Lochinvar Harmony IGNITION POINT Default - 1%, MODULATION START Default - 75%, Stage Settings

Page 23
Press to

- STAGE SETTINGS - Mode

>Ignition % Mod Start %

----- STAGE ------

IGNITION POINT

Value -> New Value

----- STAGE ------

IGNITION POINT

Value -> New Value

- STAGE

SETTINGS -

Mode

%

 

Ignition

 

>Mod Start %

 

 

 

----- STAGE

------

MODULATION START

Value ->

New Value

 

 

 

 

----- STAGE

------

MODULATION START

Value ->

New Value

 

 

 

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

Press to

show setting

Turn to

adjust value

Press to

select

new

Press to

show

setting

Turn to

adjust value

Press to

select

new

IGNITION POINT Default - 1%

When Can a Stage Begin Modulating?

The Ignition Point is the percent modulation which must be attained before the unit can be activated.

For most boilers, the Ignition Point should be set at 1%.

Older units or atmospheric units may require the modulating fuel valve to be open from 20-50% before proper ignition can be attained. Check with the boiler manufacturer if you are in doubt about the minimum position of the fuel valve for ignition.

MODULATION START Default - 75%

When Does the Next Stage Turn On?

The Modulation Start determines at what percent modulation of the current Stage the next Stage in the sequence will be activated.

For example, if the Modulation Start for Stage A is set to 75%, then when Stage A reaches 75% modulation, Stage B (if Stage B is in Auto Mode and is not already on) will be brought on in low fire.

When modulation is decreasing, the lag unit will remain on in low modulation, until the previous stage reaches 40% of its Modulation Start point, or 2% above the Ignition Point, whichever is higher.

Using the same example, as the load decreased, Stage B would modulate down to low. Stage A would then modulate down to 30%. Only then would Stage B turn off.

If the Lag Delay (see pg. 18) is set to anything other than 0, a Stage must always go up to 100% modulation before the next stage is activated. However, the Modulation Start should still be set correctly, because it will be valid when modulation is decreasing.

The Modulation Start point will generally be set differently based on the Modulating Mode selected (see pg. 12).

STAGE SETTINGS

When does the lag stage turn OFF?

At 40% of the Previous Stage Mod Point Or 2% Above the Ignition Point (Whichever is higher)

Example:

Stage A - Lead

Ignition Point - 1%

Mod Start 75%

When does Stage B turn OFF? At 40% of Stage A's Mod Point

75 x (40/100) = 30

Stage B will turn off when A's modulation reaches 30%

Modulating Mode - NORMAL

Lower settings of the modulation start point allow the next boiler in the sequence to be activated and warmed up, generally allowing more even set point control.

Higher settings of the modulation start point prevent unnecessary Stages from being activated. Also, as most units run more effi- ciently at higher modulation, a higher setting can result in fuel savings.

Some general guidelines follow:

-Less than 50% - not recommended in the Normal mode.

-50%-70% - These lower settings might be used in an application which has wide load swings such as an industrial plant or a hospital. This allows an additional boiler to be brought on line before the previous boiler has begun to reach its capacity. The next boiler will now be available for fast, high demands.

-70-90% - This range is recommended for most applications. When there are several Stages of relatively equal capacity and all can be used to hold the load, this allows some degree of overlap, without activating unnecessary Stages.

-90-100% - Recommended when one Stage can almost always handle the load, and other Stages are mainly for backup.

23

Image 23
Contents HARMONY TABLE OF CONTENTSLochinvar SEQUENCING CONTROL Harmony Function ChartHARMONY FULL MODULATIONHarmony Overview WIRING THE POWER INSTALLATIONINPUT WIRING INPUT WIRINGEMS Sourcing Current INSTALLATION INPUT WIRINGWIRING THE SHUTDOWN WIRING THE SYSTEM PROVESystem Prove WIRING THE BOILER ACTIVE INPUTSSignal Dry ContactEMS INPUT OUTPUT WIRINGWIRING A SETBACK CONNECTING AN OUTDOOR SENSORWiring the SYS Output WIRING THE SYSTEM OUTPUTWIRING THE STAGE OUTPUTS System Output Operation in Reset ModeINSTALLATION OUTPUT WIRINGWIRING TO 4-20MA MODULATING MOTORS WIRING TO VOLTAGE MODULATING MOTORSMAKING SELECTIONS USING THE MENUSUSING MENUS CHANGING SETTINGSDefault - F SYSTEM STARTUPSTARTUP SEQUENCE SELECTING THE SENSOR TYPENot available for Reset Sensor Types EMS INPUT Default - SetbackSELECTING THE MODULATING MODE Default - Normal SELECTING THE OUTPUT TYPEPress to select Process SELECTING THE OPERATING MODE Default - NormalSYSTEM STARTUP Press to select Normal or turn to scroll downTHE MAIN DISPLAY OPERATING SETTINGSRESET F AND RESET C SET POINTPROCESS GAIN/THROTTLING RANGE TABLE Default =THROTTLE GAIN/THROTTLEUsed to manually change the lead stage LEAD STAGELEAD STAGE THE SYSTEM SETTINGS MENU SYSTEM SETTINGSSETTINGS SYSTEM SETTINGSSYSTEM SETTINGS PURGE DELAY Default - 1.0 minDefault - 0 min LAG DELAYSETBACK STANDBY TIME Default - 10 minSYSTEM RUN-ONDefault - 0 min DefaultLAST STAGE HOLD Default 24hrDefault ROTATE TIMESYSTEM SETTINGS PASSWORDDefault Disabled SET TIMEMODE STAGE SETTINGSINDIVIDUAL STAGE ADJUSTMENTS THE STAGE MENU Default - OFFPress to show setting Turn to adjust value IGNITION POINT Default - 1%MODULATION START Default - 75% STAGE SETTINGSModulating Mode - PARALLEL COPY SETTINGS - STAGE A ONLYSTAGE SETTINGS OFFSET Default RESET SETTINGSRESET RATIO DefaultOUTDOOR CUTOFF RESETDefault 64F MINIMUM WATER TEMPERATURE Default 70FSTAGE OUTPUTS TROUBLESHOOTINGTROUBLESHOOTING TEMPERATURE INPUTSAPPENDIX APPENDIXSYSTEM STARTUP MENU EXTERNAL SET POINT 4-20MA EMS-CONTROLRANGEAPPENDIX MOVING AROUND THE STAGES MENUSMANUAL CONVENTIONS Index SymbolsINDEX INDEX 4-20mAExternal Input HARMONY SPECIFICATIONSLead Stage Rotation