2 Maintenance (continued)
Inspect ignition and flame sense electrodes
1.Remove the ignition and flame sense electrodes from the water heater heat exchanger access cover.
2.Remove any deposits accumulated on the ignition/flame sense electrode using sandpaper. If the electrodes cannot be cleaned satisfactorily, replace with new ones.
3.Replace ignition/flame sense electrode, making sure gasket is in good condition and correctly positioned.
Check ignition ground wiring
1.Inspect water heater ground wire from the heat exchanger access cover to ground terminal strip.
2.Verify all wiring is in good condition and securely attached.
3.Check ground continuity of wiring using continuity meter.
4.Replace ground wires if ground continuity is not satisfactory.
Check all water heater wiring
1.Inspect all water heater wiring, making sure wires are in good condition and securely attached.
Check control settings
1.Go to the Setup Screen and check all settings. See Section
1of this manual. Adjust settings if necessary. See Section
1of this manual for adjustment procedures.
2.Check settings of external limit controls (if any) and adjust if necessary.
Perform start-up and checks
1.Start water heater and perform checks and tests specified in Section 9 -
Service Manual
Check burner flame
1.Inspect flame through observation window.
2.If the flame is unsatisfactory at either high fire or low fire, turn off water heater and allow water heater to cool down. Remove the burner and clean it thoroughly using a vacuum cleaner or compressed air. Do not use compressed air to clean burner if performed inside a building.
3.Remove the burner, reference FIG.
4.When replacing the burner, ensure gasket is in good condition and positioned correctly (FIG.
Figure 2-2 Burner Assembly
DOOR FIBER
| BURNER DOOR |
|
| BURNER DOOR |
|
| HEX NUT (6) |
|
| BURNER |
|
AIR/GAS GASKET |
|
|
FLAPPER VALVE |
| IGNITER GASKET |
SCREW (5X) | IGNITER | FLAME SENSE |
| ||
FLAPPER VALVE |
| |
| GASKET | |
| FLAME SENSE | |
| IGNITER SCREW (2X) | |
| FLAME SENSE |
|
| SCREW (2X) |
|
Check flame signal
1.At high fire the flame signal shown on the display should be at least 10 microamps.
2.A lower flame signal may indicate a fouled or damaged flame sense electrode. If cleaning the flame sense electrode does not improve, ground wiring is in good condition, and ground continuity is satisfactory, replace the flame sense electrode.
3.See Section 3 - Troubleshooting in this manual for other procedures to deal with low flame signal.
Review with owner
1.Review the Armor X2 Installation and Operation Manual with the owner.
2.Emphasize the need to perform the maintenance schedule specified in the Armor X2 Installation and Operation Manual (and in this manual as well).
3.Remind the owner of the need to call a licensed contractor should the heater or system exhibit any unusual behavior.
35