3 Troubleshooting

Service Manual

￿WARNING

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Always disconnect power to the water heater before servicing. Failure to comply could result in severe personal injury, death, or substantial property damage.

Figure 3-1Control Module Fuses

F3 - 1.25 AMP FUSE

MAIN BOARD

F4 - 3.15 AMP FUSE

BLOWER

￿WARNING Never jumper (bypass) any device except for momentary testing as outlined in the

Troubleshooting chart. Severe personal injury, death, or substantial property damage can result.

Before troubleshooting:

1.Have the following items:

a.Voltmeter that can check 120 VAC, 24 VAC, and 12 VDC.

b.Continuity checker.

c.Contact thermometer.

2.Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) to water heater.

3.Make sure all external limit controls are installed and operating.

Check the following:

1.Wire connectors to control module are securely plugged in at the control module and originating control.

2.Gas pressures:

Maximum: 14 inches w.c. (3.5 kPa) natural, 14 inches w.c. (3.2 kPa) LP with no flow (lockup) or with water heater on

Minimum: 4 inches (5 inches on 1.0 models only) w.c. (1.0 kPa) natural, 8 inches w.c. (2.0 kPa) LP with gas flowing (verify during water heater startup)

Check control module fuses

NOTICE

ALWAYS check control module fuses

before replacing control module or any

 

 

major components (blower, etc.). If one

 

of these fuses is blown, it can prevent the

 

control module or other components from

 

operating.

1.Turn OFF the power to the water heater at the external line switch.

2.Remove the front access cover.

3.Remove the two (2) screws securing the control panel to the unit to gain access to the control module.

F5 - 5 AMP FUSE

PUMPS

F2 - 3.15 AMP FUSE

24V SUPPLY

4.Remove the two (2) nuts on the control module cover.

5.Inspect fuses F2, F3, F4, and F5, see FIG 3-1 below.

6.The water heater is shipped with six (6) spare fuses in a plastic bag located under the low water cutoff on the control module.

7.If necessary, replace open fuse (F3 is 1.25 amps, F2 and F4 are 3.15 amps, and F5 is 5 amps).

Note: Fuses F2 - F5 are all slow blow fuses.

￿WARNING Do not jumper fuse or replace with any fuse except as specified. Failure to comply

could result in severe personal injury, death, or substantial property damage.

8.Re-install the control module cover using the nuts removed in Step 4.

Note: If the spark wire was unplugged, reattach it to the control.

9.Re-install the control panel using the two (2) screws removed in Step 3. Re-install the front access cover after fuse inspection.

10.Restore power to the water heater at the external line switch and verify water heater operation (Section 9 - Start-up in the Armor X2 Installation and Operation Manual) after completing water heater service.

38

Image 38
Contents Models 1.0, 1.3, Contents Handling ceramic fiber materials Niosh stated First AidTroubleshooting ServiceMaintenance Armor X2 display Control inputs Primary Smart Control ModuleSecondary Smart Touch Control Module Primary Control outputsSequence of operation General OperationHow the water heater operates Sequence of operation Sequence of operationThis table lists the parameters and where to access them Parameter tableBMS Viewable and changeable control parameters Status ScreenService Details Screen Service Main Screen Setup Screen Service/Setup Parameters Screen Service Set Point Parameters Screen Night Setback Parameters Screen Cascade Parameters Screen Cascade Operation10Vdc BMS Parameters Screen 10Vdc OperationService Cascade Screen Service Temps Screen Burners Screen Graph Select Screen History Screen Service Mode Screen Maintenance Maintenance and annual startup Inspect water heater area Address reported problemsClean condensate trap Inspect water heater interiorCheck expansion tank Check water heater relief valve Flue vent system and air pipingCheck water system Check control settings Check ignition ground wiring Check all water heater wiring Check flame signalOiled bearing circulators Cleaning water heater heat exchangerCheck Delta T Troubleshooting Alarm ScreenCheck control module fuses Before troubleshootingCheck the following Troubleshooting Checking temperature sensors Temperature ResistanceFault Cause Corrective Action Drain Blocked Flow SwitchCondensate Flame outWhile Running Light cont’dFlame Lost High Limit Manual ResetCont’d Temp SW Automatic ResetHigh Limit / HEX Blower RPM’sSensor Open Louver Proving SwitchToo High Sensor ShortedLow Resets Try LaterAir Flow Too Flap ValveWriting to Internal FaultNo Error Stored MemosOr Obstruction Combustion Analysis ProcedureGas Valve Adjustment Gas Supply PressureModels 1.3 Gas valve adjustment procedureModel