Slant/Fin VHS-30, VHS-180 installation instructions Operating INSTRUCTIONS, Basic

Page 18

VICTORY II VHS Models

An automatic air vent is used to remove air from the sys- tem. It should be installed in the top of the boiler as shown in Figure 15. If system pressure needs further control, add an additional tank in parallel with original tank or install a larger capacity tank. Use appropriate size tank for volume of water in system. See chart for boiler’s volume.

Boiler Water Content

Model

Pounds

Gallons

 

 

 

VHS-30

17.5

2.1

VHS-60

24.75

3.0

VHS-90

32.00

3.8

VHS-120

39.25

4.7

VHS-150

46.50

5.6

VHS-180

53.75

6.4

 

 

 

4.Cold Water Fill

Pressure reducing (fill) valve and shut-off valve should be installed.

5.Relief Valve Discharge Piping

Use same size or larger piping than valve outlet. Must ter- minate 6" minimum from floor with a plain (no threads) end. Place a bucket under pressure relief valve discharge. Make sure discharge is always visible. DO NOT hard-pipe to drain piping.

6.Providing Protection from Freezing

Anti-freeze is sometimes used in hydronic heating systems to protect against freeze-up in the event of power failure or control shutdown when the building is unoccupied. It should be recognized that unless the building is kept above freezing temperature by some means, the plumbing system is not protected. Two types of anti-freeze may be used: ETHYLENE GLYCOL, used in automobiles, has desirable properties, but is toxic. Its use may be prohibited when system water/glycol solution is in contact with a potable water vessel (as an indirect hot water heater with built-in heating coils). PROPYLENE GLYCOL is used in the quick-freeze food industry; it is practically non-toxic. Its use may be permitted when system solution is in contact with a potable water vessel. When anti-freeze must be used, inhibited propylene glycol is recommended. Useful information on the characteristics, mixing proportions, etc. of glycol in heating systems is given in Technical Topics No. 2A, available from the Hydronics Institute, 34 Russo Place, Berkeley Heights, NJ 07922. Consult glycol manu- facturers for sources of propylene glycol.

7.Water Treatment

A good water treatment program will not only extend the useful life of this boiler but it will also save much of the time and expense of repairs made necessary by pre- ventable occurrences. A reputable water treatment compa- ny should be consulted to evaluate and determine the best overall treatment program for your boiler equipment.

PIPING A HEATING - COOLING SYSTEM TO A WATER BOILER AND CHILLER

Figure 16 illustrates a method of piping a heating-cooling sys- tem to a water boiler and a chiller. Hand valves (shown) or automatic valves must be installed to prevent circulation of chilled water in the boiler or hot water in the chiller.

The air control system and pressure control system must operate with chiller only, or the boiler only, being valved to the piping system. Separate control devices on the boiler and chiller may be used, or a single set of air and pressure con- trols on the common piping may be preferred.

If the boiler is used to supply hot water to heating coils in air handling units, flow control valves or other devices must be installed to prevent gravity circulation of water in the coils dur- ing the cooling cycle.

Figure 16.

OPERATING INSTRUCTIONS, BASIC

1.Filling and Venting Water Systems

A.Fill the system with water. Vent or purge of air.

B.Fire the boiler as soon as possible (see following warn- ing and instructions) and bring water temperature in the system.

C.Vent air and add water as needed to achieve operating pressure on boiler gauge. Pressure must be between approximately 12 psi (cold water) and 25 psi at water temperature setting of high limit control, for boilers equipped with 30 psi relief valves. Boilers rated for a higher pressure and equipped with a matching relief valve may operate at a higher pressure, but no higher than 5 psi below the relief valve opening pressure.

D.Check for and repair any leaks before placing system in service.

BEFORE FIRING BOILER, make these checks:

1.System is full of water. Air is vented or purged.

2.Relief valve is installed in accordance with ASME Boil- er and Pressure Vessel Code, Section IV. Valve open- ing is not closed or reduced in size.

