3 Troubleshooting (continued) |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||
Table 3D Troubleshooting Chart - Noisy System |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |||
| FAULT | CAUSE |
| CORRECTIVE ACTION |
|
| ||||
|
|
|
|
| ||||||
|
| - Supply gas problem. Natural gas pressures | • Refer to Section 7 - Gas Connections of the Armor X2 | |||||||
|
| should be between 4 inches w.c. (1.0 kPa) | Installation and Operation Manual for detailed | |||||||
|
| and 14 inches w.c. (3.5 kPa). LP gas | information concerning the gas supply. |
|
| |||||
|
| pressures should be between 8 inches w.c. |
|
|
|
|
|
|
| |
|
| (2.0 kPa) and 14 inches w.c. (3.2 kPa). |
|
|
|
|
|
|
| |
|
|
|
|
|
| |||||
|
|
|
| • Refer to the Gas Valve Adjustment Procedure | on | |||||
|
|
|
| page 50 of this manual for the proper gas valve setting. | ||||||
|
| - Gas/air mixture problem. | Verify that the vent/air intake lengths do not exceed the | |||||||
|
|
|
| maximum listed in the General Venting section of the | ||||||
|
|
|
| Armor X2 Installation and Operation Manual. |
|
| ||||
| Noisy |
|
|
| ||||||
|
|
| • Refer to page 35 in this manual for the burner removal | |||||||
| Operation | - Dirty/damaged burner. | and inspection procedure. Clean or replace the burner | |||||||
|
|
|
| as necessary. |
|
|
|
| ||
|
|
|
|
|
|
|
|
|
| |
|
|
|
| • Refer | to Section 6 | - | System Piping | of | the | |
|
|
|
| Armor X2 Installation and Operation Manual for | ||||||
|
| - Low water flow through the heat exchanger. | minimum flow rates. Verify that the water heater is piped | |||||||
|
|
|
| in a primary/secondary fashion and that the water heater | ||||||
|
|
|
| and system pump are running on a call for heat. |
| |||||
|
|
|
|
|
|
| ||||
|
| - Air in the piping system. | • Properly purge all air from the piping system. |
|
| |||||
|
|
|
|
|
|
|
|
|
| |
|
| - Low system water pressure. | • Verify | system pressure | is | a minimum of | 12 | psi | ||
|
| (82.7 kPa). |
|
|
|
| ||||
|
|
|
|
|
|
|
| |||
|
|
|
|
| ||||||
| No Pump | - Blown fuse. | • Replace fuse F5 on the control board, see page 38 of | |||||||
| Operation - |
|
| this manual. |
|
|
|
| ||
| HW Pump |
|
|
|
|
|
|
|
|
|
| - Faulty pump. | • Replace pump. |
|
|
|
| ||||
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
| |||
|
| - Internal fault on control board. | • Replace main control board. |
|
|
| ||||
|
|
|
|
|
|
|
|
| ||
|
| - Faulty pump relay. | • Replace relay. |
|
|
|
| |||
|
|
|
|
|
|
|
| |||
|
|
|
| • Lower | the system pressure below the | 150 | psi | |||
|
| - System pressure exceeds relief valve | (1034.2 kPa) rating of the supplied relief valve. |
|
| |||||
|
| setting. | • Improperly sized expansion tank. |
|
| |||||
| Relief Valve |
|
|
|
| |||||
| Opening |
|
|
|
|
|
|
|
|
|
-Outlet temperature exceeds relief valve • Check temperature settings of the main control board. settings.