Lochinvar 1.3, 1.5 service manual Sequence of operation

Page 9

Service Manual

1 Service (continued)

Sequence of operation

Table 1A Sequence of operation

Note: This unit is equipped with two (2) independent, but synchronized combustion systems. One of the heat exchanger combustion systems will fire first. If the demand cannot be met by one (1) combustion system the same sequence of operation will be followed to bring the second heat exchanger combustion system online.

1.Upon a call for heat, the control turns on the appropriate pumps.

2.The control confirms that the flow switch contacts are closed.

3.The control starts the blower and closes the louver contacts to begin the Pre-Purge cycle.

4.The control confirms that the blower comes up to the desired speed, the flap valve opens, and the air pressure switch, gas pressure switch (optional), louver proving switch (optional), and blocked drain switch contacts close.

5.Once the Pre-Purge cycle is complete, the control lowers the blower speed, initiates sparking of the ignition electrode, and opens the gas valve.

6.After a short wait, the control stops sparking and checks for the presence of flame current through the spark and flame sense electrodes.

7.If the control does not detect flame current, the control will try again. If no flame current is detected on the second try, the control will lockout indefinitely until the RESET button on the touch screen LCD is pressed.

If the control detects flame current, the control will hold the blower speed constant for a few seconds to allow the

8.flame to stabilize, then begin modulating the firing rate in order to maintain the controlling sensor to the desired set point temperature.

If the first heat exchanger in the water heater is unable to maintain the desired set point temperature, the second heat exchanger in the water heater will be started, using much of the same sequences as described above. Once both

9.heat exchangers are firing, the controls will work in synchronization to maintain the desired set point temperature. If the heat load should decrease sufficiently, the second heat exchanger will be shut down, much like the sequences described below.

10.Once a call for heat is satisified, the control will turn off the gas valve and begin the Post-Purge cycle. The pumps that are running will begin their respective Pump Delay cycles.

11.At the end of the Post-Purge cycle, the louver contacts will open.

12.The control verifies that the blower stops running and the flap valve closes.

13.At the end of the Pump Delay cycle(s), the pump(s) will be turned off.

9

Image 9
Contents Models 1.0, 1.3, Contents Niosh stated First Aid Handling ceramic fiber materialsService MaintenanceTroubleshooting Armor X2 display Primary Smart Control Module Control inputsControl outputs Secondary Smart Touch Control Module PrimaryGeneral Operation How the water heater operatesSequence of operation Sequence of operation Sequence of operationParameter table This table lists the parameters and where to access themBMS Status Screen Viewable and changeable control parametersService Details Screen Service Main Screen Setup Screen Service/Setup Parameters Screen Service Set Point Parameters Screen Night Setback Parameters Screen Cascade Operation Cascade Parameters Screen10Vdc Operation 10Vdc BMS Parameters ScreenService Cascade Screen Service Temps Screen Burners Screen Graph Select Screen History Screen Service Mode Screen Maintenance Maintenance and annual startup Clean condensate trap Address reported problemsInspect water heater area Inspect water heater interiorFlue vent system and air piping Check water systemCheck expansion tank Check water heater relief valve Check all water heater wiring Check ignition ground wiringCheck control settings Check flame signalCleaning water heater heat exchanger Check Delta TOiled bearing circulators Alarm Screen TroubleshootingBefore troubleshooting Check the followingCheck control module fuses Troubleshooting Temperature Resistance Checking temperature sensorsFault Cause Corrective Action Condensate Flow SwitchDrain Blocked Flame outLight cont’d Flame LostWhile Running Manual Reset Cont’dHigh Limit High Limit / HEX Automatic ResetTemp SW Blower RPM’sToo High Louver Proving SwitchSensor Open Sensor ShortedAir Flow Too Resets Try LaterLow Flap ValveNo Error Stored Internal FaultWriting to MemosGas Valve Adjustment Combustion Analysis ProcedureOr Obstruction Gas Supply PressureGas valve adjustment procedure ModelModels 1.3