Raypak 503-2003 Venting Installation Tips, Venting Configurations, Vertical Venting Category

Page 24

1.Vent must terminate at least 4 ft below, 4 ft hori- zontally from or 1 ft above any door, window or gravity air inlet to the building.

2.The vent must not be less than 7 ft above grade when located adjacent to public walkways.

3.Terminate vent at least 3 ft above any forced air inlet located within 10 ft.

4.Vent must terminate at least 4 ft horizontally, and in no case above or below unless 4 ft horizontal distance is maintained, from electric meters, gas meters, regulators, and relief equipment.

5.Terminate vent at least 6 ft away from adjacent walls.

6.DO NOT terminate vent closer than 5 ft below roof overhang.

7.The vent terminal requires a 12 in. vent terminal clearance from the wall.

8.Terminate vent at least 1 ft above grade, including normal snow line.

9.Multiple direct vent installations require a 4 ft clearance between the ends of vent caps located on the same horizontal plane.

WARNING: The Commonwealth of Massachusetts requires that sidewall vented heaters, installed in every dwelling, building or structure used in whole or in part for residential purposes, be installed using special provisions as outlined on page 55 of this manual.

Canadian Installations

Refer to latest edition of the B149 Installation Code. A vent shall not terminate:

1.Directly above a paved sidewalk or driveway which is located between two single-family dwell- ings and serves both dwellings.

2.Less than 7 ft (2.13 m) above a paved sidewalk or paved driveway located on public property.

3.Within 6 ft (1.8 m) of a mechanical air supply inlet to any building.

4.Above a meter/regulator assembly within 3 ft (915

mm)horizontally of the vertical centre-line of the regulator.

24

5.Within 6 ft (1.8 m) of any gas service regulator vent outlet.

6.Less than 1 ft (305 mm) above grade level.

7.Within 3 ft (915 mm) of a window or door which can be opened in any building, any non-mechani- cal air supply inlet to any building or the combustion air inlet of any other appliance.

8.Underneath a verandah, porch or deck, unless the verandah, porch or deck is fully open on a mini- mum of two sides beneath the floor, and the distance between the top of the vent termination and the underside of the verandah, porch or deck is greater than 1 ft (305 mm).

Venting Installation Tips

Support piping:

horizontal runs—at least every 5 ft (1.5m)

vertical runs—use braces

under or near elbows

WARNING: Examine the venting system at least once a year. Check all joints and vent pipe connections for tightness, corrosion or deterioration.

Venting Configurations

For heaters connected to gas vents or chimneys, vent installations shall be in accordance with the NFGC (U.S.), or B149 (Canada), or applicable provisions of local building codes.

Vertical Venting (Category IV)

CAUTION: This venting system requires the installation of a condensate drain in the vent piping per the vent manufacturer’s instructions. Failure to install a condensate drain in the venting system will void all warranties on this heater.

Installation

The maximum and minimum venting length for this Category IV appliance shall be determined per the NFGC (U.S.) or B149 (Canada).

The diameter of vent flue pipe should be sized accord- ing to the NFGC (U.S.) and Appendix B of B149 (Canada). The minimum flue pipe diameter for con- ventional venting using Category IV, stainless steel

