Lochinvar 1.5, 1.3 service manual Cont’d, Manual Reset, High Limit

Page 44

Service Manual

3 Troubleshooting

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

 

 

• If 24 VAC is present at the main control board, check

 

 

the wiring between the main control board and the gas

 

 

valve. Replace the wiring if necessary. Do not

 

 

disconnect the wiring from the gas valve and attempt

 

 

to measure voltage at that point. The main control

 

 

board can detect if the gas valve is not connected and

Flame Lost

 

will display the Gas Valve / Connection fault.

 

 

• If 24 VAC is present, check the outlet of the valve to

While Running

 

 

ensure the valve is flowing gas. With a manometer

(cont’d)

The unit was running and lost the flame

connected to the outlet tap of the gas valve, when the

(will require a

signal. This condition occurred twice .

unit is in

the prepurge period, there

should be

a

manual reset once the

 

negative

pressure present. When

the valve

is

condition has been

 

 

energized a change in pressure should occur. If the

corrected. Press the

 

 

pressure change does not occur, the gas valve is not

RESET button on the

 

 

opening. Replace the gas valve.

 

 

display to reset.)

 

 

 

 

• Inspect flame sensor and associated wiring.

 

 

 

 

Reference page 35 of this manual for removal and

 

 

cleaning procedures. Replace if necessary.

 

 

 

• Inspect the burner. Reference page 35 of this manual

 

 

for removal and cleaning procedures. Replace if

 

 

necessary.

 

 

 

 

• Replace the main control board.

 

 

 

 

• Verify that the system is full of water and that all air

 

 

has been properly purged from the system.

 

 

• Verify that the water heater is piped properly into the

 

 

heating system. Refer to Section 6 - System Piping

 

 

of the Armor X2 Installation and Operation Manual

Manual Reset

 

for the proper piping methods for the Armor X2.

 

 

High Limit

 

• Check voltage to water heater pump motor on a call for

(will require a

 

heat. If voltage is not present, check wiring back to

manual reset once the

The outlet water temperature has exceeded

the pump relay.

condition has been

the setting of the high limit.

• Replace the pump relay if necessary.

corrected. Press the

 

• If 120 VAC is present on a call for heat and the water

RESET button on the

 

display to reset.)

 

heater pump is not operating, replace the pump.

 

 

 

 

• If the high limit has tripped, check setting of the

 

 

device.

 

 

• Check resistance of water sensors and compare to

 

 

Table 3B on page 40 of this manual. Replace sensor

 

 

if necessary.

 

 

• Replace high limit.

44

Image 44
Contents Models 1.0, 1.3, Contents Handling ceramic fiber materials Niosh stated First AidTroubleshooting ServiceMaintenance Armor X2 display Control inputs Primary Smart Control ModuleSecondary Smart Touch Control Module Primary Control outputsSequence of operation General OperationHow the water heater operates Sequence of operation Sequence of operationThis table lists the parameters and where to access them Parameter tableBMS Viewable and changeable control parameters Status ScreenService Details Screen Service Main Screen Setup Screen Service/Setup Parameters Screen Service Set Point Parameters Screen Night Setback Parameters Screen Cascade Parameters Screen Cascade Operation10Vdc BMS Parameters Screen 10Vdc OperationService Cascade Screen Service Temps Screen Burners Screen Graph Select Screen History Screen Service Mode Screen Maintenance Maintenance and annual startup Address reported problems Clean condensate trapInspect water heater area Inspect water heater interiorCheck expansion tank Check water heater relief valve Flue vent system and air pipingCheck water system Check ignition ground wiring Check all water heater wiringCheck control settings Check flame signalOiled bearing circulators Cleaning water heater heat exchangerCheck Delta T Troubleshooting Alarm ScreenCheck control module fuses Before troubleshootingCheck the following Troubleshooting Checking temperature sensors Temperature Resistance Fault Cause Corrective Action Flow Switch CondensateDrain Blocked Flame outWhile Running Light cont’dFlame Lost High Limit Manual ResetCont’d Automatic Reset High Limit / HEXTemp SW Blower RPM’sLouver Proving Switch Too HighSensor Open Sensor ShortedResets Try Later Air Flow TooLow Flap ValveInternal Fault No Error StoredWriting to MemosCombustion Analysis Procedure Gas Valve AdjustmentOr Obstruction Gas Supply PressureModels 1.3 Gas valve adjustment procedureModel