Heater Sequence of Operation

If all limits are satisfied and there is a call for heat:

1.The heater pump is powered and begins circulat- ing water through the heat exchanger.

2.The blower is powered and goes through a 15 sec- ond prepurge beginning when air flow is proven by closure of the blower suction air pressure switch.

3.The igniter is powered, and once proven, heats up for 20 seconds.

4.The gas valve is then energized for a 4 second trial for ignition period. Trial for ignition is fixed at 50% input. The heater is allowed to modulate once flame is proven and the firing rate will adjust to match the load based on the configuration and set- tings of the temperature control or external input.

5.Once the heat demand is satisfied the gas valve will close and the blower will run a 30 second post purge. The heater pump will continue to circulate water for 0 to 10 minutes depending on the pump delay setting on the Raypak modulating tempera- ture control.

Ignition Module

When additional heat is needed, the combustion air blower starts to purge air from the combustion cham- ber for 15 seconds. On proof-of-air flow, the air-proving switch closes and the igniter is energized. To ensure safe operation, the gas valve cannot open until the igniter is verified. The main burner is automat- ically lit when the device is powered and pre-purged. The heater performs its own safety check and opens the main valve only after the igniter is proven to be capable of ignition. The standard ignition module will attempt to light three times before locking out. To reset it, turn off power to the heater, wait 30 seconds and re- apply power.

Fig. 37: Ignition Module

The optional single-try ignition module will lock out after failing to light one time. To reset it, press and release the small, recessed black push button located inside of the cut-out on the lower right-hand corner of the ignition module case. Turning off the power to the heater WILL NOT reset the ignition module.

Code

Condition

 

 

On

System OK; No faults present

 

 

Off

Possible control fault; Check power

 

 

1 Flash

Low air

 

 

2 Flashes

Flame in combustion chamber;

No call for heat

 

 

 

3 Flashes

Ignition lockout

 

 

4 Flashes

Low HSI current

 

 

5 Flashes

Low 24 VAC

 

 

6 Flashes

Internal fault; Replace control

Table S: Ignition Module Diagnostic LED Flash Codes

High Limit—Manual Reset

This heater is equipped with a fixed setting manual re- set high limit temperature device as standard or it may have an optional adjustable setting manual reset high temperature device.

The fixed setting manual reset high limit is located on the In/Out header of the heat exchanger on the right side of the heater (accessible through the front door for reset as necessary).

The optional adjustable manual reset high limit is lo- cated inside the heater junction box. Push the reset button and adjust the setting to approx. 40°F (20°C) above desired outlet temperature.

