Slant/Fin VHS-30, VHS-180 Victory II VHS Models Gas Rate Table, Safety Check

Page 20

VICTORY II VHS Models

Gas Rate Table

 

 

 

 

 

 

 

Boiler rated input in

 

 

Cubic Feet Gas Consumption

 

 

cu. ft./hr. of 1000 Btu/cu. ft.

 

 

1000 Btu/cu. ft. gas, in

 

 

Natural Gas

 

 

3 minutes, at rated input

 

 

 

 

 

 

 

 

30

 

 

1.50

 

 

60

 

 

3.00

 

 

90

 

 

4.50

 

 

120

 

 

6.00

 

 

150

 

 

7.50

 

 

180

 

 

9.00

 

 

 

 

 

 

 

The gas metered in 3 minutes to obtain rated input for each boiler model, using 1000 Btu/cu. ft. gas, is tabu- lated in gas rate table.

B.Main Burners

1.Fire the boiler continuously for at least 15 minutes, to reach burner operating temperature.

2.Observe the flames, all burners. The base of all flame jets should be blue. The tips should be blue shading to orange. NOTE: Dust, disturbed by any movement, will cause bright orange flames. Wait for dust to settle.

3.For one burner, close the air shutter until some of its flame jet tips turn yellow-white, indicating insufficient primary air. Then open shutter until whitish tips disap- pear completely. Set all burner shutters to the same opening. Observe to make sure that no yellow-white tips appear over any portion of the flame. Small yel- low tips at the pilot are permitted (see Figure 18).

NOTE: This adjustment method gives MINIMUM pri- mary air setting for safe combustion. DO NOT attempt to make this adjustment unless burners are at operat- ing temperature. Adjustment should be made with burner access panel in final operating position. Use of a mirror may be helpful to observe flames. Note that burner ports are on top of main burner tube.

Figure 18.

C.Main Burner Ignition Checkout and Pilot Adjustment

1.The pilot flame must not smother or snuff out when tested as follows:

a.Main burner ignition from cold start-repeat.

b.Continued operation of main burner.

c.Main burner ignition with appliance at maximum operating temperature after prolonged operation.

NOTE: Observe operation of the pilot burner with appliance doors in the final operating position. Use of a mirror may be helpful.

2.Pilot Burner Adjustment

The pilot flame should envelope approximately 3/8 to 1/2 inch of sensor tip (see Figure 19). To adjust pilot flame:

a.Remove the pilot adjustment cover screw from the gas control.

b.Turn pilot adjustment screw clockwise to decrease or counterclockwise to increase pilot flame.

c.Replace pilot adjustment cover screw.

Figure 19.

SAFETY CHECK

Removing Control Box (cover). See Figure 20. To remove control box:

a. Turn black screw 1/4 turn clockwise to open position.

b. Remove two sheet metal screws in the top of control box.

c. Remove control box.

To replace the box, reverse procedure. Be sure that black screw is in the lower bracket receptacle and lock position.

20

Image 20
Contents Victory Victory II VHS Models 485Installation Requirements SafetyNatural GAS-FIRED Boiler Location Liquefied Petroleum L.P. Propane GAS-FIRED Boiler LocationApproved Venting Applications Boiler Room AIR Supply and VentilationFlue GAS Venting Requirements Category II and III Venting Heat-Fab Saf-T Vent System Victory II Horizontal Sidewall Venting Victory II VHS Models Victory II VHS Models Vent Connector Material Venting RequirementsConnector Requirements Masonry Vitreous Tile-Lined Chimney not metal linedAdditional National Fuel Gas Code Boiler Gas Appliance Type B Venting and Metal-Lined Masonry ChimneyVictory II VHS Models Victory II VHS Models GAS Piping Electrical WiringVenting System Regular Inspection Water Piping Supply and ReturnCirculating Systems Air Control SystemVictory II VHS Models Piping Arrangement Operating INSTRUCTIONS, Basic Safety Information Operating InstructionsSafety Check Victory II VHS Models Gas Rate TableCare and Maintenance Annual Inspection and Cleaning Inspection During Heating SeasonVictory II Boiler Sequence of Operations Flash BACK-BURNING AT Orifices Cause Remedy Burners Fail to Operate Cause RemedyBurners will not SHUT-OFF Cause Remedy Delayed Ignition Cause Remedy Not Enough Heat Cause RemedyFumes and GAS Odors Cause Remedy Burner Short Cycles Cause RemedyAppendix a SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516

VHS-180, VHS-30 specifications

Slant/Fin, a prominent name in the heating industry, offers the VHS series, which includes the VHS-30 and VHS-180, two highly efficient hot water boilers designed for residential and light commercial applications. These units are distinguished by their durability, performance, and advanced technologies, making them ideal for a variety of heating needs.

The VHS-30 boasts a compact design, making it suitable for installations in limited spaces while still providing robust heating capabilities. It offers an output of 30,000 BTU, making it efficient for smaller buildings or homes. Conversely, the VHS-180 is designed for larger applications, delivering a powerful 180,000 BTU output, ensuring that even the most demanding spaces remain comfortably heated.

One of the standout features of both models is their ability to operate with natural gas or propane, providing flexibility based on regional gas availability and user preference. This adaptability is further enhanced by their advanced combustion technology, which allows for an efficient and clean burn. Both models incorporate a pressurized hot water boiler design which enhances their energy efficiency by maximizing heat transfer from the burner to the water.

In terms of construction, both the VHS-30 and VHS-180 are built with high-quality components designed for longevity. They feature a durable cast iron heat exchanger, which not only improves the lifespan of the unit but also contributes to its high thermal efficiency. The units are also equipped with state-of-the-art controls that allow users to monitor and adjust settings easily, ensuring optimal performance and energy savings.

Safety is another key aspect of the VHS series. Both models are equipped with numerous safety features, including a high limit temperature control, automatic restart, and a safety valve, ensuring peace of mind for homeowners and building operators alike.

Moreover, the VHS series also emphasizes ease of maintenance. The design allows for straightforward access to all critical components, making servicing and routine maintenance more manageable for technicians. As a result, this leads to reduced downtime and longer service intervals.

In conclusion, the Slant/Fin VHS-30 and VHS-180 are exemplary choices for anyone in need of reliable and efficient hot water heating solutions. Their combination of advanced technology, quality construction, and user-friendly features make them a top choice for both residential and light commercial heating applications. The VHS series stands as a testament to Slant/Fin's commitment to innovation and customer satisfaction in the heating market.