Image 24
Contents Do so may result in an explosion or fire Reference Catalog no .53G Effective Replaces 241288 RevPage Contents Pay Attention to These Terms Before Installation Installations at ElevationProduct Receipt Model IdentificationComponent Locations General InformationGeneral Safety Time/Temperature Relationships in ScaldsWater Time to Produce Serious Temp Burn Installation Installation CodesIndoor Installations Equipment BaseOutdoor Installations Combustion and Ventilation AirIndoor Units Table E Vent/Air Inlet Termination Clearances Installations Conventional Combustion Air SupplyAir Filter Direct VentCanadian Installations Water PipingGeneral Relief Valve Piping Temperature & Pressure Gauge Hydrostatic TestCold Water Operation Hydronic Heating Pump SelectionFeedwater Regulator Cold Water StartsPiping Air-Separation/Expansion TankModel 20F 30F 40F Min. Flow Max. Flow Gpm Three-Way Valves Domestic Hot WaterPotable Water and Space Heating Pool HeatingMake final adjustments when pool water approaches Pool/Spa Water Chemistry Winterizing Your HeaterExceed 5 ppm Gas Supply Gas Supply ConnectionGas Supply Pressure Automatic Chlorinators Chemical FeedersElectrical Power Connections Model In. NPT 4 in. NPT 2 in. NPTManifold Gas Pressure Model High Fire ValuesCheck the Power Source Field-Connected ControllersMaking the Electrical Connections Field Wiring Connection VentingAppliance Categories Installations Support of Vent StackVent Terminal Location Venting Installation Tips Venting ConfigurationsCanadian Installations InstallationTermination CpvcVolume Common VentingVent Model Pressure Flue ProductsHorizontal Through-the-Wall Direct Venting Category Horizontal Through-the-Wall VentingDirect Vent-Vertical Model CertifiedCombustion Air Air Inlet Horizontal Max. Length** ft Vent 10 ØOutdoor Installation Controls Freeze ProtectionOperating Modes Mode 2 Primary/Secondary Piping Mode 7 Primary/Secondary Piping with External Target Temp Modes Default Setting Range 10 VDC 20 mA10 VDC 20 mA Boiler Target Definitions Number Field Type Fault Description OperationRank High Limit-Manual Reset Heater Sequence of OperationIgnition Module Code ConditionHigh Limit-Auto Reset Optional Modulating Temperature ControlFlow Switch High & Low Gas Pressure Switches OptionalAir Pressure Switch Blocked Vent SwitchUDB Diagnostic Board Wiring Diagrams Models Models START-UP Pre Start-upPre Start-up Check Initial Start-upPreparation Start-UpBlower Check Safety Inspection Model Air Pressure Setting Setting in. WCModel Amp Draw Setting Manifold CheckLeak Test Procedure Dual-Seat Gas Valve Follow-UpOperation Lighting InstructionsPost Start-Up Check To Turn Off Gas To Appliance Troubleshooting StepMaintenance UDB Fault HistorySuggested Minimum Maintenance Schedule Preventive Maintenance Schedule PeriodicallyWeekly Semi-AnnuallyFilter Maintenance Filter ReplacementAs Required Appendix Inside Air ContaminationImportant Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products
Related manuals
Manual 58 pages 52.53 Kb

503-2003 specifications

The Raypak 503-2003 is a notable entry in the world of water heating solutions, renowned for its efficiency and reliability in both residential and commercial settings. This model is designed to provide exceptional performance while maintaining ease of use and minimization of environmental impact.

One of the standout features of the Raypak 503-2003 is its advanced heating technology. The unit utilizes a durable, copper heat exchanger which ensures quick and efficient heating of water. This heat exchanger is known for its ability to transfer heat effectively, leading to reduced energy consumption and lower utility bills. The design also allows for a seamless operation, ensuring that the system heats water swiftly without sacrificing performance.

In addition to its efficient heating capabilities, the Raypak 503-2003 is equipped with innovative controls. The digital control panel allows users to easily set and adjust the desired water temperature. This feature provides a level of convenience that simplifies operation while enhancing user experience. Furthermore, the smart technology employed in the unit ensures that it operates within optimal parameters, avoiding unnecessary energy expenditure.

Durability is another hallmark of the Raypak 503-2003. Built with heavy-duty components, this water heating solution is designed to withstand the rigors of continuous use. The rugged construction ensures longevity, making it a cost-effective investment for homeowners and businesses alike. Moreover, the unit is designed to be resistant to corrosion and wear, further extending its lifespan and reliability.

The energy efficiency of the Raypak 503-2003 is a crucial characteristic that sets it apart from competitors. Rated with a high efficiency score, this model contributes to lower emissions and is environmentally friendly. It adheres to various energy standards, making it a suitable choice for those looking to reduce their carbon footprint while enjoying reliable water heating.

Noise reduction is another important feature of the Raypak 503-2003. Designed with quiet operation in mind, the unit operates with minimal noise pollution, allowing for a pleasant environment in both residential and commercial spaces.

In summary, the Raypak 503-2003 combines advanced heating technology, user-friendly controls, durability, and energy efficiency into a robust water heating system. This makes it an excellent choice for those in need of dependable and sustainable heating solutions. Whether for daily home use or for larger commercial applications, the Raypak 503-2003 stands out as a leader in its class.