Vulcan-Hart BVD36FP52(F,L)N-1 Standing Pilot Propane/Lp Gas Conversion, B-Ventfireplaces, Model

Page 21
STANDING PILOT PROPANE/LP GAS CONVERSION

STANDING PILOT PROPANE/LP GAS CONVERSION

"B-VENT" FIREPLACES

Model

Conversion Kit Model

 

(Part Number)

BVD34FP3 SERIES

BVCK34P (19160)

BVD36FP3 SERIES

BVCK36P (19161)

BVP42FP3 SERIES

BVCK42P (19162)

FOR CONVERSION TO LIQUEFIED PETROLEUM GAS

WARNING

This conversion kit is to be installed by an Empire Comfort Systems, Inc. dealer (or other qualified agency1)* in accordance with the manufacturer's instructions and all codes and requirements of the authority having jurisdiction. Failure to follow instructions could result in serious injury or property damage. The qualified agency performing this work assumes responsibility for this conversion.

1National Fuel Gas Code Z223.1 (Latest Edition), Natural Gas and Propane Installation Code, CSA B149.1

*The term "qualified agency" means any individual, firm, corporation or company which either in person or through a representative is engaged in and is responsible for (a) the installation of gas piping or (b) the connection, installation repair, or servicing of equipment, who is experienced in such work, familiar with all precautions required, and has complied with all the requirements of the authority having jurisdiction.

PARTS LIST

Conversion Kit

BVCK34P

BVCK36P

BVCK42P

 

Model

 

 

 

 

 

 

 

 

 

Part

Kit No. 19160

Kit No. 19161

Kit No. 19162

Quantity

Description

 

 

 

Supplied

Fireplace

BVD34FP3

BVD36FP3

BVP42FP3

 

 

SERIES

SERIES

SERIES

 

Pilot Orifice

#35 (R-7658)

#35 (R-7658)

#35 (R-7658)

1

Main Burner

P-289

P-208

P-250

1

Orifice

1.35mm

1.45mm

1.65mm

 

Dexen 10" w.c.

R-7548

R-7548

R-7548

1

Regulator

 

 

 

 

Gas Conversion

2139

2139

2139

1

Label

 

 

 

 

Gas input for "B-Vent" fireplace converted to Liquefied Petroleum Gas:

BVD34FP3 SERIES

21,000 BTU per hour

BVD36FP3 SERIES

25,000 BTU per hour

BVP42FP3 SERIES

30,000 BTU per hour

The "B-Vent" fireplace when converted to LP Gas will have manifold pressure of 10.0" w.c. at the valve outlet with the inlet pressure to the valve from a minimum of 10.8" w.c., for the purpose of input adjustment, to a maximum of 14.0" w.c.

INSTRUCTIONS FOR CONVERSION

T O L"B-VENT" FIREPLACES IModel P

Conversion Kit Model(Part Number)BVD34FP3 SERIESIN

BVCK34P (19160)V E

NT

CHECK SAFETY SHUTDOWN PERFORMANCE

WARNING

Perform the safety shutdown test any time work is done on a gas system to avoid the possibility of fire or explosion with property damage, personal injury or loss of life.

SAFETY SHUTDOWN SYSTEM

Continuous Ignition Systems

1.Place gas control knob in Pilot position. Main burner should go off and pilot should remain lit.

2.Extinguish pilot flame. Pilot gas flow should stop within 3 minutes. Safety shutoff of pilot gas proves complete shutdown since safety shutoff valve blocks flow of gas to main burner and pilot.

3.Wait 5 minutes, then relight pilot burner and operate system through one complete cycle to make sure all controls operate properly.

1.If the fireplace is installed, turn off gas and electric supply before making the gas conversion.

2.Identify the fireplace model to be converted, and read all instruction steps prior to converting the gas valve.

3.Remove all logs from the burner assembly.

4.Open the sliding valve access door.

5.Depress and turn the gas cock dial to the "OFF" position.

VALVE CONVERSION

6.Remove two (2) screws, regulator, and gasket from gas valve control body.

7.Install the new gasket, regulator, and gasket from gas valve control body.

BURNER ORIFICE CONVERSION - Tube style burners

8a. On models BVD(34,36)FP3 series fireplaces, you will have a U-shaped burner tube. To gain access to the main orifice, simply bend over the small retainer tab located at the front right end of the tube using pliers.

