Slant/Fin VHS-30, VHS-180 installation instructions Appendix a

Page 26

VICTORY II VHS Models

APPENDIX A

Vent System Location and Condensation

Drain Requirements

1.The venting system shall terminate at least 3 feet above any forced air inlet located within 10 feet.

2.The venting system shall terminate at least 4 feet below, 4 feet horizontally from, or 1 foot above any door, window or gravity air inlet into any building. The bottom of the vent terminal shall be at least 12 inches above grade or the normal snow level, whichever is greater.

3.Through the wall vents for Category II and IV appli- ances shall not terminate over public walkways or over areas where condensate or vapor could create a nuisance or hazard or could be detrimental to the operation of regulators, relief valves or other equip- ment. Minimum clearance of 4' horizontally from, and in no case above or below, unless a 4' horizon- tal distance is maintained, from electric meters, gas meters, regulators and relief equipment. Where local experience indicates that condensate may be a problem with Category I and III appliances, this provision shall also apply.

4.Provision shall be made to collect and dispose of condensate from venting systems serving Category I, II, III and IV appliances.

Caution

Flue gases exiting from the vent terminal will con- dense. Building materials in the area of the vent termi- nal should be protected from discoloration and degra- dation.

APPENDIX B

Removal of Existing Boiler From

Common Vent System

a.Seal any unused openings in the common venting system.

b.Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.

c.Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the com- mon venting system are located and other spaces of the building. Turn on clothes dryer and any appli- ance not connected to the common venting sys- tem. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they will operate at maximium speed. DO NOT operate a summer exhaust fan. Close fireplace dampers.

d.Place in operation the appliance being inspected. Follow the lighting instructions. Adjust thermostat so appliance will operate continuously.

e.Test for spillage at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle, or smoke from a ciga- rette, cigar or pipe.

f.After it has been determined that each appliance remaining connected to the common venting sys- tem properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas burning appliance to their previous conditions of use.

g.Any improper operation of the common venting system should be corrected so the installation con- forms with the National Fuel Gas Code, ANSI Z223.1-latest edition. When resizing any portion of the common venting system, the common venting system should be resized to approach the mini- mum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z223.1-latest edition.

26

Image 26
Contents Victory Victory II VHS Models 485Natural GAS-FIRED Boiler Location Installation RequirementsSafety Liquefied Petroleum L.P. Propane GAS-FIRED Boiler LocationApproved Venting Applications Boiler Room AIR Supply and VentilationFlue GAS Venting Requirements Category II and III Venting Heat-Fab Saf-T Vent System Victory II Horizontal Sidewall Venting Victory II VHS Models Victory II VHS Models Vent Connector Material Venting RequirementsAdditional National Fuel Gas Code Boiler Gas Appliance Connector RequirementsMasonry Vitreous Tile-Lined Chimney not metal lined Type B Venting and Metal-Lined Masonry ChimneyVictory II VHS Models Victory II VHS Models GAS Piping Electrical WiringVenting System Regular Inspection Circulating Systems Water PipingSupply and Return Air Control SystemVictory II VHS Models Piping Arrangement Operating INSTRUCTIONS, Basic Safety Information Operating InstructionsSafety Check Victory II VHS Models Gas Rate TableCare and Maintenance Annual Inspection and Cleaning Inspection During Heating SeasonVictory II Boiler Sequence of Operations Flash BACK-BURNING AT Orifices Cause Remedy Burners Fail to Operate Cause RemedyBurners will not SHUT-OFF Cause Remedy Fumes and GAS Odors Cause Remedy Delayed Ignition Cause RemedyNot Enough Heat Cause Remedy Burner Short Cycles Cause RemedyAppendix a SLANT/FIN CORPORATION, Greenvale, N.Y Phone 516

VHS-180, VHS-30 specifications

Slant/Fin, a prominent name in the heating industry, offers the VHS series, which includes the VHS-30 and VHS-180, two highly efficient hot water boilers designed for residential and light commercial applications. These units are distinguished by their durability, performance, and advanced technologies, making them ideal for a variety of heating needs.

The VHS-30 boasts a compact design, making it suitable for installations in limited spaces while still providing robust heating capabilities. It offers an output of 30,000 BTU, making it efficient for smaller buildings or homes. Conversely, the VHS-180 is designed for larger applications, delivering a powerful 180,000 BTU output, ensuring that even the most demanding spaces remain comfortably heated.

One of the standout features of both models is their ability to operate with natural gas or propane, providing flexibility based on regional gas availability and user preference. This adaptability is further enhanced by their advanced combustion technology, which allows for an efficient and clean burn. Both models incorporate a pressurized hot water boiler design which enhances their energy efficiency by maximizing heat transfer from the burner to the water.

In terms of construction, both the VHS-30 and VHS-180 are built with high-quality components designed for longevity. They feature a durable cast iron heat exchanger, which not only improves the lifespan of the unit but also contributes to its high thermal efficiency. The units are also equipped with state-of-the-art controls that allow users to monitor and adjust settings easily, ensuring optimal performance and energy savings.

Safety is another key aspect of the VHS series. Both models are equipped with numerous safety features, including a high limit temperature control, automatic restart, and a safety valve, ensuring peace of mind for homeowners and building operators alike.

Moreover, the VHS series also emphasizes ease of maintenance. The design allows for straightforward access to all critical components, making servicing and routine maintenance more manageable for technicians. As a result, this leads to reduced downtime and longer service intervals.

In conclusion, the Slant/Fin VHS-30 and VHS-180 are exemplary choices for anyone in need of reliable and efficient hot water heating solutions. Their combination of advanced technology, quality construction, and user-friendly features make them a top choice for both residential and light commercial heating applications. The VHS series stands as a testament to Slant/Fin's commitment to innovation and customer satisfaction in the heating market.