Lochinvar Harmony PURGE DELAY Default - 1.0 min, Lag Delay, Default - 0 min, System Settings

Page 18
Press to

SYSTEM SETTINGS 1

- SYSTEM SETTINGS 1-

Auto Rotate

>Purge Delay

Lag Delay

---

PURGE

DELAY

---

Value ->

New Value

 

 

 

 

 

 

 

 

---

PURGE

DELAY

---

Value -> New Value

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

Press to

show

setting

Turn to

adjust value

Press to

select

new

Lst on

On power up, or any time the Harmony loses power, the Lead Stage will be the lowest stage in Auto Mode (that is, A first, then B, C, or D).

The Lead Stage will always be the first stage brought on and modulated when there is a call for output. As more output is needed, additional stages are added.

When less output is needed, the Lead Stage will be the first stage turned off. The bracket indicating lead stage will then switch to the next available stage in Auto Mode. For instance, if the stages were added in the sequence A, B, and C, then they will be turned off in the sequence A, B, and finally C. The lead stage will now be D when more output is needed.

PURGE DELAY Default - 1.0 min

Most fully modulating units must go through a purge cycle before they are brought on line and can begin generating heating.

After activating a new Stage, the Harmony does not adjust its modulation until the Purge Delay is over. This allows the unit to fully come on line and to begin producing output. Once the Purge Delay is over, the Harmony can begin adjusting its modulation to hold the set point.

The Purge Delay helps to prevent short cycling of a newly activated Stage. Once a Stage is activated, it MUST run through the entire Purge Delay period.

The minimum Purge Delay setting MUST be the time required for the unit’s purge cycle.

The actual Purge Delay should be set to the amount of time between when a Stage is activated, and when the Harmony sensor begins to see a change in output. This can be several minutes longer than the actual purge time of the unit.

- SYSTEM SETTINGS 1-

Purge Delay

>Lag Delay

Standby Time

--- LAG DELAY ---

Value -> New Value

--- LAG DELAY ---

Value -> New Value

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

Press to

show

setting

Turn to

adjust value

Press to

select

new

LAG DELAY

Default - 0 min

Set the Lag Delay to 0 min when two or more Stages will generally be needed to hold the load.

The Lag Delay requires the previous stage to remain at 100% modulation for the full period of the Lag Delay before another Stage can be activated. For example, if the Lag Delay is set to 10 minutes, the Lead Stage would need to remain at 100% modulation for a full ten minutes (never backing down to even 99%) before a lag stage could be activated.

The Lag Delay is useful in installations where one unit should usually have enough output to hold the load unless it fails or load conditions become extreme.

The Lag Delay overrides the value of the Modulation Point selected for each stage. Regardless of that setting, the previous stage must reach 100% and stay there before another Stage can be activated.

The full Lag Delay must always elapse regardless of what happens to system temperature. Therefore, set the Lag Delay to 0 min if you want smooth set point control from multiple units.

18

Image 18
Contents TABLE OF CONTENTS LochinvarHARMONY FULL MODULATION Harmony Function ChartHARMONY SEQUENCING CONTROLHarmony Overview INPUT WIRING INSTALLATIONINPUT WIRING WIRING THE POWERWIRING THE SYSTEM PROVE INSTALLATION INPUT WIRINGWIRING THE SHUTDOWN EMS Sourcing CurrentDry Contact WIRING THE BOILER ACTIVE INPUTSSignal System ProveCONNECTING AN OUTDOOR SENSOR OUTPUT WIRINGWIRING A SETBACK EMS INPUTSystem Output Operation in Reset Mode WIRING THE SYSTEM OUTPUTWIRING THE STAGE OUTPUTS Wiring the SYS OutputWIRING TO VOLTAGE MODULATING MOTORS OUTPUT WIRINGWIRING TO 4-20MA MODULATING MOTORS INSTALLATIONCHANGING SETTINGS USING THE MENUSUSING MENUS MAKING SELECTIONSSELECTING THE SENSOR TYPE SYSTEM STARTUPSTARTUP SEQUENCE Default - FSELECTING THE OUTPUT TYPE EMS INPUT Default - SetbackSELECTING THE MODULATING MODE Default - Normal Not available for Reset Sensor TypesPress to select Normal or turn to scroll down SELECTING THE OPERATING MODE Default - NormalSYSTEM STARTUP Press to select ProcessSET POINT OPERATING SETTINGSRESET F AND RESET C THE MAIN DISPLAYGAIN/THROTTLE Default =THROTTLE PROCESS GAIN/THROTTLING RANGE TABLELEAD STAGE LEAD STAGEUsed to manually change the lead stage SYSTEM SETTINGS SYSTEM SETTINGSSETTINGS THE SYSTEM SETTINGS MENULAG DELAY PURGE DELAY Default - 1.0 minDefault - 0 min SYSTEM SETTINGSDefault STANDBY TIME Default - 10 minSYSTEM RUN-ONDefault - 0 min SETBACKROTATE TIME Default 24hrDefault LAST STAGE HOLDSET TIME PASSWORDDefault Disabled SYSTEM SETTINGSDefault - OFF STAGE SETTINGSINDIVIDUAL STAGE ADJUSTMENTS THE STAGE MENU MODESTAGE SETTINGS IGNITION POINT Default - 1%MODULATION START Default - 75% Press to show setting Turn to adjust valueCOPY SETTINGS - STAGE A ONLY STAGE SETTINGSModulating Mode - PARALLEL Default RESET SETTINGSRESET RATIO OFFSET DefaultMINIMUM WATER TEMPERATURE Default 70F RESETDefault 64F OUTDOOR CUTOFFTEMPERATURE INPUTS TROUBLESHOOTINGTROUBLESHOOTING STAGE OUTPUTSEXTERNAL SET POINT 4-20MA EMS-CONTROLRANGE APPENDIXSYSTEM STARTUP MENU APPENDIXMOVING AROUND THE STAGES MENUS MANUAL CONVENTIONSAPPENDIX Symbols INDEXIndex INDEX HARMONY SPECIFICATIONS Lead Stage Rotation4-20mAExternal Input