Samsung NH200WHXEA, NH200WHXES Space Heating Code, Heat Pump Variables for Space Heating

Page 40

Operating advanced function

FIELD SETTING MODE

Space Heating : Code 40✴✴

Ts

DHW by Booster Heater Only

 

 

 

Tu

#3034

 

 

 

 

#4012

Ta

Field Setting Value

Main Menu &

Sub Menu Function

Description

Sub

Default

Min

Max

Step

Unit

Code

Code

 

 

 

 

 

 

 

Heating

Heat Pump

Heating/DHW Priority

✴✴11

0(DHW)

0

1(Heating)

-

-

Code 40✴✴

 

Outdoor Temp for Priority

✴✴12

0

-15

20

1

˚C

 

Heating Off

✴✴13

25

14

35

1

˚C

 

 

 

 

Overshoot

✴✴14

2

1

4

1

˚C

 

Backup Heater

Application

✴✴21

1(On)

0(Off)

1

-

-

 

 

BUH/BSH Priority

✴✴22

0(Both)

0

2(BSH)

1

-

 

 

For back-up use only

✴✴23

1(On)

0(Off)

1

-

-

 

 

Threshold Temp

✴✴24

0

-15

35

1

˚C

 

Backup Boiler

Application

✴✴31

0(No)

0

1(Yes)

-

-

 

 

Boiler Priority

✴✴32

0(Off)

0

1(On)

-

-

 

 

Threshold Temp

✴✴33

-15

-20

5

1

˚C

Heat Pump Variables for Space Heating

FSV #4011 for DHW priority is set to “0(DHW)”(Default) for the first time. In case of “1(Heating)”, the space heating by heat pump has a priority over the DHW heating by heat pump under the low outdoor temperature condition(#4012).

DHW compensation temperature in case of space heating priority:

At low outdoor temperature, the target temperature of DHW tank will be increased by the temperature difference defined in FSV #3034 to compensate the relatively cold water stored in DHW tank. In this case, the only heat source for DHW tank would be booster heater inside tank, so the lower part of water stored in tank could be cold due to “No operation of heat pump”. The corrected (higher) set point will make sure that the total heat capacity of the water in the tank remains approximately unchanged, by compensating for the colder bottom water layer of the tank (because the heat exchanger coil is not operational) with a warmer top layer.

Space heating off temperature(FSV #4013, Default “25˚C”, Range 14 ~ 35˚C):

At high outdoor temperature above this value, the space heating will be turned off, to avoid overheating.

Overshoot temperature(FSV #4014, Default “2˚C”, Range 1 ~ 4˚C): N/A yet

40_ Operating advanced function

Image 40
Contents Air to Water Heat Pump Hydro Unit F I P D DB98-32035A2High Performance at Low Temperature Quick Heating by TDM TechnologyIntegrated Heating & Cooling System at a Lower Cost Running Costs-Reduction of Up to 33.3%Contents Safety precautions Important safety symbols and precautionsFor Using Safety information This may result in harm to humans, animals or plantsOverview Control PanelChecking the function of buttons and indicators Space Operation ModeDHW Operation Mode DHWTemperature Adjustment Display FunctionHOT KEY Schedule Status Indicator Mode Status Display FunctionOptional Function Indicator A2AAvailable Mode Operating basic functionSpace Heating Operation Space Cooling Operation Water LAW Domestic Water Heating Operation To cancel the DHW mode Urgent DHW ModeOperating hot key function Outing Mode To cancel the outing modeSetting the Time Operating advanced functionSetting the 7-DAYWEEKLY Schedule Set, Cancel/Delete buttonViewing the 7-dayWeekly Schedule On / Off Display Deleting the 7-dayWeekly schedule Setting the Daily Schedule Viewing the Daily Schedule On / Off Display Deleting the daily schedule Operating the daily scheduleField Setting Mode Setting the Field Setting Value of wired remote controllerField Setting ValueFSV Table Field Setting ValueDHW BUH/BSH Priority Remote Controller Setting Range Code Space CoolingSpace Heating DHW HeatingWater Law & Room Thermostat Code Water Law for HeatingWater Law for Cooling External Room Thermostat Field OptionDHW Heating Code DHW Application Heat Pump Variables for Controlling DHW Tank#3033 Booster Heater Variables for Controlling DHW Tank Disinfection FunctionSpace Heating Code Heat Pump Variables for Space HeatingBackup Heater Variables for Space Heating External Backup Boiler for Space Heating Field OptionOuting Mode Hot Key of Wired Remote Controller Others CodeEconomic DHW Heating TDMTime-Division Multi VariablesTemperature Table DIP Switch SettingAppendix Available operation rangeMaintenance activities Maintaining the UnitTroubleshooting Tips ThermistorCommunication TroubleshootingE654 E911 Water pump & Flow S/WE912 Disposal Requirements Memo 50Memo Memo