Lochinvar Harmony STANDBY TIME Default - 10 min, SYSTEM RUN-ONDefault - 0 min, Setback

Page 19
STANDBY TIME Default - 10 min

- SYSTEM SETTINGS 1-

Lag Delay

>Standby Time

System RunOn

-- STANDBY DELAY --

Value -> New Value

-- STANDBY DELAY --

Value -> New Value

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

Press to

show

setting

Turn to

adjust value

Press to

select

new

STANDBY TIME Default - 10 min

The Standby Time only applies to Stages in Standby Mode.

A Standby Stage can only be activated after all the Stages in Auto Mode have run at 100% modulation for the full Standby Time.

Standby Stages are used for backup up or extreme load conditions only. A Standby Stage can never be a Lead Stage

The full Standby Time must always elapse regardless of what happens to system temperature. Therefore, shorter Standby Times will result in smoother set point operation in extreme conditions. Longer Standby Times will result in more loss of load, but may prevent a Standby Stage from firing if the other stages can eventu- ally meet the load, or if the load decreases.

SYSTEM SETTINGS

- SYSTEM SETTINGS 1-

Standby Time

>System RunOn

<More Settings>

--

SYSTEM

RUN-ON

--

Value ->

New Value

 

 

 

 

 

 

 

 

--

SYSTEM

RUN-ON

--

Value -> New Value

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

Press to

show

setting

Turn to

adjust value

Press to

select

new

SYSTEM RUN-ON Default - 0 min

The SYS output relay will energize whenever there is a call for output and the Shutdown feature is not active.

The SYS will remain energized while any Stage is active. When the last Stage relay turns off, the SYS output will remain energized for the period of time set by the System Run-On.

If the System Run-On is set to 0, the SYS output will turn off immediately when the last Stage turns off.

A common use of the SYS output is to control a system pump in a heating system. After the last Stage is turned off, it is often desirable to run the system pump for an additional period of time to transfer the residual heat from the boilers to the heating system.

SYSTEM SETTINGS 2

2

- SYSTEM SETTINGS 1- Standby Time System RunOn

><More Settings>

- SYSTEM SETTINGS 2- >Setback

Rotate Time Last Stg Hold

--- SETBACK ---

Value -> New Value

--- SETBACK ---

Value -> New Value

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

ADJUST

PRESS TO SELECT

Press to

show more

Press to

show setting

Turn to

adjust value

Press to

select

new

SETBACK

Default - 0

Setback is not available in the Reset, or 4-20mA EMS-Control mode.

The Setback feature can be used to provide the Harmony with a lower temperature Set Point when less load is required.

The lower Set Point will appear on the main display indicating this condition.

A typical use for Setback is to providea lower system temperature to a factory during the night or on the weekends when product is not being manufactured but heat is still required.

The Setback will not be activated unless a signal is wired into the Harmony EMS terminals. See pg. 7 for wiring.

The amount of Setback selected is subtracted from the Set Point when a Setback signal is received.

For a example, if the Set Point is 180°F and the Setback is 20°F, then when the EMS SIGNAL and SHIELD terminals are closed, the Harmony will hold a Set Point of 160°F.

19

Image 19
Contents Lochinvar TABLE OF CONTENTSHARMONY SEQUENCING CONTROL Harmony Function ChartHARMONY FULL MODULATIONHarmony Overview WIRING THE POWER INSTALLATIONINPUT WIRING INPUT WIRINGEMS Sourcing Current INSTALLATION INPUT WIRINGWIRING THE SHUTDOWN WIRING THE SYSTEM PROVESystem Prove WIRING THE BOILER ACTIVE INPUTSSignal Dry ContactEMS INPUT OUTPUT WIRINGWIRING A SETBACK CONNECTING AN OUTDOOR SENSORWiring the SYS Output WIRING THE SYSTEM OUTPUTWIRING THE STAGE OUTPUTS System Output Operation in Reset ModeINSTALLATION OUTPUT WIRINGWIRING TO 4-20MA MODULATING MOTORS WIRING TO VOLTAGE MODULATING MOTORSMAKING SELECTIONS USING THE MENUSUSING MENUS CHANGING SETTINGSDefault - F SYSTEM STARTUPSTARTUP SEQUENCE SELECTING THE SENSOR TYPENot available for Reset Sensor Types EMS INPUT Default - SetbackSELECTING THE MODULATING MODE Default - Normal SELECTING THE OUTPUT TYPEPress to select Process SELECTING THE OPERATING MODE Default - NormalSYSTEM STARTUP Press to select Normal or turn to scroll downTHE MAIN DISPLAY OPERATING SETTINGSRESET F AND RESET C SET POINTPROCESS GAIN/THROTTLING RANGE TABLE Default =THROTTLE GAIN/THROTTLELEAD STAGE LEAD STAGEUsed to manually change the lead stage THE SYSTEM SETTINGS MENU SYSTEM SETTINGSSETTINGS SYSTEM SETTINGSSYSTEM SETTINGS PURGE DELAY Default - 1.0 minDefault - 0 min LAG DELAYSETBACK STANDBY TIME Default - 10 minSYSTEM RUN-ONDefault - 0 min DefaultLAST STAGE HOLD Default 24hrDefault ROTATE TIMESYSTEM SETTINGS PASSWORDDefault Disabled SET TIMEMODE STAGE SETTINGSINDIVIDUAL STAGE ADJUSTMENTS THE STAGE MENU Default - OFFPress to show setting Turn to adjust value IGNITION POINT Default - 1%MODULATION START Default - 75% STAGE SETTINGSSTAGE SETTINGS COPY SETTINGS - STAGE A ONLYModulating Mode - PARALLEL OFFSET Default RESET SETTINGSRESET RATIO DefaultOUTDOOR CUTOFF RESETDefault 64F MINIMUM WATER TEMPERATURE Default 70FSTAGE OUTPUTS TROUBLESHOOTINGTROUBLESHOOTING TEMPERATURE INPUTSAPPENDIX APPENDIXSYSTEM STARTUP MENU EXTERNAL SET POINT 4-20MA EMS-CONTROLRANGEMANUAL CONVENTIONS MOVING AROUND THE STAGES MENUSAPPENDIX INDEX SymbolsIndex INDEX Lead Stage Rotation HARMONY SPECIFICATIONS4-20mAExternal Input