Raypak 503-2003 manual Combustion and Ventilation Air, Outdoor Installations, Indoor Units

Page 9

Venting not shown for clarity. Heater must be vented

per instructions in this manual

Fig. 6: Minimum Clearances from Combustible Surfaces – Indoor and Outdoor Installations

serviced in its installed location without movement or removal of the heater.

Service clearances less than the minimum may require removal of the heater to service either the heat exchanger or the burner components. In either case, the heater must be installed in a manner that will enable the heater to be serviced without removing any structure around the heater.

Outdoor Installations

These heaters are design-certified for outdoor installa- tion. Heaters must not be installed under an overhang unless clearances are in accordance with local instal-

lation codes and the requirements of the gas supplier. Three sides must be open in the area under the over- hang. Roof water drainage must be diverted away from heaters installed under overhangs.

The combustion air intake terminal MUST be used for outdoor installations. The elbow is shipped loose to be installed on the rear of the heater at the job site.

Heater

Min. Clearance

Minimum

from Combustible

Service

Side

Surfaces

Clearance

Rear

12”

24”

Front

Open

24”

Right Side

1”

1”

Left Side

1”

1”

Top

Unobstructed

10”

Vent

12”

12”

Termination

Table D: Clearances – Outdoor Installations

Combustion and Ventilation Air

NOTE: Use of this heater in construction areas where fine particulate matter, such as concrete or dry-wall dust, is present may result in damage to the heater that is not covered by the warranty. If operated in a construction environment, a clean source of combustion air must be provided directly to the heater.

Indoor Units

This heater must be supplied with sufficient quantities of non-contaminated air to support proper combustion and equipment ventilation. Combustion air can be sup- plied via conventional means where combustion air is drawn from the area immediately surrounding the heater, or via direct vent, where combustion air is drawn directly from outside. All installations must com- ply with the requirements of the NFGC (U.S.) and B149 (Canada), and all local codes.

CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater and void the warranty. (See the Appendix.)

NOTE: It is recommended that the intake vent be insulated to minimize sweating.

9

Image 9
Contents Reference Catalog no .53G Effective Replaces 241288 Rev Do so may result in an explosion or firePage Contents Pay Attention to These Terms Installations at Elevation Before InstallationProduct Receipt Model IdentificationGeneral Information Component LocationsGeneral Safety Time/Temperature Relationships in ScaldsWater Time to Produce Serious Temp Burn Installation Codes InstallationIndoor Installations Equipment BaseOutdoor Installations Combustion and Ventilation AirIndoor Units Table E Vent/Air Inlet Termination Clearances Conventional Combustion Air Supply InstallationsAir Filter Direct VentCanadian Installations Water PipingGeneral Relief Valve Piping Temperature & Pressure Gauge Hydrostatic TestCold Water Operation Pump Selection Hydronic HeatingFeedwater Regulator Cold Water StartsPiping Air-Separation/Expansion TankModel 20F 30F 40F Min. Flow Max. Flow Gpm Domestic Hot Water Three-Way ValvesPotable Water and Space Heating Pool HeatingMake final adjustments when pool water approaches Pool/Spa Water Chemistry Winterizing Your HeaterExceed 5 ppm Gas Supply Connection Gas SupplyGas Supply Pressure Automatic Chlorinators Chemical FeedersModel In. NPT 4 in. NPT 2 in. NPT Electrical Power ConnectionsManifold Gas Pressure Model High Fire ValuesCheck the Power Source Field-Connected ControllersMaking the Electrical Connections Field Wiring Connection VentingAppliance Categories Installations Support of Vent StackVent Terminal Location Venting Configurations Venting Installation TipsCanadian Installations InstallationCpvc TerminationCommon Venting VolumeVent Model Pressure Flue ProductsHorizontal Through-the-Wall Venting Horizontal Through-the-Wall Direct Venting CategoryModel Certified Direct Vent-VerticalCombustion Air Air Inlet Horizontal Max. Length** ft Vent 10 ØOutdoor Installation Controls Freeze ProtectionOperating Modes Mode 2 Primary/Secondary Piping Mode 7 Primary/Secondary Piping with External Target Temp Modes Default Setting Range 10 VDC 20 mA10 VDC 20 mA Boiler Target Definitions Number Field Type Fault Description OperationRank Heater Sequence of Operation High Limit-Manual ResetIgnition Module Code ConditionModulating Temperature Control High Limit-Auto Reset OptionalFlow Switch High & Low Gas Pressure Switches OptionalAir Pressure Switch Blocked Vent SwitchUDB Diagnostic Board Wiring Diagrams Models Models Pre Start-up START-UPPre Start-up Check Initial Start-upPreparation Start-UpBlower Check Model Air Pressure Setting Setting in. WC Safety InspectionModel Amp Draw Setting Manifold CheckFollow-Up Leak Test Procedure Dual-Seat Gas ValveOperation Lighting InstructionsPost Start-Up Check To Turn Off Gas To Appliance Step TroubleshootingMaintenance UDB Fault HistorySuggested Minimum Maintenance Schedule Periodically Preventive Maintenance ScheduleWeekly Semi-AnnuallyFilter Maintenance Filter ReplacementAs Required Inside Air Contamination AppendixImportant Instructions for the Commonwealth of Massachusetts Limited Parts Warranty MVB Types H and WH START-UP Checklist for FAN-ASSISTED Raypak Products
Related manuals
Manual 58 pages 52.53 Kb

503-2003 specifications

The Raypak 503-2003 is a notable entry in the world of water heating solutions, renowned for its efficiency and reliability in both residential and commercial settings. This model is designed to provide exceptional performance while maintaining ease of use and minimization of environmental impact.

One of the standout features of the Raypak 503-2003 is its advanced heating technology. The unit utilizes a durable, copper heat exchanger which ensures quick and efficient heating of water. This heat exchanger is known for its ability to transfer heat effectively, leading to reduced energy consumption and lower utility bills. The design also allows for a seamless operation, ensuring that the system heats water swiftly without sacrificing performance.

In addition to its efficient heating capabilities, the Raypak 503-2003 is equipped with innovative controls. The digital control panel allows users to easily set and adjust the desired water temperature. This feature provides a level of convenience that simplifies operation while enhancing user experience. Furthermore, the smart technology employed in the unit ensures that it operates within optimal parameters, avoiding unnecessary energy expenditure.

Durability is another hallmark of the Raypak 503-2003. Built with heavy-duty components, this water heating solution is designed to withstand the rigors of continuous use. The rugged construction ensures longevity, making it a cost-effective investment for homeowners and businesses alike. Moreover, the unit is designed to be resistant to corrosion and wear, further extending its lifespan and reliability.

The energy efficiency of the Raypak 503-2003 is a crucial characteristic that sets it apart from competitors. Rated with a high efficiency score, this model contributes to lower emissions and is environmentally friendly. It adheres to various energy standards, making it a suitable choice for those looking to reduce their carbon footprint while enjoying reliable water heating.

Noise reduction is another important feature of the Raypak 503-2003. Designed with quiet operation in mind, the unit operates with minimal noise pollution, allowing for a pleasant environment in both residential and commercial spaces.

In summary, the Raypak 503-2003 combines advanced heating technology, user-friendly controls, durability, and energy efficiency into a robust water heating system. This makes it an excellent choice for those in need of dependable and sustainable heating solutions. Whether for daily home use or for larger commercial applications, the Raypak 503-2003 stands out as a leader in its class.