STANDING PILOT TROUBLESHOOTING

STANDING PILOT TROUBLESHOOTING

With proper installation and maintenance, your new Gas Fireplace will provide years of trouble-free service. If you do experi- ence a problem, refer to the Trouble Shooting Guide below. This guide will assist a qualified service person in the diagnosis of problems and the corrective action to be taken.

1.Spark ignitor will not light pilot after repeated triggering of piezo ignitor button.

a.Defective ignitor (no spark electrode)

—Check for spark at electrode and pilot; if no spark and electrode wire is properly connected, replace ignitor.

b.No gas or low gas pressure.

—Check remote shut off valves from fireplace. Usually there is a valve near the main. There can be more than one

(1) valve between the fireplace and main.

—Low pressure can be caused by a variety of situations such as a bent line, too narrow diameter of pipe, or low line pressure. Consult with plumber or gas supplier.

c.No LP in tank.

—Check LP (propane) tank. Refill tank.

2.Pilot will not stay lit after carefully following lighting instructions.

a.Defective thermopile.

—Check that pilot flame impinges on thermopile. Clean and/or adjust pilot for maximum flame impingement. —Ensure the thermopile connections at the gas valve are fully tight.

3.Pilot burning, no gas to burner, valve knob “ON.”

a.Wall switch, remote control or wires defective.

—Check wires for proper connections. Place jumper wires across terminal at switch. If burner comes on, replace defective switch. If OK, place jumper wires across switch wires at gas valve-if burner comes on, wires are faulty or connections are bad.

b.Thermopile may not be generating sufficient millivolts. —If the pilot flame is not close enough physically to the thermopile, adjust the pilot flame.

—Be sure the wire connections from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket.

—Check the thermopile with a millivolt meter. Take the reading at TH-TP & TP terminals of the gas valve. The meter should read 350 millivolts minimum, while holding the valve knob depressed in the PILOT position, with the pilot lit, and the switch in the OFF position. Replace the faulty thermopile if the reading is below the specified minimum.

—With the pilot in the ON position, disconnect the thermopile leads from the valve. Take a reading at the thermopile leads. The reading should be 350 millivolts minimum. Replace the thermopile if the reading is below the minimum.

c.Defective valve.

—Turn valve knob to ON. Place Remote/Off/On switch to ON. Check with millivolt meter at thermopile terminals. Millivolt meter should read greater than 200 millivolts. If the reading is okay and the main burner does not ignite, replace the gas valve.

d.Plugged main burner orifice.

—Check main burner orifice for blockage and remove.

4.Frequent pilot outage problem.

a.Pilot flame may be too high or too low, or blowing (high), causing pilot safety to drop out.

—Clean and adjust flame for maximum flame impingement on the thermocouple. Follow lighting instructions carefully.

5.The pilot and main burner extinguish while in operation.

a.No LP (Propane) in tank.

Check LP (Propane) tank. Refill fuel tank.

b.Bad thermopile or thermocouple. —Replace if necessary.

c.Improper vent cap installation.

—Check for proper installation and freedom from debris or blockage.

6.(Glass) Sooting

a.Flame impingement on logs.

—Check and adjust log position. Contact Empire Comfort Systems, Inc.

b.Debris around throat of main burner.

—Inspect the opening at the base of the main burner. It is imperative that NO material be placed in this opening.

Page 20

19400-3-0406

Image 20
Contents EFFECTIVE DATE APRIL B-VENT GAS FIREPLACEThe Keystone B Vent Zero Clearance Gas Fireplace TABLE OF CONTENTS SectionIMPORTANT SAFETY INFORMATION SAFETY INFORMATION FOR USERS OF LP GAS That’s your signal to go into immediate actionLP-GASWARNING ODOR NO ODOR DETECTED - ODOR FADEINTRODUCTION Instructions to InstallerQualified Installing Agency Appliance CertificationSPECIFICATIONS FIREPLACE DIMENSIONSDim BVD34 BVD36CLEARANCES LOCATING FIREPLACEMantel Chart Figure Figure Combustible MaterialGAS SUPPLY Installing a New Main Gas CockGAS SUPPLY CONT Checking Manifold PressuresINSTALLATION Install the Fresh Air Kit - BVA1Framing and Finishing Figure Vent Pipe ClearanceFinishing Figure INSTALLATION CONTCombustible Surround Installation VENTING General MaintenanceInstalling the Vent System in a Chase Vent RunsVENTING CONT Vent SizeNever downsize venting diameters Clearances Vent ConfigurationLOG PLACEMENT 5 LOG SET EMBER MATERIAL PLACEMENT ON BURNERLOG PLACEMENT 3 LOG SET EMBER PLACEMENTBOTTOM LOG LOCATOR PINS TOP BRANCH REAR LOG BOTTOM LOGOPERATING INSTRUCTIONS GAS CONTROL KNOB SHOWN IN OFF POSITION750 Millivolt System Initial LightingOPERATING INSTRUCTIONS CONT Wall Switch, FWS-1optionalFRBC Battery Operated Remote Control Electric 120 volt Operated Remote Control, FRECSTANDING PILOT WIRING DIAGRAM FOR YOUR SAFETY, READ BEFORE LIGHTING STANDING PILOT LIGHTING INSTRUCTIONSLIGHTING INSTRUCTIONS TO TURN OFF GAS TO FIREPLACE6.Glass Sooting STANDING PILOT TROUBLESHOOTING4.Frequent pilot outage problem STANDING PILOT PROPANE/LP GAS CONVERSION CHECK SAFETY SHUTDOWN PERFORMANCESAFETY SHUTDOWN SYSTEM B-VENTFIREPLACESPILOT ORIFICE CONVERSION DIRECT IGNITION WIRING DIAGRAM OPTIONAL REMOTE CONTROL 120V DIRECT IGNITIONFOR YOUR SAFETY READ BEFORE LIGHTING DIRECT IGNITION LIGHTING INSTRUCTIONSLIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCEDIRECT IGNITION TROUBLESHOOTING DIRECT IGNITION PROPANE/LP GAS CONVERSIONVALVE CONVERSION DIRECT IGNITION PROPANE/LP GAS CONVERSIONMaxitrol Valve Conversion MAINTENANCE AND SERVICE Clean Burner and Control CompartmentCleaning Procedure Glass Cleaning Optional KitsBVD34 & BVD36 PARTS LIST Page BVD34 & BVD36 PARTS VIEW19400-3-0406 BVP42 PARTS LIST Page BVP42 PARTS VIEW19400-3-0406 FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION JUNCTION BOX FAN BLACK FAN SWITCH WHITE GROUNDBLOWER ASSEMBLY 110 VOLT AC120V DIRECT IGNITION VALVE MODELS JUNCTION BOX WIRING INSTALLATION INSTRUCTIONSSTANDARD MILLIVOLT VALVE MODELS OPTIONAL ACCESSORIES DECORATIVE ACCESSORIES Page19400-0-1005 Decorative Louver MissionSERVICE NOTES HOW TO ORDER REPAIR PARTS 19400-3-0406 SERVICE NOTESPage Page SERVICE NOTES19400-3-0406 19400-3-0406 Empire Comfort Systems, IncPage