Lochinvar Harmony Installation, Input Wiring, Mounting The Enclosure, Wiring The Power

Page 4
INSTALLATION

INSTALLATION

Mounting Holes

INSTALLATION

MOUNTING THE ENCLOSURE

Select a location near the equipment to be controlled.

The surface should be flat, and be sufficiently wide and strong to hold the Harmony.

Keep the Harmony panel away from extreme heat, cold, or humidity. Ambient operating temperature is from 20 to 120°F.

Remove the panel from the metal enclosure by removing the top center screw and loosening the two bottom screws. Lift the panel out.

Screw the enclosure to the surface through the mounting holes in the back of the enclosure.

Return the panel to the enclosure, replace the top screw, and tighten the bottom two screws.

INPUT WIRING

SAFETY

GROUND

MUST BE

CONNECTED

1

2

3

4

LINE

NEUTRAL

 

 

 

SYS

 

 

WIRING THE POWER

Bring the 120VAC 60Hz power wires through a bottom Knockout (KO) of the enclosure. The left front KO is preferred.

Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.

Connect the hot line to terminal marked LINE.

Connect the neutral line to the terminal marked NEUT.

The green ground screw MUST be connected to earth ground.

Earth

120VAC

Ground

60 Hz

INPUTS

 

To Temperature

A1

T

Sensor Mounted in

A2

TEMP

 

Common Header

 

 

A3

SHUTDOWN

 

A4

 

 

 

A5

+

 

A6

S

 

A7

NETWORK

 

 

 

A8

 

 

A9

SYSTEM

 

 

 

A10

PROVE

 

 

 

INPUT WIRING

CONNECTING THE SYSTEM SENSOR

The Harmony is designed to be connected to a temperature sensor for immersion in a 3/8ID well.

Contact the factory for additional temperature sensor options.

Locate the sensor in a common header where it will register the output of all the stages in the flow and after all stages have fed the header. If the sensor can not read the output of all the stages, it will not be able to control the system properly.

Temperature sensor wires can be extended up to 500’ by splicing with 18 gauge shielded wire (Belden #8760 or equivalent).

Do not run sensor wire in conduit with line voltage.

Temperature sensors have no polarity. Connect the wires from the sensor to the Harmony terminals marked TEMP- A1, A2.

Connect the shield to the circled terminal TEMP-A2with one of the sensor wires.

Note: Cut the shield wire at the sensor end.

4

Image 4
Contents Lochinvar TABLE OF CONTENTSHARMONY Harmony Function Chart HARMONYFULL MODULATION SEQUENCING CONTROLHarmony Overview INSTALLATION INPUT WIRINGINPUT WIRING WIRING THE POWERINSTALLATION INPUT WIRING WIRING THE SHUTDOWNWIRING THE SYSTEM PROVE EMS Sourcing CurrentWIRING THE BOILER ACTIVE INPUTS SignalDry Contact System ProveOUTPUT WIRING WIRING A SETBACKCONNECTING AN OUTDOOR SENSOR EMS INPUTWIRING THE SYSTEM OUTPUT WIRING THE STAGE OUTPUTSSystem Output Operation in Reset Mode Wiring the SYS OutputOUTPUT WIRING WIRING TO 4-20MA MODULATING MOTORSWIRING TO VOLTAGE MODULATING MOTORS INSTALLATIONUSING THE MENUS USING MENUSCHANGING SETTINGS MAKING SELECTIONSSYSTEM STARTUP STARTUP SEQUENCESELECTING THE SENSOR TYPE Default - FEMS INPUT Default - Setback SELECTING THE MODULATING MODE Default - NormalSELECTING THE OUTPUT TYPE Not available for Reset Sensor TypesSELECTING THE OPERATING MODE Default - Normal SYSTEM STARTUPPress to select Normal or turn to scroll down Press to select ProcessOPERATING SETTINGS RESET F AND RESET CSET POINT THE MAIN DISPLAYDefault = THROTTLEGAIN/THROTTLE PROCESS GAIN/THROTTLING RANGE TABLELEAD STAGE LEAD STAGEUsed to manually change the lead stage SYSTEM SETTINGS SETTINGSSYSTEM SETTINGS THE SYSTEM SETTINGS MENUPURGE DELAY Default - 1.0 min Default - 0 minLAG DELAY SYSTEM SETTINGSSTANDBY TIME Default - 10 min SYSTEM RUN-ONDefault - 0 minDefault SETBACKDefault 24hr DefaultROTATE TIME LAST STAGE HOLDPASSWORD Default DisabledSET TIME SYSTEM SETTINGSSTAGE SETTINGS INDIVIDUAL STAGE ADJUSTMENTS THE STAGE MENUDefault - OFF MODEIGNITION POINT Default - 1% MODULATION START Default - 75%STAGE SETTINGS Press to show setting Turn to adjust valueSTAGE SETTINGS COPY SETTINGS - STAGE A ONLYModulating Mode - PARALLEL RESET SETTINGS RESET RATIODefault OFFSET DefaultRESET Default 64FMINIMUM WATER TEMPERATURE Default 70F OUTDOOR CUTOFFTROUBLESHOOTING TROUBLESHOOTINGTEMPERATURE INPUTS STAGE OUTPUTSAPPENDIX SYSTEM STARTUP MENUEXTERNAL SET POINT 4-20MA EMS-CONTROLRANGE APPENDIXMANUAL CONVENTIONS MOVING AROUND THE STAGES MENUSAPPENDIX INDEX SymbolsIndex INDEX Lead Stage Rotation HARMONY SPECIFICATIONS4-20mAExternal Input