VICTORY II VHS Models
| DELAYED IGNITION |
| |
| CAUSE | REMEDY | |
| 1. | Pilot flame too low | 1.Adjust pilot flame |
| 2. | Excessive primary air | 2.Adjust primary air shutter |
| 3. | Excessive burner input | 3.Check and reduce to input shown on rating plate |
|
|
| |
| NOT ENOUGH HEAT |
| |
| CAUSE | REMEDY | |
| 1. | Thermostat setting is too low | 1.Set thermostat at higher setting |
| 2. | Boiler water maintained at too low temperature | 2.Set Aquastat at higher setting |
| 3. | Circulator not running | 3.With thermostat calling for heat, check for power to circulator. |
|
|
| If power OK but circulator not running, replace circulator |
| 4. | Boiler water level too low | 4.Carefully snap open relief valve handle to determine if boiler |
|
|
| is full of water. If not full of water, check for system leaks and |
|
|
| check water pressure regulator. Repair any system leaks. |
|
|
| Adjust or replace water pressure reducing valve |
|
|
| |
| FUMES AND GAS ODORS |
| |
| CAUSE | REMEDY | |
| 1. | Leaks in gas piping or accessories | 1.Locate leaks and repair |
| 2. | Gas leaks in service line or meter connections | 2.Close service supply valve - shut down boiler and notify utility |
| 3. | Adverse draft condition in boiler room | 3. Check air supply and venting system |
| 4. | Condensation trap is not full of water | 4.Check and fill with water |
| 5. | Venting system is physically damaged | 5.Check carefully and repair. Also, see “Venting System Regular |
|
|
| Inspection” |
| 6. | 6.Adjust gas input to that shown on boiler rating plate | |
|
|
| |
| BURNER SHORT CYCLES |
| |
| CAUSE | REMEDY | |
| 1. | Thermostat heat anticipator set too low | 1.Reset anticipator |
| 2. | Excessive pressure drop due to excess venting system | 2.Venting system must be corrected |
| 3. | Blockage or restriction in venting system | 3.Check and repair |
| 4. | Defective air flow switch (out of adjustment) | 4.DO NOT adjust, replace |
IF REPLACEMENT PARTS ARE NEEDED
When parts are needed, refer to boiler model and serial number shown on the boiler name/rating plate. Refer to publication number
Control identification and replacement should not be attempted by unskilled personnel. Only simple,
For replacement parts, heating contractors should con- tact their Slant/Fin boiler distributor.