Image 25
Contents Lochinvar TABLE OF CONTENTSHARMONY HARMONY Harmony Function ChartFULL MODULATION SEQUENCING CONTROLHarmony Overview INPUT WIRING INSTALLATIONINPUT WIRING WIRING THE POWERWIRING THE SHUTDOWN INSTALLATION INPUT WIRINGWIRING THE SYSTEM PROVE EMS Sourcing CurrentSignal WIRING THE BOILER ACTIVE INPUTSDry Contact System ProveWIRING A SETBACK OUTPUT WIRINGCONNECTING AN OUTDOOR SENSOR EMS INPUTWIRING THE STAGE OUTPUTS WIRING THE SYSTEM OUTPUTSystem Output Operation in Reset Mode Wiring the SYS OutputWIRING TO 4-20MA MODULATING MOTORS OUTPUT WIRINGWIRING TO VOLTAGE MODULATING MOTORS INSTALLATIONUSING MENUS USING THE MENUSCHANGING SETTINGS MAKING SELECTIONSSTARTUP SEQUENCE SYSTEM STARTUPSELECTING THE SENSOR TYPE Default - FSELECTING THE MODULATING MODE Default - Normal EMS INPUT Default - SetbackSELECTING THE OUTPUT TYPE Not available for Reset Sensor TypesSYSTEM STARTUP SELECTING THE OPERATING MODE Default - NormalPress to select Normal or turn to scroll down Press to select ProcessRESET F AND RESET C OPERATING SETTINGSSET POINT THE MAIN DISPLAYTHROTTLE Default =GAIN/THROTTLE PROCESS GAIN/THROTTLING RANGE TABLELEAD STAGE LEAD STAGEUsed to manually change the lead stage SETTINGS SYSTEM SETTINGSSYSTEM SETTINGS THE SYSTEM SETTINGS MENUDefault - 0 min PURGE DELAY Default - 1.0 minLAG DELAY SYSTEM SETTINGSSYSTEM RUN-ONDefault - 0 min STANDBY TIME Default - 10 minDefault SETBACKDefault Default 24hrROTATE TIME LAST STAGE HOLDDefault Disabled PASSWORDSET TIME SYSTEM SETTINGSINDIVIDUAL STAGE ADJUSTMENTS THE STAGE MENU STAGE SETTINGSDefault - OFF MODEMODULATION START Default - 75% IGNITION POINT Default - 1%STAGE SETTINGS Press to show setting Turn to adjust valueSTAGE SETTINGS COPY SETTINGS - STAGE A ONLYModulating Mode - PARALLEL RESET RATIO RESET SETTINGSDefault OFFSET DefaultDefault 64F RESETMINIMUM WATER TEMPERATURE Default 70F OUTDOOR CUTOFFTROUBLESHOOTING TROUBLESHOOTINGTEMPERATURE INPUTS STAGE OUTPUTSSYSTEM STARTUP MENU APPENDIXEXTERNAL SET POINT 4-20MA EMS-CONTROLRANGE APPENDIXMANUAL CONVENTIONS MOVING AROUND THE STAGES MENUSAPPENDIX INDEX SymbolsIndex INDEX Lead Stage Rotation HARMONY SPECIFICATIONS4-20mAExternal Input