Samsung NH160PHXEA, NH200WHXES DHW Application, Heat Pump Variables for Controlling DHW Tank

Page 37

DHW Application

The FSV #3011 in the wired remote controller should be set to “1(Yes)” to use DHW function.

Heat Pump Variables for Controlling DHW Tank

Maximum DHW tank temperature with R410A(refrigerant) heat pump operation : FSV #3021, Default 50˚C, Range : 45 ~ 55˚C.

Temperature difference determining the heat pump OFF temperature : FSV #3022, Default 2˚C, Range : 2 ~ 10˚C.

Temperature difference determining the heat pump ON temperature : FSV #3023, Default 5˚C, Range : 1 ~ 20˚C.

DHW heating mode timer : If there is simultaneous requests of space heating/cooling and DHW heating, this mode timer will toggle operation modes.

-FSV #3024(minimum DHW operating time, Default 5 min., Range 0 ~ 20 min.), #3025(maximum DHW time, Default 30 min., Range 5 ~ 95 min.), #3026(time interval between two consecutive DHW mode operations, Default 3 hour, Range 0 ~ 10 hour)

The FSV #4011 for DHW priority should be set to “0(DHW)”(Default) for the mode timer action as mentioned above.

If not, the space heating mode by heat pump has a priority over the DHW heating mode under the specified low outdoor temperature(#4012).

ENGLISH

Operating advanced function _37

Image 37
Contents F I P D DB98-32035A2 Air to Water Heat Pump Hydro UnitQuick Heating by TDM Technology High Performance at Low TemperatureIntegrated Heating & Cooling System at a Lower Cost Running Costs-Reduction of Up to 33.3%Contents Important safety symbols and precautions Safety precautionsFor Using This may result in harm to humans, animals or plants Safety informationControl Panel OverviewSpace Operation Mode Checking the function of buttons and indicatorsDHW DHW Operation ModeDisplay Function Temperature AdjustmentHOT KEY Schedule Mode Status Display Function Status IndicatorA2A Optional Function IndicatorOperating basic function Available ModeSpace Heating Operation Space Cooling Operation Water LAW Domestic Water Heating Operation To cancel the DHW mode Urgent DHW ModeOperating hot key function To cancel the outing mode Outing ModeOperating advanced function Setting the TimeSet, Cancel/Delete button Setting the 7-DAYWEEKLY ScheduleViewing the 7-dayWeekly Schedule On / Off Display Deleting the 7-dayWeekly schedule Setting the Daily Schedule Viewing the Daily Schedule On / Off Display Operating the daily schedule Deleting the daily scheduleSetting the Field Setting Value of wired remote controller Field Setting ModeField Setting Value Field Setting ValueFSV TableDHW BUH/BSH Priority Space Cooling Remote Controller Setting Range CodeSpace Heating DHW HeatingWater Law for Heating Water Law & Room Thermostat CodeExternal Room Thermostat Field Option Water Law for CoolingDHW Heating Code Heat Pump Variables for Controlling DHW Tank DHW Application#3033 Disinfection Function Booster Heater Variables for Controlling DHW TankHeat Pump Variables for Space Heating Space Heating CodeExternal Backup Boiler for Space Heating Field Option Backup Heater Variables for Space HeatingOthers Code Outing Mode Hot Key of Wired Remote ControllerEconomic DHW Heating TDMTime-Division Multi VariablesDIP Switch Setting Temperature TableAppendix Available operation rangeMaintaining the Unit Maintenance activitiesThermistor Troubleshooting TipsCommunication TroubleshootingE654 E911 Water pump & Flow S/WE912 Disposal Requirements Memo 50Memo Memo