Maintenance and annual startup
Table 2A Service and Maintenance Schedules
Service technician
(see the following pages for instructions)
| General: |
|
| |
| • Address reported problems | |||
| • Inspect interior; clean and vacuum if | |||
| necessary; |
|
| |
| • Clean condensate trap and fill with fresh | |||
| water |
|
| |
| • Check for leaks (water, gas, flue, | |||
| condensate) |
|
| |
| • Verify flue and air lines in good condition | |||
| and sealed tight |
|
| |
| • Check system | water | pressure/system | |
UP- | piping/expansion tank |
| ||
• Check control settings |
| |||
|
| |||
START | • Check ignition and flame sense | |||
electrodes (sand off any deposits; clean | ||||
| ||||
ANNUAL | and reposition) |
|
| |
• Check wiring and connections | ||||
| ||||
| • Perform | |||
| performance verification per Section 9 | |||
| in the Armor X2 Installation and | |||
| Operation Manual. |
| ||
| • Flame inspection (stable, uniform) | |||
| • Flame signal (at least 10 microamps at | |||
| high fire) |
|
| |
| •Clean the heat exchanger if flue | |||
| temperature is more than 54°F (30°C) | |||
| above return water temperature. | |||
| • Test low water flow conditions. | |||
| If combustion | or | performance | |
| indicate need: |
|
|
•Clean heat exchanger
•Remove and clean burner using compressed air only
•Clean the blower wheel
Owner maintenance
| • Check water heater area |
Daily | • Check pressure/temperature |
| gauge |
| • Check vent piping |
Monthly | • Check air piping |
| • Check air and vent termination |
| screens |
| • Check relief valve |
| • Check condensate drain system |
| • Check automatic air vents |
Every
6 months
•Check water heater piping (gas and water) for leaks
•Operate relief valve