Samsung NH200WHXES, NH160PHXEA Others Code, Outing Mode Hot Key of Wired Remote Controller

Page 42

Operating advanced function

FIELD SETTING MODE

Others : Code 50✴✴

Field Setting Value

Main Menu &

Sub Menu Function

Description

Sub

Default

Min

Max

Step

Unit

Code

Code

 

 

 

 

 

 

 

Others

Outing

Water Out Temp for

✴✴11

25

5

25

1

˚C

 

 

Cooling

Code 50✴✴

 

 

 

 

 

 

 

 

Room Temp for Cooling

✴✴12

30

18

30

1

˚C

 

 

 

 

Water Out Temp for

✴✴13

25

15

55

1

˚C

 

 

Heating

 

 

 

 

 

 

 

 

 

 

Room Temp for Heating

✴✴14

16

16

30

1

˚C

 

 

Auto Cooling WL1 Temp

✴✴15

25

5

25

1

˚C

 

 

Auto Cooling WL2 Temp

✴✴16

25

5

25

1

 

 

 

Auto Heating WL1 Temp

✴✴17

15

15

55

1

˚C

 

 

Auto Heating WL2 Temp

✴✴18

15

15

55

1

˚C

 

 

Target Tank Temp

✴✴19

30

30

70

1

˚C

 

DHW Saving Mode

Temp Difference

✴✴21

5

0

40

1

˚C

 

TDM Variable

A2A Max Operation Time

✴✴31

30

5

60

5

min

 

 

A2W Min Operation Time

✴✴32

3

0

10

1

min

Outing Mode (Hot Key of Wired Remote Controller)

All the target temperatures(both water outlet and room) for space heating/cooling/ auto(water-law) modes and the target tank temperature for DHW heating mode will be changed to the values defined in the table above to save energy consumption during the vacancy of house.

With the lowered target temperatures(FSV #5011 ~ #5019), the system will be operated normally.

Economic DHW Heating

Which is heat pump only, saving energy consumption. A target temperature of DHW shall be lowered as much as Users set with field setting values stored in wired remote controller.

-New target DHW tank temperature will be the value subtracted the difference(#5021) from the present user’s setting.

TDM(Time-Division Multi) Variables

Under the installation of both A2A(Air-To-Air type air conditioner) and A2W(Air-To-Water type hydro unit) at the same time, our outdoor machine can supply its full capacity to the operating indoor machines(including A2A and A2W). If there are simultaneous operating demands from many A2A machines with A2W, the priority of controlling the outdoor machine(ex: compressor frequency) will be given to A2A, because of their fast response for use’s comfort. Only the remaining capacity of outdoor machine will be given to A2W during A2A’s normal operation. In this case, it might take very long time for A2W heating, so the outdoor machine will alternate the controlling priorities between A2A and A2W with time basis.

A2A maximum operation time: FSV #5031(Default “30 min.”, Range 5 ~ 60 min.), After this maximum time, the outdoor machine will operate only for A2W to speed up the A2W’s heating/cooling performance, even though there are A2A’s continuous operation demands.

A2W minimum operation time: FSV #5032(Default “3 min.”, Range 0 ~ 10 min.), in this minimum time, the outdoor machine will operate only for A2W, even though there are no more A2W’s continuous operation demands.

42_ Operating advanced function

Image 42
Contents Air to Water Heat Pump Hydro Unit F I P D DB98-32035A2Integrated Heating & Cooling System at a Lower Cost High Performance at Low TemperatureQuick Heating by TDM Technology Running Costs-Reduction of Up to 33.3%Contents Safety precautions Important safety symbols and precautionsFor Using Safety information This may result in harm to humans, animals or plantsOverview Control PanelChecking the function of buttons and indicators Space Operation ModeDHW Operation Mode DHWTemperature Adjustment Display FunctionHOT KEY Schedule Status Indicator Mode Status Display FunctionOptional Function Indicator A2AAvailable Mode Operating basic functionSpace Heating Operation Space Cooling Operation Water LAW Domestic Water Heating Operation Urgent DHW Mode To cancel the DHW modeOperating hot key function Outing Mode To cancel the outing modeSetting the Time Operating advanced functionSetting the 7-DAYWEEKLY Schedule Set, Cancel/Delete buttonViewing the 7-dayWeekly Schedule On / Off Display Deleting the 7-dayWeekly schedule Setting the Daily Schedule Viewing the Daily Schedule On / Off Display Deleting the daily schedule Operating the daily scheduleField Setting Mode Setting the Field Setting Value of wired remote controllerField Setting ValueFSV Table Field Setting ValueDHW BUH/BSH Priority Space Heating Remote Controller Setting Range CodeSpace Cooling DHW HeatingWater Law & Room Thermostat Code Water Law for HeatingWater Law for Cooling External Room Thermostat Field OptionDHW Heating Code DHW Application Heat Pump Variables for Controlling DHW Tank#3033 Booster Heater Variables for Controlling DHW Tank Disinfection FunctionSpace Heating Code Heat Pump Variables for Space HeatingBackup Heater Variables for Space Heating External Backup Boiler for Space Heating Field OptionEconomic DHW Heating Outing Mode Hot Key of Wired Remote ControllerOthers Code TDMTime-Division Multi VariablesAppendix Temperature TableDIP Switch Setting Available operation rangeMaintenance activities Maintaining the UnitTroubleshooting Tips ThermistorTroubleshooting CommunicationE654 Water pump & Flow S/W E911E912 Disposal Requirements Memo 50Memo Memo