Booster Heater Variables for Controlling DHW Tank

The FSV #3031 should be set to “1(On)”(Default) to use booster heater as an additional heat source for DHW tank.

Booster heater startup delay timer : In case of DHW request, this timer will delay the operation of booster heater compared to heat pump.

-FSV #3032(Default 20 min., Range 20 ~ 95 min.), In “Power” DHW mode, the delay timer will be neglected, and the booster starts immediately.

-In “Economic” DHW mode, the DHW heating will be conducted only with heat pump.

-#3032 should be smaller than the maximum H/P time(#3025). If the delay time is set too high, it might take very long time for DHW heating.

Temperature difference determining the booster heater OFF temperature(T_BH OFF = Tu + #3033) : FSV #3033, Default 0˚C, Range : 0 ~ 4˚C.

-Temperature difference determining the booster heater ON temperature(T_BH ON = T_BH OFF - 2)

DHW compensation temperature in case of space heating/cooling priority : FSV #3034 will be explained in next page.

The FSV #4022 for booster heater priority should be set to “0(both)”(Default) or “2”(booster) to use booster heater.

If not(backup heater priority), the booster heater can be operated in case of no backup heater demand.

Disinfection Function

The FSV #3041 should be set to “1(On)”(Default) to use disinfection function.

- Scheduling : Day(#3042, Default “Friday”), starting time(#3043, Default “23:00”), target tank temp. (#3044, Default “70˚C”), duration(#3045, Default 10 min.)

Disinfection function can be performed only with Samsung’s DHW tank installation.

Urgent DHW by User’s Input (Hot Key of Wired Remote Controller)

By default setting(#3061, Default “0(Off)”, Urgent DHW heating will not be turned off automatically before user’s additional key input. If you want to quit urgent DHW function after a certain amount of duration time(#3052, Default “60 min.”, Range 30 ~ 300 min.), change the FSV #3051 to “1(On)”.

Additional Solar Panel Installation for DHW with Heat Pump (Field Option)

By default setting(#3051, Default “1(Yes)”, the DHW heating by solar panel has a priority over the heat pump operation in case of solar panel installation.

ENGLISH

Operating advanced function _39

Image 39
Contents F I P D DB98-32035A2 Air to Water Heat Pump Hydro UnitRunning Costs-Reduction of Up to 33.3% High Performance at Low TemperatureQuick Heating by TDM Technology Integrated Heating & Cooling System at a Lower CostContents Important safety symbols and precautions Safety precautionsFor Using This may result in harm to humans, animals or plants Safety informationControl Panel OverviewSpace Operation Mode Checking the function of buttons and indicatorsDHW DHW Operation ModeDisplay Function Temperature AdjustmentHOT KEY Schedule Mode Status Display Function Status IndicatorA2A Optional Function IndicatorOperating basic function Available ModeSpace Heating Operation Space Cooling Operation Water LAW Domestic Water Heating Operation Urgent DHW Mode To cancel the DHW modeOperating hot key function To cancel the outing mode Outing ModeOperating advanced function Setting the TimeSet, Cancel/Delete button Setting the 7-DAYWEEKLY ScheduleViewing the 7-dayWeekly Schedule On / Off Display Deleting the 7-dayWeekly schedule Setting the Daily Schedule Viewing the Daily Schedule On / Off Display Operating the daily schedule Deleting the daily scheduleSetting the Field Setting Value of wired remote controller Field Setting ModeField Setting Value Field Setting ValueFSV TableDHW BUH/BSH Priority DHW Heating Remote Controller Setting Range CodeSpace Cooling Space HeatingWater Law for Heating Water Law & Room Thermostat CodeExternal Room Thermostat Field Option Water Law for CoolingDHW Heating Code Heat Pump Variables for Controlling DHW Tank DHW Application#3033 Disinfection Function Booster Heater Variables for Controlling DHW TankHeat Pump Variables for Space Heating Space Heating CodeExternal Backup Boiler for Space Heating Field Option Backup Heater Variables for Space HeatingTDMTime-Division Multi Variables Outing Mode Hot Key of Wired Remote ControllerOthers Code Economic DHW HeatingAvailable operation range Temperature TableDIP Switch Setting AppendixMaintaining the Unit Maintenance activitiesThermistor Troubleshooting TipsTroubleshooting CommunicationE654 Water pump & Flow S/W E911E912 Disposal Requirements Memo 50Memo Memo