36

Image 36
Contents Do so may result in an explosion or fire Reference Catalog no .53G Effective Replaces 241288 RevPage Contents Pay Attention to These Terms Before Installation Installations at ElevationProduct Receipt Model IdentificationComponent Locations General InformationGeneral Safety Time/Temperature Relationships in ScaldsWater Time to Produce Serious Temp Burn Installation Installation CodesIndoor Installations Equipment BaseOutdoor Installations Combustion and Ventilation AirIndoor Units Table E Vent/Air Inlet Termination Clearances Installations Conventional Combustion Air SupplyAir Filter Direct VentCanadian Installations Water PipingGeneral Relief Valve Piping Temperature & Pressure Gauge Hydrostatic TestCold Water Operation Hydronic Heating Pump SelectionFeedwater Regulator Cold Water StartsPiping Air-Separation/Expansion TankModel 20F 30F 40F Min. Flow Max. Flow Gpm Three-Way Valves Domestic Hot WaterPotable Water and Space Heating Pool HeatingMake final adjustments when pool water approaches Pool/Spa Water Chemistry Winterizing Your HeaterExceed 5 ppm Gas Supply Gas Supply ConnectionGas Supply Pressure Automatic Chlorinators Chemical FeedersElectrical Power Connections Model In. NPT 4 in. NPT 2 in. NPTManifold Gas Pressure Model High Fire ValuesCheck the Power Source Field-Connected ControllersMaking the Electrical Connections Field Wiring Connection VentingAppliance Categories Installations Support of Vent StackVent Terminal Location Venting Installation Tips Venting ConfigurationsCanadian Installations InstallationTermination CpvcVolume Common VentingVent Model Pressure Flue ProductsHorizontal Through-the-Wall Direct Venting Category Horizontal Through-the-Wall VentingDirect Vent-Vertical Model CertifiedCombustion Air Air Inlet Horizontal Max. Length** ft Vent 10 ØOutdoor Installation Controls Freeze ProtectionOperating Modes Mode 2 Primary/Secondary Piping Mode 7 Primary/Secondary Piping with External Target Temp Modes Default Setting Range 10 VDC 20 mA10 VDC 20 mA Boiler Target Definitions Number Field Type Fault Description OperationRank High Limit-Manual Reset Heater Sequence of OperationIgnition Module Code ConditionHigh Limit-Auto Reset Optional Modulating Temperature ControlFlow Switch High & Low Gas Pressure Switches OptionalAir Pressure Switch Blocked Vent SwitchUDB Diagnostic Board Wiring Diagrams Models Models START-UP Pre Start-upPre Start-up Check Initial Start-upPreparation Start-UpBlower Check Safety Inspection Model Air Pressure Setting Setting in. WCModel Amp Draw Setting Manifold CheckLeak Test Procedure Dual-Seat Gas Valve Follow-UpOperation Lighting InstructionsPost Start-Up Check To Turn Off Gas To Appliance Troubleshooting StepMaintenance UDB Fault HistorySuggested Minimum Maintenance Schedule Preventive Maintenance Schedule PeriodicallyWeekly Semi-AnnuallyFilter Maintenance Filter ReplacementAs Required Appendix Inside Air ContaminationImportant Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products
Related manuals
Manual 58 pages 52.53 Kb

503-2003 specifications

The Raypak 503-2003 is a notable entry in the world of water heating solutions, renowned for its efficiency and reliability in both residential and commercial settings. This model is designed to provide exceptional performance while maintaining ease of use and minimization of environmental impact.

One of the standout features of the Raypak 503-2003 is its advanced heating technology. The unit utilizes a durable, copper heat exchanger which ensures quick and efficient heating of water. This heat exchanger is known for its ability to transfer heat effectively, leading to reduced energy consumption and lower utility bills. The design also allows for a seamless operation, ensuring that the system heats water swiftly without sacrificing performance.

In addition to its efficient heating capabilities, the Raypak 503-2003 is equipped with innovative controls. The digital control panel allows users to easily set and adjust the desired water temperature. This feature provides a level of convenience that simplifies operation while enhancing user experience. Furthermore, the smart technology employed in the unit ensures that it operates within optimal parameters, avoiding unnecessary energy expenditure.

Durability is another hallmark of the Raypak 503-2003. Built with heavy-duty components, this water heating solution is designed to withstand the rigors of continuous use. The rugged construction ensures longevity, making it a cost-effective investment for homeowners and businesses alike. Moreover, the unit is designed to be resistant to corrosion and wear, further extending its lifespan and reliability.

The energy efficiency of the Raypak 503-2003 is a crucial characteristic that sets it apart from competitors. Rated with a high efficiency score, this model contributes to lower emissions and is environmentally friendly. It adheres to various energy standards, making it a suitable choice for those looking to reduce their carbon footprint while enjoying reliable water heating.

Noise reduction is another important feature of the Raypak 503-2003. Designed with quiet operation in mind, the unit operates with minimal noise pollution, allowing for a pleasant environment in both residential and commercial spaces.

In summary, the Raypak 503-2003 combines advanced heating technology, user-friendly controls, durability, and energy efficiency into a robust water heating system. This makes it an excellent choice for those in need of dependable and sustainable heating solutions. Whether for daily home use or for larger commercial applications, the Raypak 503-2003 stands out as a leader in its class.