Raypak 503-2003 manual Gas Supply Connection, Gas Supply Pressure

Page 19

Further advice should be obtained from your pool or spa builder, accredited pool shop, or chemical suppli- er for the correct levels for your water.

Automatic Chlorinators and

Chemical Feeders

All chemicals must be introduced and completely dilut- ed into the pool or spa water before being circulated through the heater. Do not place sanitizing chemicals in the skimmer. High chemical concentrations will result when the pump is not running (e.g. overnight).

Chlorinators must feed downstream of the heater and have an anti-siphoning device to prevent chemical back-up into the heater when the pump is shut off.

NOTE: High chemical concentrates from feeders and chlorinators that are out of adjustment will cause rapid corrosion to the heat exchanger. Such damage is not covered under the warranty.

NOTE: Failure of a heat exchanger due to lime scale build-up on the heating surface, low pH or other chemical imbalance is non-warrantable.

Gas Supply

DANGER: Make sure the gas on which the heater will operate is the same type as specified on the heater’s rating plate.

Gas piping must have a sediment trap ahead of the heater gas controls, and a manual shut-off valve lo- cated outside the heater jacket. It is recommended that a union be installed in the gas supply piping adja- cent to the heater for servicing. The gas supply pressure to the heater must not exceed 10.5 in. WC for natural gas or 13.0 in. WC for propane gas. A pounds- to-inches regulator must be installed to reduce the gas supply pressure if it is higher than noted above. This regulator should be placed a minimum distance of 10 times the pipe diameter upstream of the heater gas controls. Refer to Table I for maximum pipe lengths.

Gas Supply Connection

CAUTION: The heater must be disconnected from the gas supply during any pressure testing of the gas supply system at test pressures in excess of 1/2 psi (3.45 kPa).

The heater must be isolated from the gas supply pip- ing system by closing the upstream manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.45 kPa). Relieve test pressure in the gas supply line prior to re-connecting the heater and its manual shut-off valve to the gas supply line. FAILURE

TO FOLLOW THIS PROCEDURE MAY DAMAGE THE GAS VALVE. Over-pressurized gas valves are not covered by warranty. The heater and its gas con- nections shall be leak-tested before placing the appliance in operation. Use soapy water for leak test. DO NOT use an open flame.

Fig. 17: GasSupply Connection

CAUTION: Do not use Teflon tape on gas line pipe thread. A pipe compound rated for use with natural and propane gases is recommended. Apply sparingly only on male pipe ends, leaving the two end threads bare.

CAUTION: Support gas supply piping with hangers, not by the heater or its accessories. Make sure the gas piping is protected from physical damage and freezing, where required.

Gas Supply Pressure

A minimum of 4.0 in. WC and a maximum of 10.5 in. WC upstream gas pressure is required under load and no-load conditions for natural gas. A minimum of 4.0 in. WC and a maximum of 13.0 in. WC is required for propane gas. The gas pressure regulator(s) supplied on the heater is for low-pressure service. If upstream pressure exceeds these values, an intermediate gas pressure regulator, of the lockup type, must be installed.

When connecting additional gas utilization equipment to the gas piping system, the existing piping must be checked to determine if it has adequate capacity for the combined load.

