Raypak 503-2003 manual Relief Valve Piping Temperature & Pressure Gauge, Hydrostatic Test

Page 13

CAUTION: This heater requires forced water circulation when the burner is operating. See Table F and Table G for minimum and maximum flow rates and water pump selection. The pump must be interlocked with the heater to prevent heater operation without water circulation.

NOTE: Minimum pipe size for in/out connections is 2 in. NPT for 503 and 753 models and 2-12in NPT for 1003–2003 models. Verify proper flow rates and ∆T as instructed in this manual.

Relief Valve Piping

WARNING: Pressure relief valve discharge piping must be piped near the floor and close to a drain to eliminate the potential of severe burns. Do not pipe to any area where freezing could occur. Refer to local codes.

Temperature & Pressure Gauge

The temperature and pressure gauge is shipped loose for field installation and must be installed within 12 inches of the boiler outlet (if possible) in an easily readable location. Installation must comply with ASME Section IV as well as all applicable national, state and local codes.

Hydrostatic Test

Unlike many types of heaters, this heater does not re- quire hydrostatic testing prior to being placed in operation. The heat exchanger has already been fac- tory-tested and is rated for 160 psi operating pressure. However, Raypak does recommend hydrostatic test- ing of the piping connections to the heater and the rest of the system prior to operation. This is particularly true for hydronic systems using expensive glycol- based anti-freeze. Raypak recommends conducting the hydrostatic test before connecting gas piping or electrical supply.

Leaks must be repaired at once to prevent damage to the heater. NEVER use petroleum-based stop-leak compounds.

To perform hydrostatic test:

1.Connect fill water supply. With bleed valve open, fill heater with water. When water flows from bleed valve, shut off water. Close bleed valve. Carefully fill the rest of the system, making sure to eliminate any entrapped air by using high-point vents. Close

feed valve. Test at standard operating pressure for at least 24 hours.

2.Make sure constant gauge pressure has been maintained throughout test.

3.Check for leaks. Repair if found.

Cold Water Operation

CAUTION: Damage due to internal condensation may occur if the heater inlet water temperature does not exceed 120°F (49°C) within 7 minutes of start- up.

This heater is equipped with a proprietary condensate evaporation system which will evaporate any conden- sate that may begin to accumulate inside the primary heat exchanger with water temperatures as low as 120°F (49°C).

Heaters operated with an inlet temperature of less than 120°F (49°C) MUST have a manual bypass (see Fig. 16) or an approved low-temperature operation system (Figs. 9 and 10) to prevent problems with con- densation. This piping is similar to a primary/secondary boiler installation with a bypass acting as the secondary boiler piping. Raypak strong- ly recommends that thermometer(s) be placed into the heater piping next to the in/out header to facilitate tem- perature adjustment. Inlet water temperatures below 120°F (49°C) can excessively cool the products of combustion, resulting in collection of condensate in the heat exchanger area beyond the capacity of the con- densate evaporation system.

Failure to reach or exceed 120°F (49°C) within 7 min- utes may damage or cause failure of the heat exchanger, combustion chamber, or other parts within the combustion chamber. It can cause operational problems, bad combustion, sooting, flue gas leakage and reduced service life of the appliance and the vent system. A bypass allows part of the heater discharge water to be mixed with the cooler water returning to the heater inlet to increase the heater inlet temperature above 120°F (49°C). This precautionary measure should prevent the products of combustion from con- densing beyond the ability of the condensate management system employed in this heater in most installations. Warranty claims will be denied for damage or failures caused by condensation.

Cold water operation issues are applicable to both cold water start and cold water run applications. Cold water operation for 7 minutes or less on initial daily start-up is acceptable. Where cold water starts will last