9a. Remove the 1/4" long screw from the air shutter at the left end of the tube.

10a. Pull up on the back of the burner and rotate forward to gain access to the main orifice. Remove the orifice and replace with the LP orifice designated in the orifice reference chart. Secure the new orifice.

11a. Pivot the burner tube back down in its original position mating with the air shutter, and reinstall the 1/4" long screw. Set the air shutter opening in accordance with the dimension shown in the reference chart for the appropriate model fireplace.

19400-3-0406

Page 21

Image 21
Contents B-VENT GAS FIREPLACE The Keystone B Vent Zero Clearance Gas FireplaceEFFECTIVE DATE APRIL Section TABLE OF CONTENTSIMPORTANT SAFETY INFORMATION That’s your signal to go into immediate action SAFETY INFORMATION FOR USERS OF LP GASLP-GASWARNING ODOR NO ODOR DETECTED - ODOR FADEInstructions to Installer INTRODUCTIONQualified Installing Agency Appliance CertificationFIREPLACE DIMENSIONS SPECIFICATIONSDim BVD34 BVD36LOCATING FIREPLACE CLEARANCESMantel Chart Figure Figure Combustible MaterialInstalling a New Main Gas Cock GAS SUPPLYChecking Manifold Pressures GAS SUPPLY CONTInstall the Fresh Air Kit - BVA1 INSTALLATIONFraming and Finishing Figure Vent Pipe ClearanceINSTALLATION CONT Combustible Surround InstallationFinishing Figure General Maintenance VENTINGInstalling the Vent System in a Chase Vent RunsVent Size VENTING CONTNever downsize venting diameters Clearances Vent ConfigurationEMBER MATERIAL PLACEMENT ON BURNER LOG PLACEMENT 5 LOG SETEMBER PLACEMENT LOG PLACEMENT 3 LOG SETBOTTOM LOG LOCATOR PINS TOP BRANCH REAR LOG BOTTOM LOGGAS CONTROL KNOB SHOWN IN OFF POSITION OPERATING INSTRUCTIONS750 Millivolt System Initial LightingWall Switch, FWS-1optional OPERATING INSTRUCTIONS CONTFRBC Battery Operated Remote Control Electric 120 volt Operated Remote Control, FRECSTANDING PILOT WIRING DIAGRAM STANDING PILOT LIGHTING INSTRUCTIONS FOR YOUR SAFETY, READ BEFORE LIGHTINGLIGHTING INSTRUCTIONS TO TURN OFF GAS TO FIREPLACESTANDING PILOT TROUBLESHOOTING 4.Frequent pilot outage problem6.Glass Sooting CHECK SAFETY SHUTDOWN PERFORMANCE STANDING PILOT PROPANE/LP GAS CONVERSIONSAFETY SHUTDOWN SYSTEM B-VENTFIREPLACESPILOT ORIFICE CONVERSION OPTIONAL REMOTE CONTROL 120V DIRECT IGNITION DIRECT IGNITION WIRING DIAGRAMDIRECT IGNITION LIGHTING INSTRUCTIONS FOR YOUR SAFETY READ BEFORE LIGHTINGLIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCEDIRECT IGNITION PROPANE/LP GAS CONVERSION DIRECT IGNITION TROUBLESHOOTINGDIRECT IGNITION PROPANE/LP GAS CONVERSION Maxitrol Valve ConversionVALVE CONVERSION Clean Burner and Control Compartment MAINTENANCE AND SERVICECleaning Procedure Glass Cleaning Optional KitsBVD34 & BVD36 PARTS LIST BVD34 & BVD36 PARTS VIEW 19400-3-0406Page BVP42 PARTS LIST BVP42 PARTS VIEW 19400-3-0406Page FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION JUNCTION BOX FAN BLACK FAN SWITCH WHITE GROUND FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATIONBLOWER ASSEMBLY 110 VOLT ACJUNCTION BOX WIRING INSTALLATION INSTRUCTIONS STANDARD MILLIVOLT VALVE MODELS120V DIRECT IGNITION VALVE MODELS OPTIONAL ACCESSORIES Page DECORATIVE ACCESSORIES19400-0-1005 Decorative Louver MissionSERVICE NOTES HOW TO ORDER REPAIR PARTS SERVICE NOTES Page19400-3-0406 SERVICE NOTES 19400-3-0406Page Empire Comfort Systems, Inc Page19400-3-0406