Lochinvar Harmony Output Wiring, WIRING TO 4-20MA MODULATING MOTORS, Installation, Voltage

Page 9
Wiring the Stage Outputs

3 4 5 6 7 8 9 10 11 12

C

SYS

A

B

C

D

 

 

OPERATING LIMIT

 

 

 

OUTPUTS

 

 

 

 

Limit Circuit

Wiring the Stage Outputs

Each Stage output (A through D) has one Normally Open (N.O.) relay contact.

The N.O. contacts are dry contacts only. They do not source any voltage.

Each N.O. contact is capable of switching 6A resistive at 120VAC.

Total output of all stages, including the SYS, must not exceed 15A.

Wire the N.O. relay contacts in series with the boiler’s limit circuit.

Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.

INSTALLATION

Typical for each stage

4-20 mA

MODULATION OUTPUTS

Common

Common

Common

Common

mA

 

mA

 

mA

 

mA

 

 

 

 

 

 

 

 

 

 

 

C1

C2

C3

C4

C5

C6

C7

C8

C9

C10 C11 C12

A

B

C

D

-+

4 - 20mA Motor

WIRING TO 4-20 MA MODULATING MOTORS

The Harmony can be equipped to operate up to four 4-20 mA modulating motors.

To program the control for 4-20 mA output, see System Startup settings, pg. 12.

Apply the supplied label marked 4-20 mA below the output termi- nals.

The output boards are connected on the rear of the panel.

The pair of outputs A and B are controlled by a one output board. The pair of outputs C and D are controlled by a second output board.

The Harmony sources 24VDC excitation voltage for the 4-20mA signal.

Wire as shown below:

 

 

Common

mA Source (+)

 

 

 

 

 

Stage A

C1

C2

Harmony

Stage B

C4

C5

Sources

 

 

 

Stage C

C7

C8

Current

 

Stage D

C10

C11

 

 

 

 

OUTPUT WIRING

Voltage

MODULATION OUTPUTS

V+ V+ V+ V+

GND

GND

GND

GND

 

 

 

 

 

 

 

 

C1

C2

C3

C4

C5

C6

C7

C8

C9

C10 C11 C12

 

A

 

 

 

B

 

 

 

C

 

 

 

D

 

 

 

 

 

 

 

 

 

0- 5 V

 

0- 5 V

 

0- 5 V

 

0- 5 V

 

or

 

 

or

 

 

or

 

 

or

0-10V

 

0-10V

 

0-10V

 

0-10V

Motor

 

Motor

 

Motor

 

Motor

 

A

 

 

B

 

 

C

 

 

D

WIRING TO VOLTAGE MODULATING MOTORS

The Harmony can be equipped to operate up to four 0-5 V, 0-10V, 1- 5V, or 2-10V modulating motors.

Apply the supplied label marked Voltage below the output terminals.

The output boards are connected on the rear of the panel.

To select the range, 0-5V, 0-10V, 1-5V or 1-10V, see pg. 12.

The pair of outputs A and B are controlled by a one output board. The pair of outputs C and D are controlled by another output board.

Wire as shown below:

 

GND

V+

 

 

 

Stage A

C1

C3

Stage B

C4

C6

 

 

 

Stage C

C7

C9

Stage D

C10

C12

 

 

 

9

Image 9
Contents TABLE OF CONTENTS LochinvarHARMONY HARMONY Harmony Function ChartFULL MODULATION SEQUENCING CONTROLHarmony Overview INPUT WIRING INSTALLATIONINPUT WIRING WIRING THE POWERWIRING THE SHUTDOWN INSTALLATION INPUT WIRINGWIRING THE SYSTEM PROVE EMS Sourcing CurrentSignal WIRING THE BOILER ACTIVE INPUTSDry Contact System ProveWIRING A SETBACK OUTPUT WIRINGCONNECTING AN OUTDOOR SENSOR EMS INPUTWIRING THE STAGE OUTPUTS WIRING THE SYSTEM OUTPUTSystem Output Operation in Reset Mode Wiring the SYS OutputWIRING TO 4-20MA MODULATING MOTORS OUTPUT WIRINGWIRING TO VOLTAGE MODULATING MOTORS INSTALLATIONUSING MENUS USING THE MENUSCHANGING SETTINGS MAKING SELECTIONSSTARTUP SEQUENCE SYSTEM STARTUPSELECTING THE SENSOR TYPE Default - FSELECTING THE MODULATING MODE Default - Normal EMS INPUT Default - SetbackSELECTING THE OUTPUT TYPE Not available for Reset Sensor TypesSYSTEM STARTUP SELECTING THE OPERATING MODE Default - NormalPress to select Normal or turn to scroll down Press to select ProcessRESET F AND RESET C OPERATING SETTINGSSET POINT THE MAIN DISPLAYTHROTTLE Default =GAIN/THROTTLE PROCESS GAIN/THROTTLING RANGE TABLELEAD STAGE LEAD STAGEUsed to manually change the lead stage SETTINGS SYSTEM SETTINGSSYSTEM SETTINGS THE SYSTEM SETTINGS MENUDefault - 0 min PURGE DELAY Default - 1.0 minLAG DELAY SYSTEM SETTINGSSYSTEM RUN-ONDefault - 0 min STANDBY TIME Default - 10 minDefault SETBACKDefault Default 24hrROTATE TIME LAST STAGE HOLDDefault Disabled PASSWORDSET TIME SYSTEM SETTINGSINDIVIDUAL STAGE ADJUSTMENTS THE STAGE MENU STAGE SETTINGSDefault - OFF MODEMODULATION START Default - 75% IGNITION POINT Default - 1%STAGE SETTINGS Press to show setting Turn to adjust valueCOPY SETTINGS - STAGE A ONLY STAGE SETTINGSModulating Mode - PARALLEL RESET RATIO RESET SETTINGSDefault OFFSET DefaultDefault 64F RESETMINIMUM WATER TEMPERATURE Default 70F OUTDOOR CUTOFFTROUBLESHOOTING TROUBLESHOOTINGTEMPERATURE INPUTS STAGE OUTPUTSSYSTEM STARTUP MENU APPENDIXEXTERNAL SET POINT 4-20MA EMS-CONTROLRANGE APPENDIXMOVING AROUND THE STAGES MENUS MANUAL CONVENTIONSAPPENDIX Symbols INDEXIndex INDEX HARMONY SPECIFICATIONS Lead Stage Rotation4-20mAExternal Input