Lochinvar 1.5 service manual Gas valve adjustment procedure, Models 1.3

Page 50

3 Troubleshooting

Gas valve adjustment procedure

If adjustment of the gas valve is deemed necessary, use the following procedures: (Note: The procedures below are model specific.)

CAUTION Under normal operating conditions this valve should not need adjusting.

Model 1.0

Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-2. Using a screwdriver, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 49 of this manual to measure the combustion.

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3F on page 49 or replace the gas valve.

Figure 3-2Gas Valve Adjustment: Model 1.0

THROTTLE ADJUSTMENT SCREW

Service Manual

Models 1.3 - 1.5

Locate the throttle adjustment screw on top of the gas valve, see FIG. 3-3. Using an Allen wrench, turn the screw a 1/4 turn counterclockwise to increase CO2 levels or a 1/4 turn clockwise to decrease CO2 levels. After one adjustment on the valve, follow the Combustion Analysis Procedure on page 49 of this manual to measure the combustion.

If combustion is still not within the specified range, repeat the procedure. This procedure SHOULD NOT be performed more than four (4) times. If after four (4) adjustments and the combustion is still not within the specified range, revisit the possible causes in Table 3F on page 49 or replace the gas valve.

Figure 3-3Gas Valve Adjustment: Models 1.3 - 1.5

THROTTLE ADJUSTMENT

SCREW (REMOVE BLUE COVER)

50

Image 50
Contents Models 1.0, 1.3, Contents Handling ceramic fiber materials Niosh stated First AidTroubleshooting ServiceMaintenance Armor X2 display Control inputs Primary Smart Control ModuleSecondary Smart Touch Control Module Primary Control outputsSequence of operation General OperationHow the water heater operates Sequence of operation Sequence of operationThis table lists the parameters and where to access them Parameter tableBMS Viewable and changeable control parameters Status ScreenService Details Screen Service Main Screen Setup Screen Service/Setup Parameters Screen Service Set Point Parameters Screen Night Setback Parameters Screen Cascade Parameters Screen Cascade Operation10Vdc BMS Parameters Screen 10Vdc OperationService Cascade Screen Service Temps Screen Burners Screen Graph Select Screen History Screen Service Mode Screen Maintenance Maintenance and annual startup Inspect water heater area Address reported problemsClean condensate trap Inspect water heater interiorCheck expansion tank Check water heater relief valve Flue vent system and air pipingCheck water system Check control settings Check ignition ground wiringCheck all water heater wiring Check flame signalOiled bearing circulators Cleaning water heater heat exchangerCheck Delta T Troubleshooting Alarm ScreenCheck control module fuses Before troubleshootingCheck the following Troubleshooting Checking temperature sensors Temperature ResistanceFault Cause Corrective Action Drain Blocked Flow SwitchCondensate Flame outWhile Running Light cont’dFlame Lost High Limit Manual ResetCont’d Temp SW Automatic ResetHigh Limit / HEX Blower RPM’sSensor Open Louver Proving SwitchToo High Sensor Shorted Low Resets Try Later Air Flow Too Flap ValveWriting to Internal FaultNo Error Stored MemosOr Obstruction Combustion Analysis ProcedureGas Valve Adjustment Gas Supply PressureModels 1.3 Gas valve adjustment procedureModel