13

Image 13
Contents Reference Catalog no .53G Effective Replaces 241288 Rev Do so may result in an explosion or firePage Contents Pay Attention to These Terms Installations at Elevation Before InstallationProduct Receipt Model IdentificationGeneral Information Component LocationsTime/Temperature Relationships in Scalds General SafetyWater Time to Produce Serious Temp Burn Installation Codes InstallationIndoor Installations Equipment BaseCombustion and Ventilation Air Outdoor InstallationsIndoor Units Table E Vent/Air Inlet Termination Clearances Conventional Combustion Air Supply InstallationsAir Filter Direct VentWater Piping Canadian InstallationsGeneral Hydrostatic Test Relief Valve Piping Temperature & Pressure GaugeCold Water Operation Pump Selection Hydronic HeatingFeedwater Regulator Cold Water StartsAir-Separation/Expansion Tank PipingModel 20F 30F 40F Min. Flow Max. Flow Gpm Domestic Hot Water Three-Way ValvesPotable Water and Space Heating Pool HeatingMake final adjustments when pool water approaches Winterizing Your Heater Pool/Spa Water ChemistryExceed 5 ppm Gas Supply Connection Gas SupplyGas Supply Pressure Automatic Chlorinators Chemical FeedersModel In. NPT 4 in. NPT 2 in. NPT Electrical Power ConnectionsManifold Gas Pressure Model High Fire ValuesField-Connected Controllers Check the Power SourceMaking the Electrical Connections Venting Field Wiring ConnectionAppliance Categories Support of Vent Stack InstallationsVent Terminal Location Venting Configurations Venting Installation TipsCanadian Installations InstallationCpvc TerminationCommon Venting VolumeVent Model Pressure Flue ProductsHorizontal Through-the-Wall Venting Horizontal Through-the-Wall Direct Venting CategoryModel Certified Direct Vent-VerticalCombustion Air Air Inlet Horizontal Max. Length** ft Vent 10 ØOutdoor Installation Freeze Protection ControlsOperating Modes Mode 2 Primary/Secondary Piping Mode 7 Primary/Secondary Piping with External Target Temp 10 VDC 20 mA Modes Default Setting Range10 VDC 20 mA Boiler Target Definitions Operation Number Field Type Fault DescriptionRank Heater Sequence of Operation High Limit-Manual ResetIgnition Module Code ConditionModulating Temperature Control High Limit-Auto Reset OptionalFlow Switch High & Low Gas Pressure Switches OptionalBlocked Vent Switch Air Pressure SwitchUDB Diagnostic Board Wiring Diagrams Models Models Pre Start-up START-UPPre Start-up Check Initial Start-upStart-Up PreparationBlower Check Model Air Pressure Setting Setting in. WC Safety InspectionModel Amp Draw Setting Manifold CheckFollow-Up Leak Test Procedure Dual-Seat Gas ValveLighting Instructions OperationPost Start-Up Check To Turn Off Gas To Appliance Step TroubleshootingUDB Fault History MaintenanceSuggested Minimum Maintenance Schedule Periodically Preventive Maintenance ScheduleWeekly Semi-AnnuallyFilter Replacement Filter MaintenanceAs Required Inside Air Contamination AppendixImportant Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products
Related manuals
Manual 58 pages 52.53 Kb

503-2003 specifications

The Raypak 503-2003 is a notable entry in the world of water heating solutions, renowned for its efficiency and reliability in both residential and commercial settings. This model is designed to provide exceptional performance while maintaining ease of use and minimization of environmental impact.

One of the standout features of the Raypak 503-2003 is its advanced heating technology. The unit utilizes a durable, copper heat exchanger which ensures quick and efficient heating of water. This heat exchanger is known for its ability to transfer heat effectively, leading to reduced energy consumption and lower utility bills. The design also allows for a seamless operation, ensuring that the system heats water swiftly without sacrificing performance.

In addition to its efficient heating capabilities, the Raypak 503-2003 is equipped with innovative controls. The digital control panel allows users to easily set and adjust the desired water temperature. This feature provides a level of convenience that simplifies operation while enhancing user experience. Furthermore, the smart technology employed in the unit ensures that it operates within optimal parameters, avoiding unnecessary energy expenditure.

Durability is another hallmark of the Raypak 503-2003. Built with heavy-duty components, this water heating solution is designed to withstand the rigors of continuous use. The rugged construction ensures longevity, making it a cost-effective investment for homeowners and businesses alike. Moreover, the unit is designed to be resistant to corrosion and wear, further extending its lifespan and reliability.

The energy efficiency of the Raypak 503-2003 is a crucial characteristic that sets it apart from competitors. Rated with a high efficiency score, this model contributes to lower emissions and is environmentally friendly. It adheres to various energy standards, making it a suitable choice for those looking to reduce their carbon footprint while enjoying reliable water heating.

Noise reduction is another important feature of the Raypak 503-2003. Designed with quiet operation in mind, the unit operates with minimal noise pollution, allowing for a pleasant environment in both residential and commercial spaces.

In summary, the Raypak 503-2003 combines advanced heating technology, user-friendly controls, durability, and energy efficiency into a robust water heating system. This makes it an excellent choice for those in need of dependable and sustainable heating solutions. Whether for daily home use or for larger commercial applications, the Raypak 503-2003 stands out as a leader in its class.