Service Manual
3 Troubleshooting
Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface
FAULT | DESCRIPTION | CORRECTIVE ACTION |
| |||
|
|
| ||||
|
| • If 24 VAC is present at the main control board, check | ||||
|
| the wiring between the main control board and the gas | ||||
|
| valve. Replace the wiring if necessary. Do not | ||||
|
| disconnect the wiring from the gas valve and attempt | ||||
|
| to measure voltage at that point. The main control | ||||
|
| board can detect if the gas valve is not connected and | ||||
Flame Lost |
| will display the Gas Valve / Connection fault. |
| |||
| • If 24 VAC is present, check the outlet of the valve to | |||||
While Running |
| |||||
| ensure the valve is flowing gas. With a manometer | |||||
(cont’d) | The unit was running and lost the flame | |||||
connected to the outlet tap of the gas valve, when the | ||||||
(will require a | ||||||
signal. This condition occurred twice . | unit is in | the prepurge period, there | should be | a | ||
manual reset once the | ||||||
| negative | pressure present. When | the valve | is | ||
condition has been |
| |||||
| energized a change in pressure should occur. If the | |||||
corrected. Press the |
| |||||
| pressure change does not occur, the gas valve is not | |||||
RESET button on the |
| |||||
| opening. Replace the gas valve. |
|
| |||
display to reset.) |
|
|
| |||
| • Inspect flame sensor and associated wiring. | |||||
|
| |||||
|
| Reference page 35 of this manual for removal and | ||||
|
| cleaning procedures. Replace if necessary. |
| |||
|
| • Inspect the burner. Reference page 35 of this manual | ||||
|
| for removal and cleaning procedures. Replace if | ||||
|
| necessary. |
|
| ||
|
| • Replace the main control board. |
|
|
|
| • Verify that the system is full of water and that all air | |
|
| has been properly purged from the system. | |
|
| • Verify that the water heater is piped properly into the | |
|
| heating system. Refer to Section 6 - System Piping | |
|
| of the Armor X2 Installation and Operation Manual | |
Manual Reset |
| for the proper piping methods for the Armor X2. | |
|
| ||
High Limit |
| • Check voltage to water heater pump motor on a call for | |
(will require a |
| heat. If voltage is not present, check wiring back to | |
manual reset once the | The outlet water temperature has exceeded | the pump relay. | |
condition has been | the setting of the high limit. | • Replace the pump relay if necessary. | |
corrected. Press the | |||
| • If 120 VAC is present on a call for heat and the water | ||
RESET button on the |
| ||
display to reset.) |
| heater pump is not operating, replace the pump. | |
|
| ||
|
| • If the high limit has tripped, check setting of the | |
|
| device. | |
|
| • Check resistance of water sensors and compare to | |
|
| Table 3B on page 40 of this manual. Replace sensor | |
|
| if necessary. | |
|
| • Replace high limit. |
44