Samsung NH300WHXEA, NH200WHXES Remote Controller Setting Range Code, Space Cooling, Space Heating

Page 33

Remote Controller Setting Range : Code 10✴✴

Field Setting Value

Main Menu &

Sub Menu Function

Description

Sub

Default

Min

Max

Step

Unit

Code

Code

 

 

 

 

 

 

 

Remote

Water Out Temp for Cooling

Max

✴✴11

25

18

25

1

˚C

Min

✴✴12

16

5

18

1

˚C

Controller

 

 

Max

✴✴21

30

24

30

1

˚C

Setting Range

Room Temp for Cooling

Min

✴✴22

18

18

22

1

˚C

 

 

Code 10✴✴

Water Out Temp for Heating

Max

✴✴31

55

37

55

1

˚C

 

Min

✴✴32

25

15

37

1

˚C

 

 

 

Room Temp for heating

Max

✴✴41

30

24

30

1

˚C

 

Min

✴✴42

16

16

22

1

˚C

 

 

 

DHW Tank Temp

Max

✴✴51

50

50

70

1

˚C

 

Min

✴✴52

40

30

40

1

˚C

 

 

Space Cooling

Target water outlet temperature : Upper limit(#1011, Default 25ºC, Range : 18 ~ 25ºC), Lower limit(#1012, Default 16ºC, Range : 5 ~ 18ºC)

-With this default FSV settings, user can change the target water outlet temperature within the range of 5 ~ 25ºC for cooling

Target room temperature : Upper limit(#1021, Default 30ºC, Range : 24 ~ 30ºC),

Lower limit(#1022, Default 18ºC, Range : 18 ~ 22ºC)

-With this default FSV settings, user can change the target room temperature within the range of 18 ~ 30ºC for cooling.

The #1 DIP switch in the wired remote controller should be set to “OFF”(Default) for cooling operation of heat pump.

The #2 DIP switch in the wired remote controller should be set to “OFF”(Default) to control the water outlet temperature.

The #2 DIP switch in the wired remote controller should be set to “ON” to control the room temperature.

The #3 DIP switch in the wired remote controller should be set to “OFF”(Default) to control the air sensor in remote controller.

The #3 DIP switch in the wired remote controller should be set to “ON” to control the external air sensor.

Space Heating

Target water outlet temperature : Upper limit(#1031, Default 55ºC, Range : 37 ~ 55ºC), Lower limit(#1032, Default 25ºC, Range : 15 ~ 37ºC)

-With this default FSV settings, user can change the target water outlet temperature within the range of 25 ~ 55ºC for heating.

Target room temperature : Upper limit(#1041, Default 30ºC, Range : 24 ~ 30ºC),

Lower limit(#1042, Default 16ºC, Range : 16 ~ 22ºC)

-With this default FSV settings, user can change the target room temperature within the range of 16 ~ 30ºC for heating.

The #2 DIP switch in the wired remote controller should be set to “OFF”(Default) to control the water outlet temperature.

The #2 DIP switch in the wired remote controller should be set to “ON” to control the room temperature.

DHW Heating

Target DHW tank temperature : Upper limit(#1051, Default 50ºC, Range : 50 ~ 80ºC), Lower limit(#1052, Default 40ºC, Range : 30 ~ 40ºC)

-With this default FSV settings, user can change the target tank temperature within the range of 40 ~ 50ºC for DHW heating.

The FSV #3011 in the wired remote controller should be set to “1(Yes)” to use DHW function.

ENGLISH

Operating advanced function _33

Image 33
Contents F I P D DB98-32035A2 Air to Water Heat Pump Hydro UnitQuick Heating by TDM Technology High Performance at Low TemperatureIntegrated Heating & Cooling System at a Lower Cost Running Costs-Reduction of Up to 33.3%Contents Important safety symbols and precautions Safety precautionsFor Using This may result in harm to humans, animals or plants Safety informationControl Panel OverviewSpace Operation Mode Checking the function of buttons and indicatorsDHW DHW Operation ModeDisplay Function Temperature AdjustmentHOT KEY Schedule Mode Status Display Function Status IndicatorA2A Optional Function IndicatorOperating basic function Available ModeSpace Heating Operation Space Cooling Operation Water LAW Domestic Water Heating Operation Urgent DHW Mode To cancel the DHW modeOperating hot key function To cancel the outing mode Outing ModeOperating advanced function Setting the TimeSet, Cancel/Delete button Setting the 7-DAYWEEKLY ScheduleViewing the 7-dayWeekly Schedule On / Off Display Deleting the 7-dayWeekly schedule Setting the Daily Schedule Viewing the Daily Schedule On / Off Display Operating the daily schedule Deleting the daily scheduleSetting the Field Setting Value of wired remote controller Field Setting ModeField Setting Value Field Setting ValueFSV TableDHW BUH/BSH Priority Space Cooling Remote Controller Setting Range CodeSpace Heating DHW HeatingWater Law for Heating Water Law & Room Thermostat CodeExternal Room Thermostat Field Option Water Law for CoolingDHW Heating Code Heat Pump Variables for Controlling DHW Tank DHW Application#3033 Disinfection Function Booster Heater Variables for Controlling DHW TankHeat Pump Variables for Space Heating Space Heating CodeExternal Backup Boiler for Space Heating Field Option Backup Heater Variables for Space HeatingOthers Code Outing Mode Hot Key of Wired Remote ControllerEconomic DHW Heating TDMTime-Division Multi VariablesDIP Switch Setting Temperature TableAppendix Available operation rangeMaintaining the Unit Maintenance activitiesThermistor Troubleshooting TipsTroubleshooting CommunicationE654 Water pump & Flow S/W E911E912 Disposal Requirements Memo 50Memo Memo