Lochinvar Harmony Troubleshooting, Temperature Inputs, Stage Outputs, System Output

Page 27
TROUBLESHOOTING

TROUBLESHOOTING

No Display, or Garbled Display

TEMPERATURE

Value

(in degrees F)

(in Ohms)

Check the 120VAC power input to the Harmony. Turn power to the

0

42683

Harmony off and back on.

10

31215

 

TEMPERATURE INPUTS

20

23089

25

19939

Display shows OPN

30

17264

Check the System Startup settings (pg. 11) to be sure the Harmony is

configured correctly to read the temperature input. Then check a

35

14985

sensor is connected and the wires are continuous to the Harmony.

40

13040

Finally follow the procedure for Incorrect Temperature Display.

 

 

45

11374

Display shows SHT

50

9944

The Harmony sees a short across the sensor input terminals.

 

 

55

8714

Remove the wires from either the SYSTEM TEMP or OUT TEMP

60

7653

terminals (whichever is reading SHT). The display should change to

70

5941

read OPN. If it doesn’t, the Harmony may be damaged.

80

4649

Display shows an Incorrect Temperature Display

Remove the wires from either the SYSTEM TEMP or OUT TEMP

90

3667

terminals (whichever is reading incorrectly). The display should

100

2914

change to read OPN. If it doesn’t, the Harmony may be damaged.

 

 

110

2332

Take an ohm reading across the detached sensor wires. The ohm

120

1879

reading should correspond to the side chart. If it doesn’t, the sensor

130

1524

may be damaged.

140

1243

 

 

150

1021

STAGE OUTPUTS

160

842

When the unit's Mode is set to ON, the unit does not come

170

699

on

180

583

To set the Mode to ON, see pg. 22. Remove any wires attached to the

190

489

Harmony output. Check for continuity across the stage's N.O.

200

412

contacts. If there is continuity, the Harmony output is working correctly. Check the wiring and the unit being energized to determine why it is not operating.

Red stage light is lit, but the unit is not on

The Harmony is calling for this unit to be on. Follow the procedure above.

Red stage light is not lit, but the unit is on

The Harmony is not calling for this unit to be active. Remove any wires attached to the Harmony output. Check for continuity across the N.O. contacts. If there is no continuity, the Harmony output is working correctly. Check the unit for any other operating controls which may be causing it to energize.

SYSTEM OUTPUT

Output is required but the SYSTEM component does not come on

Check the display to see if the temperature is above the Set Point or if the Outdoor Cutoff is active.

Red SYSTEM light is lit, but the SYSTEM component is not on

The Harmony is calling for the unit. Check for continuity across the N.O. SYS contacts. If there is continuity, the Harmony is working correctly. Check the wiring and the component being energized to determine why it is not operating.

Red stage light is not lit, but the SYSTEM component is on

The Harmony is not calling for the component to run. Remove any wires attached to the Harmony's SYS terminals. Check the N.O. terminals are open. If they are, check the unit for any other operating controls which may be causing it to energize.

TROUBLESHOOTING

27

Image 27
Contents TABLE OF CONTENTS LochinvarHARMONY SEQUENCING CONTROL Harmony Function ChartHARMONY FULL MODULATIONHarmony Overview WIRING THE POWER INSTALLATIONINPUT WIRING INPUT WIRINGEMS Sourcing Current INSTALLATION INPUT WIRINGWIRING THE SHUTDOWN WIRING THE SYSTEM PROVESystem Prove WIRING THE BOILER ACTIVE INPUTSSignal Dry ContactEMS INPUT OUTPUT WIRINGWIRING A SETBACK CONNECTING AN OUTDOOR SENSORWiring the SYS Output WIRING THE SYSTEM OUTPUTWIRING THE STAGE OUTPUTS System Output Operation in Reset ModeINSTALLATION OUTPUT WIRINGWIRING TO 4-20MA MODULATING MOTORS WIRING TO VOLTAGE MODULATING MOTORSMAKING SELECTIONS USING THE MENUSUSING MENUS CHANGING SETTINGSDefault - F SYSTEM STARTUPSTARTUP SEQUENCE SELECTING THE SENSOR TYPENot available for Reset Sensor Types EMS INPUT Default - SetbackSELECTING THE MODULATING MODE Default - Normal SELECTING THE OUTPUT TYPEPress to select Process SELECTING THE OPERATING MODE Default - NormalSYSTEM STARTUP Press to select Normal or turn to scroll downTHE MAIN DISPLAY OPERATING SETTINGSRESET F AND RESET C SET POINTPROCESS GAIN/THROTTLING RANGE TABLE Default =THROTTLE GAIN/THROTTLELEAD STAGE LEAD STAGEUsed to manually change the lead stage THE SYSTEM SETTINGS MENU SYSTEM SETTINGSSETTINGS SYSTEM SETTINGSSYSTEM SETTINGS PURGE DELAY Default - 1.0 minDefault - 0 min LAG DELAYSETBACK STANDBY TIME Default - 10 minSYSTEM RUN-ONDefault - 0 min DefaultLAST STAGE HOLD Default 24hrDefault ROTATE TIMESYSTEM SETTINGS PASSWORDDefault Disabled SET TIMEMODE STAGE SETTINGSINDIVIDUAL STAGE ADJUSTMENTS THE STAGE MENU Default - OFFPress to show setting Turn to adjust value IGNITION POINT Default - 1%MODULATION START Default - 75% STAGE SETTINGSCOPY SETTINGS - STAGE A ONLY STAGE SETTINGSModulating Mode - PARALLEL OFFSET Default RESET SETTINGSRESET RATIO DefaultOUTDOOR CUTOFF RESETDefault 64F MINIMUM WATER TEMPERATURE Default 70FSTAGE OUTPUTS TROUBLESHOOTINGTROUBLESHOOTING TEMPERATURE INPUTSAPPENDIX APPENDIXSYSTEM STARTUP MENU EXTERNAL SET POINT 4-20MA EMS-CONTROLRANGEMOVING AROUND THE STAGES MENUS MANUAL CONVENTIONSAPPENDIX Symbols INDEXIndex INDEX HARMONY SPECIFICATIONS Lead Stage Rotation4-20mAExternal Input