RESET RATIOS
| 1:4 | 1:3 | 1:2 | 1:1.5 |
| 220 |
|
|
|
| 210 |
|
| 1:1.25 |
°F) |
|
|
| |
200 |
|
|
| |
(in | 190 |
|
| 1:1 |
Temperature | 180 |
|
|
|
170 |
|
| 1.25:1 | |
|
|
| ||
160 |
|
| 1.5:1 | |
150 |
|
| 2:1 | |
Water | 140 |
|
| |
|
|
| ||
130 |
|
| 3:1 | |
| 120 |
|
| 4:1 |
|
|
|
| |
| 110 |
|
|
|
| 100 |
|
|
|
| 70 60 50 40 | 30 | 20 10 | 0 |
Outdoor Temperature (in °F)
| Temp |
|
|
|
<A> | B | C | D |
|
OFF | OFF | OFF | OFF |
|
SETTINGS | ||||
>Set Point |
|
| show | |
Lead Stage |
| PRESS TO SELECT | Settings | |
Gain |
|
|
|
RESET SETTINGS
RESET RATIO | Default 1:1 |
•The Reset Ratio controls how much heat will be added based on outdoor temperature. The Reset Ratios are shown as Outdoor Temperature:Water Temperature.
•A 1:1 Reset Ratio signifies for each degree it gets colder outside, the Calculated water temperature will raise 1 degree.
•The other Reset Ratios are adjustable from 1:4 to 4:1.
•The Reset Ratio curves start at 70°F. At 70°F the Harmony will require 100°F water. Note that this is not the point where the Harmony will begin giving heat. That point is determined by the Outdoor Cutoff (next page). Also note that this starting point can be changed by adjusting the Offset (below).
•For new installations with standard baseboard heating, begin with a Reset Ratio of 1:1.
•For new installations with radiant heat, begin with a Reset Ratio curve of 2:1.
•Adjust the Reset Ratio value in cold weather. If the ambient indoor temperatures are cold in the cold weather, pick the next higher Reset Ratio (that is, go from 1:1 to 1:1.25). If the ambient building tempera- tures are warm in the cold weather, pick the next lower Reset Ratio (from 1:1 to 1.25:1).
•After adjusting the Reset Ratio curve, wait at least 24 hours before making another adjustment.
•To adjust the Reset Ratio, from the main display press the ADJUST/ SELECT knob to obtain the Settings menu. Select Set Point. The Reset Ratio choices will now be shown.
RESET SETTINGS
RESET | RATIO | |
1.00°OD = | 1.25°Sys | |
>1.00°OD = | 1.00°Sys | |
1.25°OD = | 1.00°Sys | |
|
|
|
RESET | RATIO | |
1.00°OD = | 1.50°Sys | |
>1.00°OD = | 1.25°Sys | |
1.00°OD = | 1.00°Sys | |
|
|
|
RESET | RATIO | |
1.00°OD = | 1.50°Sys | |
>1.00°OD = | 1.25°Sys | |
1.00°OD = | 1.00°Sys |
ADJUST | Press to |
| select |
PRESS TO SELECTSet Point | |
ADJUST | Turn to |
| |
PRESS TO SELECT | scroll |
ADJUST | Press to |
| select |
PRESS TO SELECT | new |
OFFSET Default 0
•The Offset value moves the starting point of the Reset Ratio curves (see charts below).
•Therefore, any change made to the Offset will immediately change the value of the Harmony Set Point water temperature by the same amount.
•For example, if the calculated Set Point water temperature were 150°F based on the specific outdoor temperature and Reset Ratio, then increasing the Offset from 0°F to 10°F would increase the Set Point water temperature to 160°F.
Temperature | 130 |
| 1:3 |
| 1:1 | Temperature | 110 |
| 1:3 |
| 1:1 | Temperature | 150 |
| 1:3 |
| 1:1 |
120 |
|
|
|
| 100 |
|
|
|
| 140 |
|
|
|
| |||
Water |
|
|
|
| Water |
|
|
|
| Water |
|
|
|
| |||
110 |
|
|
| 4:1 | 90 |
|
|
| 4:1 | 130 |
|
|
| 4:1 | |||
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
100 70 | 60 | 50 | 40 |
| 8070 | 60 | 50 | 40 | 120 70 | 60 | 50 | 40 | |||||
|
| Outdoor Temperature |
|
| Outdoor Temperature |
|
| Outdoor Temperature | |||||||||
With a 0° Offset, the ratio curves | With a | With a +20° Offset, the ratio curves | |||||||||||||||
begin at 100° Water Temperature. | begin at 80° Water Temperature. | begin at 120° Water Temperature. |
25