Raypak 503-2003 manual Field-Connected Controllers, Check the Power Source

Page 21

WARNING: Using a multi-meter, check the following voltages at the circuit breaker panel prior to connecting any equipment. Make sure proper polarity is followed and house ground is proven. (See Fig. 19.)

Check the power source:

AC = 108 VAC Minimum, 132 VAC MAX AB = 108 VAC Minimum, 132 VAC MAX BC = <1 VAC Maximum

FRONT WIRING PANEL LOW VOLTAGE ELECTRICAL CONNECTIONS

Fig. 18: Wiring Electrical Connections

Field-Connected Controllers

It is strongly recommended that all individually-pow- ered control modules and the heater should be supplied from the same power source.

NOTE: Field-supplied isolation relays should be installed when field- connecte d controllers are mounted more than 50 equivalent feet (18 AWG) from heater. See wiring diagrams.

NOTE: Minimum 18 AWG, 105°C, stranded wire must be used for all low voltage (less than 30 volts) external connections to the unit. Solid conductors should not be used because they can cause excessive tension on contact points. Install conduit as appropriate. All high voltage wires must be the same size (105°C, stranded wire) as the ones on the unit or larger.

Check the Power Source

BLACK CIRCUIT

BREAKER

WHITE

GREEN

GROUND

A B C

Fig. 19: Wiring Connections

Fig. 20: Multi-meter

Making the Electrical Connections

Refer to Fig. 18-21.

1.Verify that circuit breaker is properly sized by referring to heater rating plate. A dedicated circuit breaker should be provided.

2.NOTE: Current draw noted on rating plate does not include pump current.

3.Turn off all power to the heater. Verify that power has been turned off by testing with a multi-meter prior to working with any electrical connections or components.

4.Observe proper wire colors while making electri- cal connections. Many electronic controls are polarity sensitive. Components damaged by im- proper electrical installation are not covered by warranty.

5.Provide overload protection and a disconnect means for equipment serviceability as required by local and state code.

6.Install heater controls, thermostats, or building management systems in accordance with the applicable manufacturers’ instructions.

7.Conduit should not be used as the earth ground.

21

Image 21
Contents Reference Catalog no .53G Effective Replaces 241288 Rev Do so may result in an explosion or firePage Contents Pay Attention to These Terms Installations at Elevation Before InstallationProduct Receipt Model IdentificationGeneral Information Component LocationsGeneral Safety Time/Temperature Relationships in ScaldsWater Time to Produce Serious Temp Burn Installation Codes InstallationIndoor Installations Equipment BaseOutdoor Installations Combustion and Ventilation AirIndoor Units Table E Vent/Air Inlet Termination Clearances Conventional Combustion Air Supply InstallationsAir Filter Direct VentCanadian Installations Water PipingGeneral Relief Valve Piping Temperature & Pressure Gauge Hydrostatic TestCold Water Operation Pump Selection Hydronic HeatingFeedwater Regulator Cold Water StartsPiping Air-Separation/Expansion TankModel 20F 30F 40F Min. Flow Max. Flow Gpm Domestic Hot Water Three-Way ValvesPotable Water and Space Heating Pool HeatingMake final adjustments when pool water approaches Pool/Spa Water Chemistry Winterizing Your HeaterExceed 5 ppm Gas Supply Connection Gas SupplyGas Supply Pressure Automatic Chlorinators Chemical FeedersModel In. NPT 4 in. NPT 2 in. NPT Electrical Power ConnectionsManifold Gas Pressure Model High Fire ValuesCheck the Power Source Field-Connected ControllersMaking the Electrical Connections Field Wiring Connection VentingAppliance Categories Installations Support of Vent StackVent Terminal Location Venting Configurations Venting Installation TipsCanadian Installations InstallationCpvc TerminationCommon Venting VolumeVent Model Pressure Flue ProductsHorizontal Through-the-Wall Venting Horizontal Through-the-Wall Direct Venting CategoryModel Certified Direct Vent-VerticalCombustion Air Air Inlet Horizontal Max. Length** ft Vent 10 ØOutdoor Installation Controls Freeze ProtectionOperating Modes Mode 2 Primary/Secondary Piping Mode 7 Primary/Secondary Piping with External Target Temp Modes Default Setting Range 10 VDC 20 mA10 VDC 20 mA Boiler Target Definitions Number Field Type Fault Description OperationRank Heater Sequence of Operation High Limit-Manual ResetIgnition Module Code ConditionModulating Temperature Control High Limit-Auto Reset OptionalFlow Switch High & Low Gas Pressure Switches OptionalAir Pressure Switch Blocked Vent SwitchUDB Diagnostic Board Wiring Diagrams Models Models Pre Start-up START-UPPre Start-up Check Initial Start-upPreparation Start-UpBlower Check Model Air Pressure Setting Setting in. WC Safety InspectionModel Amp Draw Setting Manifold CheckFollow-Up Leak Test Procedure Dual-Seat Gas ValveOperation Lighting InstructionsPost Start-Up Check To Turn Off Gas To Appliance Step TroubleshootingMaintenance UDB Fault HistorySuggested Minimum Maintenance Schedule Periodically Preventive Maintenance ScheduleWeekly Semi-AnnuallyFilter Maintenance Filter ReplacementAs Required Inside Air Contamination AppendixImportant Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products
Related manuals
Manual 58 pages 52.53 Kb

503-2003 specifications

The Raypak 503-2003 is a notable entry in the world of water heating solutions, renowned for its efficiency and reliability in both residential and commercial settings. This model is designed to provide exceptional performance while maintaining ease of use and minimization of environmental impact.

One of the standout features of the Raypak 503-2003 is its advanced heating technology. The unit utilizes a durable, copper heat exchanger which ensures quick and efficient heating of water. This heat exchanger is known for its ability to transfer heat effectively, leading to reduced energy consumption and lower utility bills. The design also allows for a seamless operation, ensuring that the system heats water swiftly without sacrificing performance.

In addition to its efficient heating capabilities, the Raypak 503-2003 is equipped with innovative controls. The digital control panel allows users to easily set and adjust the desired water temperature. This feature provides a level of convenience that simplifies operation while enhancing user experience. Furthermore, the smart technology employed in the unit ensures that it operates within optimal parameters, avoiding unnecessary energy expenditure.

Durability is another hallmark of the Raypak 503-2003. Built with heavy-duty components, this water heating solution is designed to withstand the rigors of continuous use. The rugged construction ensures longevity, making it a cost-effective investment for homeowners and businesses alike. Moreover, the unit is designed to be resistant to corrosion and wear, further extending its lifespan and reliability.

The energy efficiency of the Raypak 503-2003 is a crucial characteristic that sets it apart from competitors. Rated with a high efficiency score, this model contributes to lower emissions and is environmentally friendly. It adheres to various energy standards, making it a suitable choice for those looking to reduce their carbon footprint while enjoying reliable water heating.

Noise reduction is another important feature of the Raypak 503-2003. Designed with quiet operation in mind, the unit operates with minimal noise pollution, allowing for a pleasant environment in both residential and commercial spaces.

In summary, the Raypak 503-2003 combines advanced heating technology, user-friendly controls, durability, and energy efficiency into a robust water heating system. This makes it an excellent choice for those in need of dependable and sustainable heating solutions. Whether for daily home use or for larger commercial applications, the Raypak 503-2003 stands out as a leader in its class.