3.Venting is installed according to instructions under

“FLUE GAS VENTING REQUIREMENTS”.

4.All wiring is completed, following applicable wiring dia- grams.

5.Using soap solution, check for gas leaks in all gas pip- ing from meter to boiler pilot and manifold. DO NOT use open flame.

2.Initial Start

Safe lighting and other performance criteria were met when testing various gas manifold and control assemblies used on the Victory II Series Boilers under the ANSI Z21.13- latest edition.

18

Image 18
Contents Victory Victory II VHS Models 485Natural GAS-FIRED Boiler Location Installation RequirementsSafety Liquefied Petroleum L.P. Propane GAS-FIRED Boiler LocationBoiler Room AIR Supply and Ventilation Flue GAS Venting RequirementsApproved Venting Applications Category II and III Venting Heat-Fab Saf-T Vent System Victory II Horizontal Sidewall Venting Victory II VHS Models Victory II VHS Models Vent Connector Material Venting RequirementsAdditional National Fuel Gas Code Boiler Gas Appliance Connector RequirementsMasonry Vitreous Tile-Lined Chimney not metal lined Type B Venting and Metal-Lined Masonry ChimneyVictory II VHS Models Victory II VHS Models Electrical Wiring Venting System Regular InspectionGAS Piping Circulating Systems Water PipingSupply and Return Air Control SystemVictory II VHS Models Piping Arrangement Operating INSTRUCTIONS, Basic Safety Information Operating InstructionsSafety Check Victory II VHS Models Gas Rate TableCare and Maintenance Annual Inspection and Cleaning Inspection During Heating SeasonVictory II Boiler Sequence of Operations Burners Fail to Operate Cause Remedy Burners will not SHUT-OFF Cause RemedyFlash BACK-BURNING AT Orifices Cause Remedy Fumes and GAS Odors Cause Remedy Delayed Ignition Cause RemedyNot Enough Heat Cause Remedy Burner Short Cycles Cause RemedyAppendix a SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516

VHS-180, VHS-30 specifications

Slant/Fin, a prominent name in the heating industry, offers the VHS series, which includes the VHS-30 and VHS-180, two highly efficient hot water boilers designed for residential and light commercial applications. These units are distinguished by their durability, performance, and advanced technologies, making them ideal for a variety of heating needs.

The VHS-30 boasts a compact design, making it suitable for installations in limited spaces while still providing robust heating capabilities. It offers an output of 30,000 BTU, making it efficient for smaller buildings or homes. Conversely, the VHS-180 is designed for larger applications, delivering a powerful 180,000 BTU output, ensuring that even the most demanding spaces remain comfortably heated.

One of the standout features of both models is their ability to operate with natural gas or propane, providing flexibility based on regional gas availability and user preference. This adaptability is further enhanced by their advanced combustion technology, which allows for an efficient and clean burn. Both models incorporate a pressurized hot water boiler design which enhances their energy efficiency by maximizing heat transfer from the burner to the water.

In terms of construction, both the VHS-30 and VHS-180 are built with high-quality components designed for longevity. They feature a durable cast iron heat exchanger, which not only improves the lifespan of the unit but also contributes to its high thermal efficiency. The units are also equipped with state-of-the-art controls that allow users to monitor and adjust settings easily, ensuring optimal performance and energy savings.

Safety is another key aspect of the VHS series. Both models are equipped with numerous safety features, including a high limit temperature control, automatic restart, and a safety valve, ensuring peace of mind for homeowners and building operators alike.

Moreover, the VHS series also emphasizes ease of maintenance. The design allows for straightforward access to all critical components, making servicing and routine maintenance more manageable for technicians. As a result, this leads to reduced downtime and longer service intervals.

In conclusion, the Slant/Fin VHS-30 and VHS-180 are exemplary choices for anyone in need of reliable and efficient hot water heating solutions. Their combination of advanced technology, quality construction, and user-friendly features make them a top choice for both residential and light commercial heating applications. The VHS series stands as a testament to Slant/Fin's commitment to innovation and customer satisfaction in the heating market.