Raypak 503-2003 manual Filter Maintenance, Filter Replacement, As Required

Page 50

6.Perform leakage test on gas valves. (See Fig. 48.)

7.Test air switch in accordance with manufacturer’s instructions. (Turn panel switch to the “On” posi- tion until blower is proven, then turn the switch to “Off.”

8.Inspect and clean burner using shop air.

As Required

1.Recondition or replace low water cut-off device (if equipped).

2.Check drip leg and gas strainers.

3.Check flame failure detection system. (See “Post Start-Up Check,” page 45.)

4.Check igniter. (Resistance reading should be 42- 70 ohms at ambient temperature).

5.Check flame signal strength. (Flame signal should be greater than 1 microampere as measured at the 2 pins on the upper left corner of the ignition control).

6.Check firing rate control by checking the manifold pressure. (See “Manifold Check” on page 43.)

7.Test safety/safety relief valves in accordance with ASME Heater and Pressure Vessel Code Section IV.

Filter Maintenance

NOTE: Use Raypak replacement filters, kit number 012552F (12”X12”) for models 503-1003 and kit number 012553F (16”X16”) for models 1253-2003.

Inspect quarterly

Replace when tracking pressure exceeds -0.5 in. WC at 100% fan speed, except for models 1003, 1753 and 2003, which need to be replaced when tracking pressure exceeds -0.7 in. WC at 100% fan speed.

Filter Replacement

1.Remove the filter box cover by loosening and removing the two wing nuts holding it in place.

Fig. 49: Remove the Air Filter Box Cover

2.Remove the filter by lifting it straight up and out of the slot in the filter box.

Fig. 50: Remove the Air Filter

3.Reverse steps 1 and 2 to install the new filter. Use Raypak replacement filters, kit number 012552F (12”X12”) for models 503-1103 and kit number 012553F (16”X16”) for models 1253-2003.

50

Image 50
Contents Do so may result in an explosion or fire Reference Catalog no .53G Effective Replaces 241288 RevPage Contents Pay Attention to These Terms Product Receipt Before InstallationInstallations at Elevation Model IdentificationComponent Locations General InformationWater Time to Produce Serious Temp Burn General SafetyTime/Temperature Relationships in Scalds Indoor Installations InstallationInstallation Codes Equipment BaseIndoor Units Outdoor InstallationsCombustion and Ventilation Air Table E Vent/Air Inlet Termination Clearances Air Filter InstallationsConventional Combustion Air Supply Direct VentGeneral Canadian InstallationsWater Piping Cold Water Operation Relief Valve Piping Temperature & Pressure GaugeHydrostatic Test Feedwater Regulator Hydronic HeatingPump Selection Cold Water StartsModel 20F 30F 40F Min. Flow Max. Flow Gpm PipingAir-Separation/Expansion Tank Potable Water and Space Heating Three-Way ValvesDomestic Hot Water Pool HeatingMake final adjustments when pool water approaches Exceed 5 ppm Pool/Spa Water ChemistryWinterizing Your Heater Gas Supply Pressure Gas SupplyGas Supply Connection Automatic Chlorinators Chemical FeedersManifold Gas Pressure Model Electrical Power ConnectionsModel In. NPT 4 in. NPT 2 in. NPT High Fire ValuesMaking the Electrical Connections Check the Power SourceField-Connected Controllers Appliance Categories Field Wiring ConnectionVenting Vent Terminal Location InstallationsSupport of Vent Stack Canadian Installations Venting Installation TipsVenting Configurations InstallationTermination CpvcVent VolumeCommon Venting Model Pressure Flue ProductsHorizontal Through-the-Wall Direct Venting Category Horizontal Through-the-Wall VentingCombustion Air Air Inlet Horizontal Max. Length** ft Vent Direct Vent-VerticalModel Certified 10 ØOutdoor Installation Operating Modes ControlsFreeze Protection Mode 2 Primary/Secondary Piping Mode 7 Primary/Secondary Piping with External Target Temp 10 VDC 20 mA Boiler Target Modes Default Setting Range10 VDC 20 mA Definitions Rank Number Field Type Fault DescriptionOperation Ignition Module High Limit-Manual ResetHeater Sequence of Operation Code ConditionFlow Switch High Limit-Auto Reset OptionalModulating Temperature Control High & Low Gas Pressure Switches OptionalUDB Diagnostic Board Air Pressure SwitchBlocked Vent Switch Wiring Diagrams Models Models Pre Start-up Check START-UPPre Start-up Initial Start-upBlower Check PreparationStart-Up Model Amp Draw Setting Safety InspectionModel Air Pressure Setting Setting in. WC Manifold CheckLeak Test Procedure Dual-Seat Gas Valve Follow-UpPost Start-Up Check OperationLighting Instructions To Turn Off Gas To Appliance Troubleshooting StepSuggested Minimum Maintenance Schedule MaintenanceUDB Fault History Weekly Preventive Maintenance SchedulePeriodically Semi-AnnuallyAs Required Filter MaintenanceFilter Replacement Appendix Inside Air ContaminationImportant Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products
Related manuals
Manual 58 pages 52.53 Kb

503-2003 specifications

The Raypak 503-2003 is a notable entry in the world of water heating solutions, renowned for its efficiency and reliability in both residential and commercial settings. This model is designed to provide exceptional performance while maintaining ease of use and minimization of environmental impact.

One of the standout features of the Raypak 503-2003 is its advanced heating technology. The unit utilizes a durable, copper heat exchanger which ensures quick and efficient heating of water. This heat exchanger is known for its ability to transfer heat effectively, leading to reduced energy consumption and lower utility bills. The design also allows for a seamless operation, ensuring that the system heats water swiftly without sacrificing performance.

In addition to its efficient heating capabilities, the Raypak 503-2003 is equipped with innovative controls. The digital control panel allows users to easily set and adjust the desired water temperature. This feature provides a level of convenience that simplifies operation while enhancing user experience. Furthermore, the smart technology employed in the unit ensures that it operates within optimal parameters, avoiding unnecessary energy expenditure.

Durability is another hallmark of the Raypak 503-2003. Built with heavy-duty components, this water heating solution is designed to withstand the rigors of continuous use. The rugged construction ensures longevity, making it a cost-effective investment for homeowners and businesses alike. Moreover, the unit is designed to be resistant to corrosion and wear, further extending its lifespan and reliability.

The energy efficiency of the Raypak 503-2003 is a crucial characteristic that sets it apart from competitors. Rated with a high efficiency score, this model contributes to lower emissions and is environmentally friendly. It adheres to various energy standards, making it a suitable choice for those looking to reduce their carbon footprint while enjoying reliable water heating.

Noise reduction is another important feature of the Raypak 503-2003. Designed with quiet operation in mind, the unit operates with minimal noise pollution, allowing for a pleasant environment in both residential and commercial spaces.

In summary, the Raypak 503-2003 combines advanced heating technology, user-friendly controls, durability, and energy efficiency into a robust water heating system. This makes it an excellent choice for those in need of dependable and sustainable heating solutions. Whether for daily home use or for larger commercial applications, the Raypak 503-2003 stands out as a leader in its class.