19

Image 19
Contents Reference Catalog no .53G Effective Replaces 241288 Rev Do so may result in an explosion or firePage Contents Pay Attention to These Terms Model Identification Before InstallationInstallations at Elevation Product ReceiptGeneral Information Component LocationsTime/Temperature Relationships in Scalds General SafetyWater Time to Produce Serious Temp Burn Equipment Base InstallationInstallation Codes Indoor InstallationsCombustion and Ventilation Air Outdoor InstallationsIndoor Units Table E Vent/Air Inlet Termination Clearances Direct Vent InstallationsConventional Combustion Air Supply Air FilterWater Piping Canadian InstallationsGeneral Hydrostatic Test Relief Valve Piping Temperature & Pressure GaugeCold Water Operation Cold Water Starts Hydronic HeatingPump Selection Feedwater RegulatorAir-Separation/Expansion Tank PipingModel 20F 30F 40F Min. Flow Max. Flow Gpm Pool Heating Three-Way ValvesDomestic Hot Water Potable Water and Space HeatingMake final adjustments when pool water approaches Winterizing Your Heater Pool/Spa Water ChemistryExceed 5 ppm Automatic Chlorinators Chemical Feeders Gas SupplyGas Supply Connection Gas Supply PressureHigh Fire Values Electrical Power ConnectionsModel In. NPT 4 in. NPT 2 in. NPT Manifold Gas Pressure ModelField-Connected Controllers Check the Power SourceMaking the Electrical Connections Venting Field Wiring ConnectionAppliance Categories Support of Vent Stack InstallationsVent Terminal Location Installation Venting Installation TipsVenting Configurations Canadian InstallationsCpvc TerminationModel Pressure Flue Products VolumeCommon Venting VentHorizontal Through-the-Wall Venting Horizontal Through-the-Wall Direct Venting Category10 Ø Direct Vent-VerticalModel Certified Combustion Air Air Inlet Horizontal Max. Length** ft VentOutdoor Installation Freeze Protection ControlsOperating Modes Mode 2 Primary/Secondary Piping Mode 7 Primary/Secondary Piping with External Target Temp 10 VDC 20 mA Modes Default Setting Range10 VDC 20 mA Boiler Target Definitions Operation Number Field Type Fault DescriptionRank Code Condition High Limit-Manual ResetHeater Sequence of Operation Ignition ModuleHigh & Low Gas Pressure Switches Optional High Limit-Auto Reset OptionalModulating Temperature Control Flow SwitchBlocked Vent Switch Air Pressure SwitchUDB Diagnostic Board Wiring Diagrams Models Models Initial Start-up START-UPPre Start-up Pre Start-up CheckStart-Up PreparationBlower Check Manifold Check Safety InspectionModel Air Pressure Setting Setting in. WC Model Amp Draw SettingFollow-Up Leak Test Procedure Dual-Seat Gas ValveLighting Instructions OperationPost Start-Up Check To Turn Off Gas To Appliance Step TroubleshootingUDB Fault History MaintenanceSuggested Minimum Maintenance Schedule Semi-Annually Preventive Maintenance SchedulePeriodically WeeklyFilter Replacement Filter MaintenanceAs Required Inside Air Contamination AppendixImportant Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products
Related manuals
Manual 58 pages 52.53 Kb

503-2003 specifications

The Raypak 503-2003 is a notable entry in the world of water heating solutions, renowned for its efficiency and reliability in both residential and commercial settings. This model is designed to provide exceptional performance while maintaining ease of use and minimization of environmental impact.

One of the standout features of the Raypak 503-2003 is its advanced heating technology. The unit utilizes a durable, copper heat exchanger which ensures quick and efficient heating of water. This heat exchanger is known for its ability to transfer heat effectively, leading to reduced energy consumption and lower utility bills. The design also allows for a seamless operation, ensuring that the system heats water swiftly without sacrificing performance.

In addition to its efficient heating capabilities, the Raypak 503-2003 is equipped with innovative controls. The digital control panel allows users to easily set and adjust the desired water temperature. This feature provides a level of convenience that simplifies operation while enhancing user experience. Furthermore, the smart technology employed in the unit ensures that it operates within optimal parameters, avoiding unnecessary energy expenditure.

Durability is another hallmark of the Raypak 503-2003. Built with heavy-duty components, this water heating solution is designed to withstand the rigors of continuous use. The rugged construction ensures longevity, making it a cost-effective investment for homeowners and businesses alike. Moreover, the unit is designed to be resistant to corrosion and wear, further extending its lifespan and reliability.

The energy efficiency of the Raypak 503-2003 is a crucial characteristic that sets it apart from competitors. Rated with a high efficiency score, this model contributes to lower emissions and is environmentally friendly. It adheres to various energy standards, making it a suitable choice for those looking to reduce their carbon footprint while enjoying reliable water heating.

Noise reduction is another important feature of the Raypak 503-2003. Designed with quiet operation in mind, the unit operates with minimal noise pollution, allowing for a pleasant environment in both residential and commercial spaces.

In summary, the Raypak 503-2003 combines advanced heating technology, user-friendly controls, durability, and energy efficiency into a robust water heating system. This makes it an excellent choice for those in need of dependable and sustainable heating solutions. Whether for daily home use or for larger commercial applications, the Raypak 503-2003 stands out as a leader in its class.