3 Troubleshooting (continued)

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

Air pressure switch contacts are open.

• Check the wiring connections to switch. Wires should

 

 

be connected to the common and normally closed

 

 

terminals.

 

 

• Vent/air intake lengths exceed the maximum allowed

 

 

lengths. Refer to Section 3 - General Venting of the

 

 

Armor X2 Installation and Operation Manual for

 

 

proper lengths.

 

 

• Check for obstruction or blockage in the vent/air

 

 

intake pipes or at terminations.

 

 

• Check reference hoses connected to the air pressure

Air Flow Too

 

switch for blockage or obstruction.

Low

 

• Inspect the burner. Reference page 35 of this manual

(will require a manual

 

for removal and cleaning procedures. Replace if

reset once the condition

 

necessary.

has been corrected.

 

• Inspect the heat exchanger. Reference page 36 of

Press the RESET button

 

on the display to reset.)

 

this manual for removal and cleaning procedures.

 

 

Replace if necessary.

 

 

• Faulty air pressure switch. Replace switch.

 

 

 

 

 

• Check the wiring connections to the flap valve switch.

 

 

Replace or repair wiring if necessary.

 

 

• Check for obstruction in the vent / air intake pipes or

 

Flap valve contacts are in an open position.

at terminations.

 

 

 

 

• Verify combustion air blower is operating. Replace if

 

 

necessary.

 

 

• Replace flap valve switch.

 

 

 

 

 

• Check wiring connections to the flap valve switch.

Flap Valve

 

Replace or repair wiring if necessary.

Flap valve contacts are in a closed position.

 

Stuck Open

• Check flap valve for obstruction or blockage.

 

 

• Replace flap valve switch.

 

 

 

Too Many

Too many manual resets have occurred

• Wait 15 minutes and try again.

• Turn power off to unit, wait 30 seconds and then turn

Resets - Try Later

during a 15 minute period.

 

 

power back on.

 

 

 

 

 

• Check 120 VAC supply to the transformer.

Voltage Too

 

• Check wiring connections at the low voltage terminal

120 VAC input to the main control board has

strip.

Low

 

dropped below 80 VAC.

• Check the wire size/length to remote devices.

 

 

 

 

 

• Replace the main control board.

 

 

 

47

Image 47
Contents Models 1.0, 1.3, Contents Niosh stated First Aid Handling ceramic fiber materialsTroubleshooting ServiceMaintenance Armor X2 display Primary Smart Control Module Control inputsControl outputs Secondary Smart Touch Control Module PrimarySequence of operation General OperationHow the water heater operates Sequence of operation Sequence of operationParameter table This table lists the parameters and where to access themBMS Status Screen Viewable and changeable control parametersService Details Screen Service Main Screen Setup Screen Service/Setup Parameters Screen Service Set Point Parameters Screen Night Setback Parameters Screen Cascade Operation Cascade Parameters Screen10Vdc Operation 10Vdc BMS Parameters ScreenService Cascade Screen Service Temps Screen Burners Screen Graph Select Screen History Screen Service Mode Screen Maintenance Maintenance and annual startup Inspect water heater interior Address reported problemsClean condensate trap Inspect water heater areaCheck expansion tank Check water heater relief valve Flue vent system and air pipingCheck water system Check flame signal Check ignition ground wiringCheck all water heater wiring Check control settingsOiled bearing circulators Cleaning water heater heat exchangerCheck Delta T Alarm Screen TroubleshootingCheck control module fuses Before troubleshootingCheck the following Troubleshooting Temperature Resistance Checking temperature sensorsFault Cause Corrective Action Flame out Flow SwitchCondensate Drain BlockedWhile Running Light cont’dFlame Lost High Limit Manual Reset Cont’d Blower RPM’s Automatic ResetHigh Limit / HEX Temp SWSensor Shorted Louver Proving SwitchToo High Sensor OpenFlap Valve Resets Try LaterAir Flow Too LowMemos Internal FaultNo Error Stored Writing toGas Supply Pressure Combustion Analysis ProcedureGas Valve Adjustment Or ObstructionModels 1.3 Gas valve adjustment procedureModel