Vulcan-Hart BVP42FP32(F,L)N-1, BVP42FP52(F,L)N-1 Gas Supply, Installing a New Main Gas Cock

Page 8
GAS SUPPLY

GAS SUPPLY

The gas pipeline can be brought in through the right or left side of the appliance. Consult the current National Fuel Gas Code, ANSI Z223.1 CAN/CGA-B149 (.1 or .2) installation code.

Recommended Gas Pipe Diameter

Pipe Length

Schedule 40 Pipe

Tubing, Type L

(Feet)

Inside Diameter

Outside Diameter

 

 

 

 

 

 

Nat.

L.P.

Nat.

L.P.

 

 

 

 

 

0-10

1/2"

3/8"

1/2"

3/8"

 

12.7mm

9.5mm

12.7mm

9.5mm

 

 

 

 

 

11-40

1/2"

1/2"

5/8"

1/2"

 

12.7mm

12.7mm

15.9mm

12.7mm

 

 

 

 

 

41-100

1/2"

1/2"

3/4"

1/2"

 

12.7mm

12.7mm

19mm

12.7mm

 

 

 

 

 

101-150

3/4"

1/2"

7/8"

3/4"

 

19mm

12.7mm

22.2mm

1.9 mm

 

 

 

 

 

Note: Never use plastic pipe. Check to confirm whether your local codes allow copper tubing or galvanized.

Note: Since some municipalities have additional local codes, it is always best to consult your local authority and installation code.

The use of the following gas connectors is recommended:

ANS Z21.24 Appliance Connectors of Corrugated Metal Tubing and Fittings.

ANS Z21.45 Assembled Flexible Appliance Connectors of Other Than All-Metal Construction

The above connectors may be used if acceptable by the authority having jurisdiction. The state of Massachusetts requires that a flexible appliance connector cannot exceed three feet in length.

 

 

Figure 6

 

Gas Supply Pressure (inches w.c.)

 

Minimum

Normal

Maximum

Natural Gas

4.5"

7.0"

14.0"

LP (Propane)

10.8"

11.0"

14.0"

 

Manifold Pressure (inches w.c.)

 

 

Normal (HI)

 

Natural Gas

 

3.5"

 

LP (Propane)

 

10.0"

 

Installing a New Main Gas Cock

Each appliance should have its own manual gas cock.

A manual main gas cock should be located in the vicinity of the unit. Where none exists, or where its size or location is not adequate, contact your local authorized installer for installation or relocation.

Compounds used on threaded joints of gas piping shall be resistant to the action of liquefied petroleum gases. The gas lines must be checked for leaks by the installer. This should be done with a soap solution watching for bubbles on all exposed connections, and if unexposed, a pressure test should be made.

Never use an exposed flame to check for leaks. Appliance must be disconnected from piping at inlet of control valve and pipe capped or plugged for pressure test. Never pressure test with appliance connected; control valve will sustain damage!

NOTE: The millivolt gas controls are equipped with a captured screw type pressure test point, therefore it is not necessary to provide a 1/8" test point up stream of the control.

Ondirectignitionvalves,hexplugsmaybereplacedwithhosefittings for pressure checks, then reinstalled before operating fireplace.

When using copper or flex connector use only approved fittings.

The appliance and it’s individual shut off valve must be disconnected from supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5kPa).

The appliance must be isolated from the gas supply piping system by closing its individual manual shut off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5kPa).

Attention! If one of the procedures results in pressures in excess of 1/2 psig (14" w.c.) (3.5 kPa) on the fireplace gas valve, it will result in a hazardous condition.

Page 8

19400-3-0406

Image 8
Contents EFFECTIVE DATE APRIL B-VENT GAS FIREPLACEThe Keystone B Vent Zero Clearance Gas Fireplace TABLE OF CONTENTS SectionIMPORTANT SAFETY INFORMATION SAFETY INFORMATION FOR USERS OF LP GAS That’s your signal to go into immediate actionLP-GASWARNING ODOR NO ODOR DETECTED - ODOR FADEINTRODUCTION Instructions to InstallerQualified Installing Agency Appliance CertificationSPECIFICATIONS FIREPLACE DIMENSIONSDim BVD34 BVD36CLEARANCES LOCATING FIREPLACEMantel Chart Figure Figure Combustible MaterialGAS SUPPLY Installing a New Main Gas CockGAS SUPPLY CONT Checking Manifold PressuresINSTALLATION Install the Fresh Air Kit - BVA1Framing and Finishing Figure Vent Pipe ClearanceFinishing Figure INSTALLATION CONTCombustible Surround Installation VENTING General MaintenanceInstalling the Vent System in a Chase Vent RunsVENTING CONT Vent SizeNever downsize venting diameters Clearances Vent ConfigurationLOG PLACEMENT 5 LOG SET EMBER MATERIAL PLACEMENT ON BURNERLOG PLACEMENT 3 LOG SET EMBER PLACEMENTBOTTOM LOG LOCATOR PINS TOP BRANCH REAR LOG BOTTOM LOGOPERATING INSTRUCTIONS GAS CONTROL KNOB SHOWN IN OFF POSITION750 Millivolt System Initial LightingOPERATING INSTRUCTIONS CONT Wall Switch, FWS-1optionalFRBC Battery Operated Remote Control Electric 120 volt Operated Remote Control, FRECSTANDING PILOT WIRING DIAGRAM FOR YOUR SAFETY, READ BEFORE LIGHTING STANDING PILOT LIGHTING INSTRUCTIONSLIGHTING INSTRUCTIONS TO TURN OFF GAS TO FIREPLACE6.Glass Sooting STANDING PILOT TROUBLESHOOTING4.Frequent pilot outage problem STANDING PILOT PROPANE/LP GAS CONVERSION CHECK SAFETY SHUTDOWN PERFORMANCESAFETY SHUTDOWN SYSTEM B-VENTFIREPLACESPILOT ORIFICE CONVERSION DIRECT IGNITION WIRING DIAGRAM OPTIONAL REMOTE CONTROL 120V DIRECT IGNITIONFOR YOUR SAFETY READ BEFORE LIGHTING DIRECT IGNITION LIGHTING INSTRUCTIONSLIGHTING INSTRUCTIONS TO TURN OFF GAS TO APPLIANCEDIRECT IGNITION TROUBLESHOOTING DIRECT IGNITION PROPANE/LP GAS CONVERSIONVALVE CONVERSION DIRECT IGNITION PROPANE/LP GAS CONVERSIONMaxitrol Valve Conversion MAINTENANCE AND SERVICE Clean Burner and Control CompartmentCleaning Procedure Glass Cleaning Optional KitsBVD34 & BVD36 PARTS LIST Page BVD34 & BVD36 PARTS VIEW19400-3-0406 BVP42 PARTS LIST Page BVP42 PARTS VIEW19400-3-0406 FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION FBB4 OPTIONAL VARIABLE SPEED BLOWER INSTALLATION JUNCTION BOX FAN BLACK FAN SWITCH WHITE GROUNDBLOWER ASSEMBLY 110 VOLT AC120V DIRECT IGNITION VALVE MODELS JUNCTION BOX WIRING INSTALLATION INSTRUCTIONSSTANDARD MILLIVOLT VALVE MODELS OPTIONAL ACCESSORIES DECORATIVE ACCESSORIES Page19400-0-1005 Decorative Louver MissionSERVICE NOTES HOW TO ORDER REPAIR PARTS 19400-3-0406 SERVICE NOTESPage Page SERVICE NOTES19400-3-0406 19400-3-0406 Empire Comfort Systems, IncPage